| 1 | M&L for taking down desert cooler of any type/size/model from any height / floor for servicing like changing of wood wool pads, kit motor, submersible pump, fan blade, front grill, wiring, capacitor, cleaning or any other repair work as specified and re-fixing to existing place after repair work/overhauling complete all as specified and directed.Note :- (i) The rates quoted by the contractor shall deemed to include the cost of taking down and fixing charge of \"Supply only\" items.(ii)The spare parts required to be replaced shall be measured and paid separately under relevant items as \"Supply only\". |
| 2 | Supply only wood wool padof suitable size for 24” sweep desert cooler complete all as specified and directed 01 Set comprising of 3 Nos of pads approximate weight 800-900 Gms.(As per sample.) |
| 3 | All as per item No 2 above but 20” sweep approximate weight 700 -800 Gms. As per sample. |
| 4 | Supply only of submersible pump motor 230 Volts, single phase, AC suitable for Plastic/Steel body Desert cooler complete all as specified & as directed. Note for item Nos 2 to 4 :- Materials of item Nos 2 to 4 to be incorporated in item No 1 here-in-before |
| 5 | Supply and fixing in repairs ofdesert cooler kit fan motor, single speed, 230 V, 50 Hz of capacity 90 Watt 1450 RPM, copper wounded including nuts bolts for fixing complete all as specified and directed. |
| 6 | Supply and fixing in repairs Desert cooler exhaust fan motor, single speed, 230 V, 50 Hz of capacity 150 Watt 1400 RPM, copper wounded including nuts bolts for fixing complete all as specified and directed. |
| 7 | Supply only front grill for desert cooler of approved make suitable for fixing 5 Amp switch, three speed regulator and indicating lamp all as specified and directed (As per Sample). |
| 8 | Supply only running capacitor of 4 MFD capacity complete all as specified and as directed. |
| 9 | Supply only running capacitor of 6 MFD capacity complete all as specified and as directed. |
| 10 | Supply only wire mesh for desert cooler pad (Set of Three) including taking down old one. |
| 11 | Supply only PVC pipe for connecting pump and water distributor of size 15 mm dia including PVC elbows. |
| 12 | Supply only PVC elbow for desert cooler. As per sample |
| 13 | Supply only PVC 4 Way distribution cross for desert cooler. As per sampleNote for item Nos 7 to 13 :- Materials of item Nos 7 to 13 to be incorporated in item No 1 here-in-before |
| 14 | Supply and fixing flexible copper conductor cable, 3 corePVC insulated & PVC sheathed of size 1.5sqmm including taking down old unserviceable one complete all as specified and as directed. |
| 15 | Supply and fixing in repairs desert coolers fan blade of 18\" (inch) sweep make out of Aluminum complete all as specified and as directed. |
| 16 | Supply and fixing in repairs desert coolers fan blade of 20\" (inch) sweep make out of Aluminum complete all as specified and as directed. |
| 17 | Supply and fixing in repairs side panel of desert cooler of 20” sweep made out with GI sheet of 20 SWG duly painted with two coats of synthetic enamel paint (1st grade quality) over a coat of red oxide zinc chrome primer complete all as specified & as directed. |
| 18 | Supply and fixing in repairs switch piano flush type single pole one way 5Amp / 6 Amp 230 V for desert cooler complete all as specified and as directed. |
| 19 | Supply and fixing in repairs 3 pin plug top 5 Amp, 230V for desert cooler complete all as specified and as directed. |
| 20 | Supply and fixing in repairs 3 pin plug top 15 Amp, 230V for desert cooler complete all as specified and as directed. |
| 21 | Supply and fixing in repairs cooler fan motor bracket sets made up as existing includingpainting complete all as specified and directed. |
| 22 | Preparation for old painted surface of desert cooler of any capacity and any make on inner surface & outer surface.Repainting the complete desert coolers ie side panel, bracket, body & desert cooler stand with two coats of synthetic enameled paint (1st grade quality) including two coats of black water proof paint on reserve water tank & marking with “AGE(I) HIGHGROUND (MES)” letter size of 50mm height at stencil in black/white including servicingandgreasing of fan motor/pump and replacement of PVC pipe worn out nut, bolts and washers as per site requirement complete all as specified and as directed |
| 23 | S&F in repairs desert cooler body of size 25 inch x 25 inch x 36 inch (height) with side panels (03 Nos) fabricated out of 20 SWG PGI Sheet alongwith PVC front grill, distribution switch, 5 Amp piano switch and tank of depth 11 inch. Painting the complete desert cooler i.e, side panel, bracket body with two coat of synthetic enamel paint (Ist grade quality) over a coat of red oxide zinc chrome primer and two coat of black water proof paint on reserve tank and marking with \"AGE(I) HIGHGROUND (MES)\" letter size of 50mm height complete all as specified and as directed. |
| 24 | Taking downfor servicingof split type AC 1.5/2/3 TR Capacityincluding cleaning of cooling coil, air filters/plasma filters etc, (Indoor unit), condenser, compressors, fan motor etc,(Out door unit) with vacuum cleaner OR cleaning solution including checkingthe serviceability of electrical/electronic circuits relays, wiring kit, thermostat switches knobs, remote control unit including PCB, fan, blower, etc., changing connections from heating mode to cooling mode or vice-versa and keeping the AC unit in satisfactory working condition after necessary servicing/ repair/ replacement of defective spares as required and refixing the same in existing position complete all specified and as directed by Engineer-in-Charge. Note : Indoor unit drainage system should be cleaned properly during servicing to avoid any water leakage, if found will be repaired/cleaned properly without any extra cost to department. |
| 25 | Taking downfor servicingofWindow type AC 1.5/2 TR Capacityincluding cleaning of cooling coil, air filters , condenser, compressors, fan motor etc with vacuum cleaner or cleaning solution includingcheckingthe serviceability of electrical/electronic circuits relays, wiring kit, thermostat switches knobs, remote control unit including PCB, fan, blower, etc, changing connections from heating mode to cooling mode or vice-versa andkeepingthe AC unit in satisfactory working condition after necessary servicing/ repair/ replacement of defective spares as required and refixing the same in existing positioncomplete all specified and as directed by Engineer-in-Charge.Notes for Ser Item No 24 & 25 :- (i) Replacement of defectivespares for making the AC units in satisfactory working conditionwill be measured & paidseparately under relevant items and Labour charges for taking out old spares & refixing of new sparesshall deemed to be included in unit quoted rate. (ii) Penaltywill be charged for not attending complaint from 12 Hoursto 24 hours Rs. 500/- each complaint. Furtherif complaint not attended and rectifiedwithin 24 hours after intimation (Intimation will be given by message/whats app/mail by mentioningtime of complaint,for that contractor has to submit his authorised reps details for receiving complaint) of complaint, failing which same will be got rectified through spot quotation by job order by any other agency and double of the job order amount to be deducted from contractors dues. |
| 26 | Supply only Running capacitor 36+6 MFD. |
| 27 | Supply only Running capacitor 45+5 MFD. |
| 28 | Supply only Running capacitor 50+6 MFD. |
| 29 | Supply only Starting capacitor 80-100 MFD. |
| 30 | Supply only Starting capacitor 100-120 MFD. |
| 31 | Supply only Starting Relay 1622 or equivalent. |
| 32 | Supply only Starting Relay 2000 or equivalent |
| 33 | Supply only Overload Relay suitable for any type / capacity of ac. |
| 34 | Supply only Thermostat switch 2059/2064/2054 or equivalent. |
| 35 | Supply only Condenser fan blade for Window type A.C of Capacity 1.5/2/3 TR made of Plastic. |
| 36 | Supply only Condenser fan blade for spilt Type A.C of Capacity 1.5/2/3 TR made of Plastic. |
| 37 | Supply only Wiring kit for Window/split type AC of Capacity 1.5/2 TR |
| 38 | Supply only Remote control compatible for split or window type AC of Cap 1.5/2/3 TR of any make and model as per site requirement as directed by Engr-in-Charge. |
| 39 | Supply only main printed circuit board (PCB) with connected accessories and sensors suitable for split or window type AC of capacity 1.5/2/3 TR as directed by Engr-in-Charge. |
| 40 | Supply only main printed circuit board (PCB) inverter type with connected accessories and sensors (complete for indoor and outdoor unit) suitable for inverter type AC of capacity 1.5/2/3 TR complete all as specified and as directed. Note for item Nos 26 to 40:- Materials of item Nos 26 to 40 to be incorporated in item No 24 & 25 here-in-before. |
| 41 | Supply & fixing in repairs plastic louvers for (Front panel) for window AC 1.5/2 TR complete all as directed by Engr-in-Charge. |
| 42 | Supply & fixing in repairs of suctionand discharge valve set of size 15mm (5/8\"\"), 6mm (1/4\"\") and 12mm (1/2\"\")for Split AC 1.5/2/3 TR capacity complete all as directed by Engr-in-Charge. {Note:-(i) 15mm (5/8\"\") or 6mm (1/4\"\") and 12mm (1/2\"\") made one set(ii) Supply & filling of refrigerant gas shall be measured and paid under relevent item.} |
| 43 | Supply & fixing in repairs of capillary tube for Split/ Window type AC of capacity 1.5/2/3 TR complete all as directed by Engr-in-Charge. |
| 44 | Supply & fixing in repairs of capillary filter for Split/ Windowtype AC of capacity 1.5/2 TR complete all as directed by Engr-in-Charge. |
| 45 | Disconnecting the unserviceable PCB compatible from existing Window/ Split type AC of capacity 1.5/2/3 TR and refixing after necessary repair for satisfactory functioning of the AC unit complete allas specified and directed by Engineer-in-charge. |
| 46 | Taking down unserviceable reversible valve for split/ window type AC of capacity 1.5TR and supply & fixing new reversible valve with solenoid coil including required copper pipe complete all as specified and directed by Engr-in-charge. (Note:- Supply & filling of refrigerant gasshall be measured and paid under relevent item.) |
| 47 | -ditto- all as per item No. 46 above but spilt/window type Air Conditioner of capacity2 TR. |
| 48 | -ditto- all as per item No. 46 above but spilt/window type Air Conditioner of capacity3 TR. |
| 49 | Disconnecting from mains and taking out existing unserviceable sealed compressor unit from the window type Air Conditioner of Cap2 Ton,of any make any type from any locationandSupply , Installingand testing of new sealed unit compressoralongwith test certificate from manufacturer includingcleaning and removing dust/dirt from the cooling coil condenser coilwith necessary modification capillary tube etc & charging of refrigerent gas and commissioning complete all as specified & directed by Engg-in-Charge.Note :- Transportation Charges from siteto trade workshop and back to original location after repair shall be deemed to be included in unit rate quoted above. |
| 50 | -ditto- all as per item No. 49 abovebut window type Air Conditioner ofCapacity1.5 TR. |
| 51 | -ditto- all as per item No. 49 abovebut spilt type Air Conditioner ofCapacity 3 TR. |
| 52 | -ditto- all as per item No. 49 abovebut spilt type Air Conditioner ofCapacity 2 TR. |
| 53 | -ditto- all as per item No. 49 abovebut spilt type Air Conditioner ofCapacity 1.5 TR. |
| 54 | Supply & fixing in repairs of Window A/C air blower motor copper wounded for 1.5 TR & 2 TR capacity AC complete all as specified & as directed. |
| 55 | Supply & fixing in repair copper wounded indoor air blower motor for Split AC 1.5/2/3 TR capacity complete all as specified & as directed. |
| 56 | Supply & fixing in repairs of copper wounded condenser fan motor for Split type AC of 1.5/2/3 TR capacity outdoor units complete all as specified & as directed. |
| 57 | Disconnecting the mains and taking out the unserviceable condenser coilof window type AC of capacity 1.5/ 2TR of any make from any location and supply, fixing and testing new condenser coil as per existing size & patterns for complete all as specified & as directed. |
| 58 | -ditto- all as per item No. 57 above but spilt type Air Conditioner Capacity 1.5/2/3 TR. |
| 59 | Supply & fixing in repairs of evaporator/cooling coil for window type Air Conditioner of capacity 1.5/ 2TRof existing make and size complete all as specified & as directed by Engr-in-Charge. |
| 60 | -ditto- all as per item No. 59 above but spilt type Air Conditioner Capacity 1.5/2/3 TR. |
| 61 | Supply and fixing in repairs of1.5TR capacity split type Air Conditioner outdoor kit including condenser coil, blower motor, chasis, base plate complete set except compressor complete all as specified & as directed by Engr-in-Charge. |
| 62 | -ditto- all as per item No. 61 above but spilt type Air Conditioner of capacity2 TR. |
| 63 | Taking down unserviceable indoor unitof split type AC of any make andsupply & fixing new indoor unit complete set suitable for 1.5 TRcapacity complete all as directed by Engr-in-Charge. |
| 64 | -ditto- all as per item No. 63 above but spilt type Air Conditioner of capacity2 TR. |
| 65 | Supply & fixing heavy duty copper pipe 6 mm (1/4\") dia/ bore complete including insulation brazing, welding, nuts,bolts and screws of required size including taking down old unserviceable one complete all as specified and directed by Engr-in-Charge. |
| 66 | -ditto- all as per item No. 65 above but copper pipe 12 mm (1/2\") dia/ bore. |
| 67 | -ditto- all as per item No. 65 above but copper pipe 15mm (5/8\") dia/ bore. |
| 68 | Taking down unserviceable insulation for copper pipe, supply and fixing new insulation for copper pipes suitabale for Split AC of capacity from 1.5/ 2 / 3 TR all as specified and directed by Engineer-in-charge. |
| 69 | Taking down unserviceable PVC drain pipe and supply & fixing new PVC drain pipe 15 mm dia for Split/window AC all as specified and directed by Engineer-in-charge. |
| 70 | Supply and filling or topup refrigerant gas of any type as per site requirement (R-22/R-410A/R-32/R-134) in window/Split Type AC of capacity 1.5/2/3 TR, water cooler of capacity 40/80, 60/120, 150/150, deep freezer and refrigerator unit including detecting the leakage of gas at any location and rectifying the defect to stop the leakage by gas welding or by any other means including cutting and brazing of copper tubes testing and commissioning complete in satisfactory working condition. Note : If any defect/ leakage found after repair within three month, leakage will be rectified and filling or topup of refrigerant gas with free of cost. No extra cost will be paid to contractor for rerectification. |
| 71 | Taking down unserviceable contactor and supply and fixing new contactor single phase suitable for Split AC of capacity 1.5/2/3 TR all as specified as directed by Engineer in-charge. |
| 72 | Dismantling and removing defective burnt blower unit motor of any capacity and make of 1.5/2 TR capacity window type AC and rewinding the motor with enamel copper winding wire of existing guage and size including replacement of worn out motor bearing etc, refixing and testing all as directed. |
| 73 | Dismantling and removing defective burnt blower unit motor of any capacity and make of indoor units of split type AC of capacity 1.5/2/3 TR capacity rewinding the motor with enamel copper winding wire of existing guage and size including replacement of worn out motor bearing etc, refixing and testing all as directed. |
| 74 | Dismantling and removing defective burnt outdoor unit motor of any capacity and make of indoor units of split type AC of capacity 1.5/2/3 TR capacity rewinding the motor with enamel copper winding wire of existing guage and size including replacement of worn out motor bearing etc, refixing and testing all as directed. |
| 75 | Dismantling the existing broken blower fan blade of the indoor units of the split type AC of Capacity 1.5/2/3 TR and supply and fixing in repairs new blower fan blade complete all as specified and directed. |
| 76 | Material and labour for sub main wiring with two runs of single core 4 Sqmm (nominal area) PVC insulated copper conductor FRLS (conforming to IS-694), multistranded,unsheathed1100 volts grade in PVC casing caping(heavy grade) of adequit size with all fittings and casing capingaccessories of surface/ conceal type as per site requirement including one run 4 Sqmm single core unsheathed multistranded copper conductor cable FRLS (conforming to IS-694)as earth wire including taking down old unservisible sub main wiring complete all as specified and as directed. |
| 77 | -ditto- all as per item no 76 but 2.5 sqmm (nominal area).{Notes for item No.76 &77 :-(i) Two runs of cable with one runs earth wire and PVC conduit or casing capping with connected accessories shall be measured as one unit length. (ii) Earth wire shall run inside the casing capping. (iii) Suitable color code of wire must be ensure for phase/ neutral/ earth.} |
| 78 | Supply and fixing in repairs of metal clad socket outlet with single pole and nuetral enclosure with two pin and earth plug socket complete with one single pole MCB 20 Amps iincluding taking down old unservisible metal clad socket complete all as specified and as directed. |
| 79 | Supply and fixing in repairs of MCB SP 240 volts 6 to 32 Amps, 10 kA, \"C\" curve complete all as specified and as directed. |
| 80 | Supply & fixing in repair metal clad socket of 20 Amps complete all as specified & as directed. |
| 81 | Supply & fixing in repairs metal clad plug with two pin of capacity 20 Ampscomplete all as specified & as directed. |
| 82 | Collecting of unserviceable voltage stabilizer of capacity 1 to 5 KVA from the MES store yard or dismantlingthe same from site and transporting to contractors workshop for locating the fault including checking the serviceability of electrical/electronic circuits relays and replacement of defective spare parts, reassembling after making connections, testing by applying low and high voltage input to get the 230 volts correct output and transporting back the same to MES store yard complete all as specified and directed by Engr-in-chargeNote :- 1. Replacement of defectivespares and rewinding of transformer of voltage stabilizer will be measured & paidseparately under relevant items and Labour charges for taking out old spares & fixing of new sparesshall deemed to be included in unit rate quoted. |
| 83 | Supply only Voltmeter (Analog) 0 to 300 volts any type shape single phase 50 Hz AC supply. |
| 84 | Supply only Digitaltype Voltmeter0 to 300 volts any type shape single phase 50 Hz ACsupply. |
| 85 | Supply only Printer circuit control card suitable for 1 to 5 KVA. |
| 86 | Supply only Input/output switch. |
| 87 | Supply only Push on switch. |
| 88 | Supply only Indicator light complete with bulbs. |
| 89 | Supply only Trigger Transformer for 1 to 5 KVA. |
| 90 | Supply only Relay for 1 to 5 KVA voltage stablizer. |
| 91 | Supply only Time delay and High/low voltage cut off circuit with relay suitable for 1 KVA to 5 KVA.Note for item Nos 83 to 91 :- Materials of item Nos 83 to 91 to be incorporated in item No 82 here-in-before |
| 92 | Taking out the burnt winding of transformer of voltage stabilizer and preparing core after cleaning by suitable cleaning agent and rewinding the transformer of voltage stabilizer with super enameld copper wire of existing gauge including varnishing, heating and refiting of capacity 1 to 5 KVA voltage stabilizer, complete all as specifies & directed by Engr-in-Charge. |
| 93 | Disconnecting from mains and taking downfor servicingofWater Cooler ofCapacity 40/80, 60/120,Ltrs including cleaning of cooling coil, air filters, condenser, compressors, fan motor etc with vacuum cleaner or cleaning solution includingcheckingthe serviceability of electrical/electronic circuits relays, wiring kit, thermostat switches knobs,fan andblower, etc., andkeepingthe Water coolerunit in satisfactory working condition after necessary servicing/ repair/ replacement of defective spares as required and installation in same location complete all as specified and as directed by Engineer-in-Charge.Note :- 1. Replacement of defectivespares for making the water cooler units in satisfactory working condition will be measured & paidseparately under relevant items and Transportation & labour charges for taking down old spares and fixing of new sparesshall deemed to be included in unit rate quoted above. |
| 94 | Supply only over load protector relay suitable for 40/80, 60/120 & 150/150 Ltrs capacity water coolers. |
| 95 | Supply only thermostat suitable for 40/80, 60/120, 150/150 Ltr capacity water coolers. |
| 96 | Supply only condenser motor fan blade suitable for 40/80, 60/120, 150/150 Ltr capacity water coolers. |
| 97 | Supply only PVC flexible drain Hose Pipe 40 mm with connected accessories. |
| 98 | Supply only Waste water tray complete suitable for 40/80, 60/120, 150/150 Ltr capacity water coolers all as directed. |
| 99 | Supply only chromium plated push taps suitable for 40/80/120/150 Ltr capacity water coolers all as directed. |
| 100 | Supply only PVC float valve of size 15mm dia with all connected accessories complete suitable for 40/ 80/ 120/ 150 Ltr capacity water coolers including GI socket of same size all as directed. |
| 101 | Supply only Starting Capacitor 25 MFD. |
| 102 | Supply only running Capacitor 10 MFD. |
| 103 | Supply only Starting relaysuitable for 40/80, 60/120, 150/150 Ltr. Note for item Nos. 94 to 103 :- Materials of item Nos. 94 to 103 to be incorporated in item No 93 here-in-before |
| 104 | Preparation for old painted surface of water cooler of any capacity and any make on inner surface (excluding water storage) & outer surface. Repainting the complete water coolers with two coats of synthetic enameled paint (1st grade quality) including two coats of water proof paint & marking with “AGE(I) HIGHGROUND (MES)” letter size of 50mm height at stencil in black/white including servicingandgreasing of fan motor/ pump and replacement of PVC pipe worn out nut, bolts and washers as per site requirement complete all as specified and as directed |
| 105 | Disconnecting the electric mains and taking out unserviceable condenser fan motor 1/16 HP from water cooler cap.60/120, 150/150 Ltr and supply and replace with new motor single phase AC 220 V of same capacity including reconnecting the electric connections and testing complete all as directed by Engr-in-Charge. |
| 106 | All as per item No.105 above but 1/32 HP Water coolerofCapacity 40/80 Ltrs. |
| 107 | Dismantling and removing defective compressor and supply and fixing (in repairs) new sealed compressor of approved make obtained from authorised dealers submitting Warranty certificate & test certificates from manufacturer/authorised dealers including charging of refrigerent gas, commissioning and testing Water Coolers of 40/80 Ltrs capacity complete all as specified and directed. |
| 108 | All as per item No.107 above but Water Coolers of 60/120 Ltrs capacity complete all as specified and directed. |
| 109 | All as per item No.107 above but Water Coolers of 150/150 Ltrs capacity complete all as specified and directed. |
| 110 | Disconnecting the mains and taking out the unserviceable condenser coil and S&F new condenser coil as per existing size & patterns for Water Coolers of capacity 60/120, 150/150 Ltrs complete all as specified & as directed. |
| 111 | Disconnecting the mains and taking out the unserviceable condenser coiland S&F new condenser coil as per existing size & patterns for Water/Coolers of capacity 40/80Ltrs complete all as specified & as directed. |
| 112 | Dismantling the evaporator/cooling coil of water cooler capacity 150/150, 60/120 & 40/80 Ltrs, checking the leakages of gas and rectify the leakages by brazing or as other manner complete all as specified & as directed by Engr-in-Charge. |
| 113 | Taking down unserviceable PVC connection pipe and Supply and Fixing of PVC connections 15 mm dia bore with PTMT nuts of length 900 mm complete all as specified & as directed. |
| 114 | Dismantling of existing repairable Refrigerators of any make and from its position after disconnecting electric connections, transporting from site to contractor\"s workshop for carrying out repairs and renewal/replacement of parts, reassembling and transporting back to the site including installation of the same on the same location and making electric connection etc, all as specified and directed by Engineer-in-Charge. Note :-Parts renewed shall be measured and paid separately under appropriate items. |
| 115 | Supply only capillary tube of existing size including necessary brazing suitable for 165 to 330 Ltrs capacity refrigerator, including dismantling the old unserviceable one all as specified and directed. |
| 116 | Supply only over load protector relay suitable for 165 to 330 Ltrs capacity refrigerator all as directed. |
| 117 | Supply only thermostat suitable for 165 to 330 Ltrs capacity refrigerators all as directed. |
| 118 | Supply only freezer door with spring of refregierators of any capacity & make all as specified and directed. |
| 119 | Supply only vegetable basket with glass suitable for 165 to 330 Ltrs capacity refrigerators. |
| 120 | Supply only PVC defrost tray as per sample suitable of 165 to 330 Ltrs capacity refrigerators. |
| 121 | Supply only door gasket for refrigerators of capacity upto 330 Ltrs complete all as specified and directed.Note for item Nos 115 to 121 :- Materials of item No 115 to 121 to be incorporated in item No 114 here-in-before |
| 122 | Dismantling and removing defective compressor and supply and fixing (in repairs) new sealed compressor of approved make obtained from authorised dealers submitting Warranty certificate & test certificates from manufacturer/authorised dealers including charging of refrigerent gas R-22/134A/ R-410a, commissioning and testingrefrigerators of 165 to 210 Ltrs capacity complete all as specified and directed. |
| 123 | Dismanling and removing defective compressor and supply and fixing (in repairs) new sealed compressor of approved make obtained from authorised dealers submitting Warranty certificate & test certificates from manufacturer/authorised dealers including charging of refrigerent gas R-22/134A/R410a, commissioning and testingrefrigerators of 280 to 330 Ltrs capacity complete all as specified and directed. Note for item No. 122 & 123:-(i)The rates quoted by the contractor shall deemed to include the transportation cost from site of installation to contractor\"s repair workshop and back. |
| 124 | Dismantling of existing repairable deep freezers of any make and from its position after disconnecting electric connections, transporting from site to contractor\"s workshop fro carrying out repairs and renewal/replacement of parts, reassembling and transporting back to the site including installation of the same on the same location and making electric connection etc, all as specified and directed by Engineer-in-Charge. Note :-Parts renewed shall be measured and paid separately under appropriate items. |
| 125 | Supply only starting relay 1/6 HP open with OLP all as specified and directed. |
| 126 | Supply only starting relay for 1/8 HP open type with OLP all as specified and directed. |
| 127 | Supply only over load protector suitable for upto 500 Ltrs capacity deep freezer all as specified and directed. |
| 128 | Supply only running capacitor for upto 500 Ltrs capacity deep freezer all as specified. |
| 129 | Supply only thermostat suitable for upto 500 Ltrs capacity deep freezer all as specified and directed. |
| 130 | Supply only starting capacitor for upto 500 Ltrs capacity deep freezer all as specified and directed. |
| 131 | Supply only Axial Fan for deep freezers of any make and capacity complete all as specified and directed. Note for item Nos 125 to 131 :- Materials of item Nos 125 to 131 to be incorporated in item No 124 here-in-before |
| 132 | Taking down defective compressor of deep freezer of capacity Upto 500 Ltrs and any make and supplying and fixing new sealed unit compressor as specified here under including brazing and with necessary nuts and bolts, copper filter, capilary and supply & charging of refrigerant gas Non CFC based or equivalent to Non CFC gas in required qty and testing complete all as specified and directed by Engineer-in-Charge. |
| 133 | M&L for disconnecting the unserviceable PCBs from existing Inverter ACs of capacity 1.5/2/3 TR, and re-fixing after necessary repair for satisfactory functioning of the AC unit complete all as specified and directed. |
| 134 | M&L for disconnecting the unserviceable DC condensor fan motor of outdoor units and Supply, fixing & testing for proper functioning of existing Inverter ACs of any make and capacity 1.5/2/3 TR complete all as specified and as directed. |
| 135 | M&L for disconnecting the unserviceable DC blower fan motor of Indoor units and Supply, fixing & testing for proper functioning of existing Inverter ACs of any make and capacity 1.5/2/3 TR complete all as specified and as directed. |
| 136 | Dismantling and Refixing the Split AC of 1.5/2/3 TR including drilling of holes into a wall for connecting indoor with outdoor unit’s pipes and connecting indoor and outdoor units with copper pipes and installation of drainage pipes and fixing outdoor unit on separately ODU stand, temperature & gas pressure testing, gas charging,Carpentry work, Plumbing, masonry & white cementing Note : Cost of drain Pipe, copper pipe of required size, Refrigerent gas filling or top up , outdoor stand, power plug, MCB and copper wire as if required are included in the quoted rate. No extra cost to be paid to the contractor. |
| 137 | Note: The total amount shall subject to adjustment of credit of Rs 45147.50 for old Materials as per Schedule of Credit |