| 1 | Dismantling of ACSR or AAC conductor complete all as specified and directed. |
| 2 | Dismantling cross arms of MS channel or angle sections etc complete and setting for re-use or takingto schedule of creditcomplete all as specified and directed. |
| 3 | Dismantling insulators any type any size complete all as specified and directed. |
| 4 | M&L for dismantling concrete poles/ struts, any size complete all as specified and directed. |
| 5 | Supply, laying and testing XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 3.5 core 50 sq mm incl taking out/ down old u/s existing cable. complete all as specifiedand directed by Engr-in-Charge. |
| 6 | Supply, laying and testing XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 4 core 16 sq mm incl taking out/ down old u/s existing cable complete all as specifiedand directed by Engr-in-Charge. |
| 7 | Supply, laying and testing XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 3.5 core 35 sq mm complete all as specifiedand directed by Engr-in-Charge. Note for item No.5 to 7.1.The rate quoted by the contractor deemed to be inclusive of suitable size aluminium lugs at any required length at both ends of cable.2.Suitable size of cable chromium plated stainless steel grands etc. as specifiedand directed by Engr-in-Charge. |
| 8 | M&L for Wiring with 1.5 sq mm 2runs of single core multistrandPVC insulated, unsheathed cable conforming to IS - 694, 1100 volts with copper conductor etc as required and connecting toboardto fitting as specifiedand directed by Engr-in-Charge. |
| 9 | M & L Earthing complete for sub station equipments with galvanized steel earth pole electrod of size 600x600x6.3mm thick burried directly in the ground (earth pit not less than 2.25 metre deep below normal ground level) with top edge ofplate not less than 1.5 metre below the ground level, connected to galvanised iron strip 25 x 4 mm by means of nuts, bolts,check nuts and washers of galvanised or steel all as specified or shown in electrical plate No. 3 of SSR-2009( Part-l), including ncessary earth work and excavation in any strata, GI pipe 40mm dia light grade for protection of galvanised iron earthing strip upto 7.5 mtrs,including concrete chamber of PCC (1:4:8) type D-2 (using 40mm graded stone aggregate) having copping in PCC (1:3:6) Type C-1using 20mm graded stonr aggregate. Intemal surface of concrete chamber shall be plasteredwith 12mm thickcement mortar (1;4) and 50mm thick RCC cover in proportion (1:2:4) type B-1using 20mm gradedstone aggregate, reinforced with 8mm dia tor bar@ 80mm c/c both ways and charcoale dust common salt etc.,funneltesting point, 8 mesh per liner inch, including test point , testing, incl taking out old u/s earthing materials complete all as specified and directed. |
| 10 | Supply and fixing steel tubular pole, swaged, complete with cast iron base plate, finial taper plug, bolts, nuts, washer and screws including painting with two coats of aluminium paint over one coat of red oxide primer on all exposed surfaces and tarring with black bituminous paints to portion embedded in PCC including numbering of poles with two coats of synthetic enamel paints, type 410-SP-31 (9 meter long) complete all as specified and directed . |
| 11 | S&F in replacementLED Ornamental aluminium casted bollard LED light 18 Watt with Presure die cast IP-65 lite fitting PC cover , PU painted power LED light complete all as specified and as directed. |
| 12 | Supply and fixing in replacement LED street light fittings 70 watts 230 V AC outdoor type with high pressure die cast aluminium housing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including therma; management in multiple optics complete with IP 65/66 protection complete with provision of twin corecopper wire 23/0.0076 upto security light from pole loop box,including street light brackets made out of GI tubing light grade, 40 mm bore 1200 mm long bent to sahpe at 120 degree, fixed on pole by providing MS clamp made up to flat iron 50 x 6 mm including nuts and washer of suitable size, fixed in repairs complete all as specifiedand directed by Engr-in-Charge.Cat No. ENDURACITYLINERNEOSL70WLED757PASYBOTG of Make : Havells or equivalent in Make/Brands as per approved list in Tender Documents. |
| 13 | S&F pole box for street lightdust and vermin proof with hinged door and locking arrangement make Sintex model GSJB 3020 complete with 4 way connector 2 Nos. of capacity 60 ampsincl one MCB SP C series 06 amps 10 KA capacityfor Security light connection with flexIble wire 3 core 2.5 sqmmwith suitable size of PVC conduit and including suitable clamps & suitable size brass chrome plated glands-02 nos at bottom for cable entry and exit complete all as specified and as directed. |
| 14 | M&L of9 mtr high hot dip galvanised octagonal pole with 155 mm bottom A/Fand 70mm top A/F made up of 3 mm thk. HT sheet alongwith base plate of size 250x250x12 mm thickness PCD -200mm and 4 nos of M24X750mm long J type EN 8 grade foundation bolts along with template including1.5 meter long hot dip galvanised single arm bracket made up of 40nb dia GI pipe suitable to mount on pole having top 70mmA/F, complete all as specified and directed. Note : Excavation and PCC will be measured and paid separately under respective items. |
| 15 | M&L of9 mtr high hot dip galvanised octagonal pole with 155 mm bottom A/Fand 70mm top A/F made up of 3 mm thk. HT sheet alongwith base plate of size 250x250x12 mmthickness PCD -200mm and 4 nos of M24X750mm long J type EN 8 grade foundation bolts along with template including1.5 meter long hot dip galvanised double arm bracket made up of 40nb dia GI pipe suitable to mount on pole having top 70mmA/F, complete all as specified and directed.Note : Excavation and PCC will be measured and paid separately under respective items. |
| 16 | M&L for Cutting existing road surfaces or hard standing 0.45 mtr depth and 0.3 mtr width (22 CM thick comprising bituminous topping) for laying of pipes/cables and making good to the disturbed surfaces to match with existing complete all as specified and directed. Note : Rate quoted by the contractor deemed to be inclusive of PCC 1:2:4 to be required to making good the disturbed surface to match with existing complete all as specified and directed. |
| 17 | Supply and fixingof GI tubing, light grade, 50 mm bore with all fitting lais in trenches / pole / wall for protection of cables in repairs complete all as specified and directed. |
| 18 | Excavation in trenches in soft/ loosesoil and not exc 1.5 m wide and n.exc 1.5 m in depth for laying of cable /fixing poles, stays etc and getting out complete all as specified and directed |
| 19 | Returning, filling in excavated approved soil, including spreading, leveling, watering and well ramming in layers not exceeding 25cm each complete all as specified and directed |
| 20 | Removing excavated material (surplus soil) to a distance not exceeding 50 mtrs and depositing where directed at a level not exc 1.5 m above the starting point complete all as specified and directed. |
| 21 | M&L for sand cushning to U/G cable in layers of 23cm thick (8 cm before laying the cable and 15 cm thick after laying the cable) in trenches including watering and consolidation, complete all as specified and directed. Note : Compacted Thickness shall be 18 cm considered for measurement and payment purpose. |
| 22 | M&L for bricksslightly over burnt (kiln burnt), modularbricks , best quality, locally available , laid flat, dry, laid in trenches along the length of cable transvarsally with width equal to length of brickfor cable protection complete all as specified and as directed. |
| 23 | M & L for Horizontal drilling hole at a depth upto 1 mtr below the normal ground level of suitable size to insert pipe upto 40-100mm dia across the road across the horizontal position at different location complete all as specified and as directed. |
| 24 | M&L for PCC 1:4:8, type D2 (using 40 mm graded crushed stone aggregate) as in base the pole, complete all as specified and directed. |
| 25 | M&L forPCC 1:3:6, type C2 (using 40 mm graded crushed stone aggregate) as in foundation for poles with formworkcomplete all as directed and as specified. |
| 26 | M&L for PCC 1:2:4, type B1 (using 20 mm graded crushed stone aggregate) as in base,coping of the pole, complete all as specified and directed. |
| 27 | Net Contract Sum will be after deducting Sch of Credit of Rs91,624.00 |