| Sl. No. | Item Description |
| 1 | M& L for disconnecting electrically connected incoming and outgoing LT UG cable of LT panel of any size and replace burnt/unsv suitable size of aluminium bus bar,aluminium lugs, Welding work for hinges and doors, fixing the locking arrangement including scraping outdoor/indoor side of LT Panel and painting with two coat of synthetic enamelled seimens gray spraypaints on outdoor/Indoor side over one coat of red oxide primer, and reconnecting LT UG cable of all suitable size cable and aluminium lugs by using crimping tool, nut, bolt washer etc and all necesary work required for smooth functioningof LT panel all specified and directed by Engr-in-Charge.Notes: (i) Spare Parts like MCCBs , Voltmeter, Ammeter, indicating LED RYB lapms, selector switches are measured separately under relevant items.(ii) End termination joints kits are measured seperately under relevant items here-in after. |
| 2 | Labour for Shifting of LT Panel after Disconnecting all the electric cable connections and earthing terminals from the LT Panel including transporting & fixing to another location and necessary earthwork & PCC works all as directed by Engr-in-Charge. |
| 3 | S & F in replacement MCCB 415 Volts 4 pole 400 Amps 50 Hz with rupturing capacity 50 KA alonwith spreader terminal with adjustable thermal setting and Ics=100%Icu including lugs/thimbles of suitable size in existing panels complete all as specified and directed.Note : Necessary addition /alteration required to adjust MCCB in the panel shall be done by the contractor and no extra payment will be made to the contractor. |
| 4 | All as per Item No.03 above but ofMCCB 315 Amps 4 pole 50 Hz 415 V with rupturing capacity 36 KA & Ics=100%Icu |
| 5 | All as per Item No.03 above but ofMCCB 250 Amps 4 pole 50 Hz 415 V with rupturing capacity 36 KA & Ics=100%Icu |
| 6 | All as per Item No.03 above but ofMCCB 200 Amps 4 pole 50 Hz 415 V with rupturing capacity 36 KA & Ics=100%Icu |
| 7 | All as per Item No.03 above but ofMCCB 100 Amps 4 pole 50 Hz 415 V with rupturing capacity 25 KA & Ics=100%Icu |
| 8 | S&Fheat shrink LT end joints for XLPE UG Cable of size 25 sqmm to 50 sqmm ,1.1 KV Grade |
| 9 | S&Fheat shrink LT end joints for XLPE UG Cable of size 70 sqmm to 150 sqmm ,1.1 KV Grade |
| 10 | S&Fheat shrink LT end joints for XLPE UG Cable of size 185 sqmm to 300 sqmm ,1.1 KV Grade |
| 11 | S&Fheat shrink LT end joints for XLPE UG Cable of size400 sqmm ,1.1 KV Grade |
| 12 | S&Fheat shrink LT straight through joints for XLPE UG Cable of size 25 sqmm to 50 sqmm ,1.1 KV Grade |
| 13 | S&Fheat shrink LT straight through joints for XLPE UG Cable of size 70 sqmm to 150 sqmm,1.1 KV Grade |
| 14 | S&F heat shrink LT straight through joints for XLPE UG Cable of size 185 sqmm to 240 sqmm,1.1 KV Grade |
| 15 | S&Fheat shrink LT straight through joints for XLPE UG Cable of size 300 sqmm to 400 sqmm,1.1 KV Grade |
| 16 | M&L for Digital voltmeter 0-500 volt with selector switch complete all as specified and directed by Engr-in-Charge. Make L&T/Havells/CG/AE |
| 17 | M&L for Digital Ammeter 0-800 Amp with selector switch and suitable size of CTs complete all as specified and directed by Engr-in-Charge. Make L&T/Havells/CG/AE |
| 18 | S & F in replacementLED type phase indication lamp of Red /Blue/Green colour for phase indication in existing panels complete all as specified and directed. |
| 19 | Supply and fix in replacement copper bus bar in the panelof exsiting size and capacity for phase and neutral with heat shrinkable PVC sleeves in different colour codes for phase indication all as per directed. |
| 20 | All as per item No 19.00 above but aluminium bus bar complete all as specified & directed. |
| 21 | Supply & fix in replacement ofOn load Change over switch 125 Amp, 415V 50Hz with Sheet steel enclosure and operatinghandleconfirming to IEC : 60947-3 including connection and testing complete all as specified and as directed by Engr-in-Charge. (Make :- L&T /Schneider/C&S/Havells). |
| 22 | Supply & fix in replacement ofOn load Change over switch 63 Amp, 415V 50Hz with Sheet steel enclosure and operatinghandleconfirming to IEC : 60947-3 including connection and testing complete all as specified and as directed by Engr-in-Charge. (Make :- L&T /Schneider/C&S/Havells). |
| 23 | Supply,installing,commissioning and testing in replacement of LT Panel/ LT feeder pillar outdoor type front and rear openableof dimension as per specified by manufacturer ,CPRI certified factory made cubical type weather and vermin proof fixed on and including ventilation and louvers arrangementwith angle iron frame of size 50mm x 50mm x 6mm, pedastial type and provided with four Nos of angle iron supports ( size of legs 600mm) duly embedded in foundation by PCC 1:2:4 type B-1 using 20 mm graded stone aggregate and as directed at site fabricated out of 3.15 mm thick CRCA steel sheet withthe degree of protectionIP-55 and including duly painted powder coated ( 7 Tank Process) and keeping adequate working space inside of the box and double door handle includingfront mounted cabinet, rod operated locking arrangement wih keys & countersunk holes at bottom for base mounting brackets and sheet steel gland plates for cable entry, formed gasket arround doors as directed before manufacturing the panel including Bus bar of following capacity and type with stainless steel nut bolts washers and spares holes with nut bolts on each bus bar and duly coveredwith shrinkable PVC sleeves as per colour coding ieRed, Yellow,Blue and Black & mounted on DMC / epoxy insulator and making connection of cables with appropriate size of lugs and cable glands and also two No danger Notice plate fixed on panel & The panel shall be prewired with suitable size PVC insulated copper conductor cable not less than 2.5 sqmm, multistrandedcomplete all as specified and directed.Note (a) The contractor shall submit the drawing of panels for approval to AGE(I)before manufacturing the panels.(b) All the MCCBs fixed in vertical ON/OFF positions with separate compartments for each swithgears.(c) All existing cable of any size will be connected with suitable size of cable lugs,glands, nut bolt etc as required at site and as directed(d) Cost of cable lugs, nut bolts, gland etc shall be deemed to be included in the above quoted rates.(e) Panels should be confiremed to IEC-61439 updated and switchgear confirmed to IS-8623 |
| 24 | The above Panel in item No 23 above housed with the following accessories:- INCOMING:-a) BusbarTPN, tinned copper Bus bar electrolytic grade copper rating 800 Amps , 4 strip covered with colour coded and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators,- 01 Set ( R Y B & N)(b) ACB (Air Circuit Breaker), 4 pole, 630 Amp, 415V 50Hz with Microprocessor based SR18G, MDO, C - power Draw -out ACB, including under voltage,rating breaking capacity 50 kA– 01 No(c) LED type Phase indicator lamp(RYB)= 03 Nosd)Ammeter Digital type CT operated, with selector switch and suitable size of CTs -01 Sete)Volt Meter Digital type 0-500 V range, (With selector switch) - 01 SetOUTGOING :-a) MCCB 4 pole 400 Amp 50 KA ,415 V, 50 Hz alongwith Spreader terminals with adjustable thermal and magnetic setting with (Ics= 100% Icu) – 02 Nos(b) MCCB 4 pole 250 Amp 36 KA, 415 V, 50 Hz alongwith Spreader terminals with adjustable thermal setting with (Ics= 100% Icu) – 02 Nos(c) MCCB 4 pole 200 Amp 25 KA,415 V, 50 Hz alongwith Spreader terminals with adjustable thermal setting with (Ics= 100% Icu) – 01 No(d) Digital Timer assembly three phase astronomical type with suitable contactor and MCB TPN 63 Amp capacity with Auto Manual Switch and indicating Lamp and connected wiring and fuse assembly with outgoing connection marking plate for street light - 01 Set ( fixed in separate compartment of the Panel) |
| 25 | The above Panel in item No 23 above housed with the following accessories:- INCOMING:-a) BusbarTPN, Aluminium, 630 Amps- 01 Set ( R Y B & N)(b) MCCB 4 pole 400 Amp 50 KA ,415 V, 50 Hz alongwith Spreader terminals with adjustable thermal & magnetic setting with (Ics= 100% Icu) – 01 No(c) LED type Phase indicator lamp(RYB)= 03 Nosd)Ammeter Digital type CT operated, with selector switch and suitable size of CTs -01 Sete)Volt Meter Digital type 0-500 V range, (With selector switch) - 01 SetOUTGOING :-a) MCCB 4 pole 250 Amp 36 KA,415 V, 50 Hz alongwith Spreader terminals with adjustable thermal setting with (Ics= 100% Icu) – 02 Nos(b) MCCB 4 pole 200 Amp 36 KA,415 V, 50 Hz alongwith Spreader terminals with adjustable thermal setting with (Ics= 100% Icu) – 02 Nos(c) MCCB 4 pole 100 Amp 25 KA,415 V, 50 Hz alongwith Spreader terminals with adjustable thermal setting with (Ics= 100% Icu) – 01 No(d) Digital Timer assembly three phase astronomical type with suitable contactor and MCB TPN 63 Amp capacity with Auto Manual Switch and indicating Lamp and connected wiring and fuse assembly with outgoing connection marking plate for street light - 01 Set ( fixed in separate compartment of the Panel) |
| 26 | Ditto all as above in item No 23 above but panel housed and comprised with the following accessories:- INCOMING:-a)ON LOAD Changeover Switch three phase 415 Volts 50 Hz, 250 Amps capacity -01 Nos(b) BusbarTPN, Aluminium, 500 Amps- 01 Set ( R Y B & N)(b) MCCB 4 pole 250 Amp 36 KA ,415 V, 50 Hz alongwith Spreader terminals with adjustable thermal & magnetic setting with (Ics= 100% Icu) – 01 No(c) LED type Phase indicator lamp(RYB)= 03 Nosd)Ammeter Digital type CT operated, with selector switch and suitable size of CTs -01 Sete)Volt Meter Digital type 0-500 V range, (With selector switch) - 01 SetOUTGOING :-a) MCCB 4 pole 160 Amp 25 KA,415 V, 50 Hz alongwith Spreader terminals with adjustable thermal setting with (Ics= 100% Icu) – 02 Nos(b) MCCB 4 pole 100 Amp 25 KA,415 V, 50 Hz alongwith Spreader terminals with adjustable thermal setting with (Ics= 100% Icu) – 02 Nos(c) MCCB 4 pole 63 Amp 16 KA,415 V, 50 Hz alongwith Spreader terminals with adjustable thermal setting with (Ics= 100% Icu) – 01 Nos |
| 27 | Ditto all as above in item No 23 above but panel housed and comprised with the following accessories:- INCOMING:-a) BusbarTPN, Aluminium, 400 Amps- 01 Set ( R Y B & N)(b) MCCB 4 pole 200 Amp 36 KA ,415 V, 50 Hz alongwith Spreader terminals with adjustable thermal & magnetic setting with (Ics= 100% Icu) – 01 No(c) LED type Phase indicator lamp(RYB)= 03 Nosd)Ammeter Digital type CT operated, with selector switch and suitable size of CTs -01 Sete)Volt Meter Digital type 0-500 V range, (With selector switch) - 01 SetOUTGOING :-a) MCCB 4 pole 100 Amp 25 KA,415 V, 50 Hz alongwith Spreader terminals with adjustable thermal setting with (Ics= 100% Icu) – 02 Nos(b) MCCB 4 pole 63 Amp 16 KA,415 V, 50 Hz alongwith Spreader terminals with adjustable thermal setting with (Ics= 100% Icu) – 04 Nos |
| 28 | Supply & installation and testing & Commissining CPRI approved outdoor cubical type IP 54,LT feeder piller box of High Mast Pole Lights suitable for 415 V, 3 phase 50 Hz , AC supply system, dust,weather& vermin proof, made of 3.15 mm thick CRCA sheet, powder coated with 7 tank process,TPN copper busbars of rating 250 Amp Cap.Bottom base channel of MS section not less then 45mmx45mmx5mm thick, entire panel shall have a common aluminium earth bar of size 25mm x5mm at the rear with 2 no earth stud,double door both side opening single door system lockable/openable by key from both sides having flush pattern fancy locks with louvers. cable entry with glands, foundation/grouting on & including PCC as per site requirement with the following : The drawing of the feeder pillar box will be approved by Engr-in-Charge & AGE(I) and the same having following electric controls:Incoming:(i) MCCB 63 Amps 4 Pole 415 volts 50 Hz 16 KA connected with required bus bar connections - 01 Nos(ii) Digital Voltmeter -01 , Digital Ampmeter- with CT 01 set, Indicating Lamp RYB- 01 setOutgoing:(i) MCB 40 Amps TPN415 volts 50 Hz 16 KA - 02 Nos(ii) Three Phase Digital Timer switch astronomical type with suitable contactors & Relay protection switches & fuses- 01 (iii) Auto manual switch for timer operation mode.(iv) Push button switch assembly for lowering and raising with torque motor for light fittings structure of High Mast Pole. |
| 29 | Supply & installation and testing & Commissining CPRI approved outdoor cubical type IP 54,LT feeder piller box suiable for 415 V, 3 phase 50 Hz , AC supply system, dust,weather& vermin proof, made of 3.15 mm thick CRCA sheet, powder coated with 7 tank process,TPN copper busbars of rating 250 Amp Cap.Bottom base channel of MS section not less then 45mmx45mmx5mm thick, entire panel shall have a common aluminium earth bar of size 25mm x5mm at the rear with 2 no earth stud,double door both side opening single door system lockable/openable by key from both sides having flush pattern fancy locks with louvers. cable entry with glands, foundation/grouting on & including PCC as per site requirement with the following :- (a) Bus bar electrolytic grade copper and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulator 250 Amp,4 pole, not less then 45 CM long mounted on insulators for incoming supply - 1 Set (Set of 4 strips) (b) Phase indicator lamp RYB LED type-1 Set (Set of three). (c) Digital Voltmeter & Ammeter - 02 Nos(d) CT of suitable ratio (Set of three)Incoming: (a) MCCB 160 Amp, 415V, 50 Hz,FP,,25 ka, Ics= 100% Icu fixed type, complete all as specified and directed by Engr-in-Charge.Note :- 1.Panel shall be installed at least 60 cm above ground 2.All civil/electrical work & material is deemed to be included in the quoted rates3.Drawing of Lt feeder panel shall be got approved from AGE(I).4. panel shall confirm to IEC - 61439 updated to date. |
| 30 | Supply & installation and testing & Commissining CPRI approved outdoor cubical type IP 54,LT feeder piller box suiable for 415 V, 3 phase 50 Hz , AC supply system, dust,weather& vermin proof, made of 3.15 mm thick CRCA sheet, powder coated with 7 tank process,TPN Aluminium busbars of rating 300 Amp and size 50mmX6 mm .Bottom base channel of MS section not less then 40mmx40mmx5mm thick, entire panel shall have a common aluminium earth bar of size 25mm x5mm at the rear with 2 no earth stud,double door both side opening single door system lockable/openable by key from both sides having flush pattern fancy locks with louvers. cable entry with glands, foundation/grouting on & including PCC as per site requirement with the following :- (a) Bus bar TPN Aluminium size 50mmX6mm supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulator 300 Amp,4 pole, not less then 45 CM long mounted on insulators for incoming supply - 1 Set (Set of 4 strips) (b) Phase indicator lamp RYB LED type-1 Set (Set of three). (c) Digital Voltmeter & Ammeter - 02 Nos(d) CT of suitable ratio (Set of three)Note :- 1.Panel shall be installed at least 60 cm above ground 2.All civil/electrical work & material is deemed to be included in the quoted rates3.Drawing of LT feeder panel shall be got approved from AGE(I).4. panel shall confirm to IEC - 61439 updated to date. |
| 31 | S&F and commissioning and testing of Automatic Naturetimer switch control of StreetLights complete with MCB,Power and Panel based on lux level of natural light.The sensor (Nature Switch) alongwith and including supply and fix of suitable power contactor of 1 Nos 40 Amps (Two pole ) two Nos MCB 63 Amps (single pole) and support terminals enclosed inpole /wall mountable enclosure of suitable size made out of rust proof electric shock proof termite proof and FR grade special moulding compound sintex make SMC junction box of suitable size confirming to IP54 circuit wiring suitable enoughto take load of 8 KW single phase load, with Auto and Manual Mode opeartion facility all as per Kakatiya Energy System Ltd Hydrabad Model SWADEEP Model SWADEEP-02EC8KW 1P , Healer Enterprises or techno commercially equivalent models in Havells/ L & T complete all as specified and directed. Note:- The contractor shall provide the company test certificates of the timer |
| 32 | Supply and fix in repairs loop-in loop-out junction box of size 25X25x15 cm made of 1.6mm thick PVC sheet weather proof, dust and vermin proof with hinged door of locking arrangements and slanting cover on topwith provision of aluminium busbar of size 25 x 2mm - 4 Nos (R,Y,B,N)fixed on insulator complete fixed on pole with and including suitable size MS flat iron clamps, nuts, bolts and washers, etc complete all as specified & directed. |
| 33 | Supply and fix in repairs street light bracket made out of 40 mm dia GI pipe medium grade of length upto 1.5 mtr bent to shape required with and including 2 Nos,40 x 6 mm MS flat iron clamps with nuts, bolts, washer etc and applying one coat of aluminium paint to clamps including dismantling of old broken brackets complete all as specified and directed. |
| 34 | Labour for making hole in the existing Steel Tubular Pole of any make ( Swan Neck/ Swaged Pole) by means of welding or drilling near Junction box of poles and top near street lights of the pole suitablefor passing of service cable from PVC Junction box to the street lightsinside the steel tubular pole complete all as specified and directed. |
| 35 | M&L for shifting of brackets clamps of security /street light of Poles from existinglocation to desiredlocation and height as per specified including opening and re- fixing the same by tightening with new nut bolts washers etc all as specified and directed. |
| 36 | M& L for Cleaning and preparation ofElectric Steel tubularpole complete and painting with one coat of aluminium paint including channels/ street light clamps, brackets , cross arms and making black & white strips and red & white Strips as directed with synthetic enameled paint of 30 cm height, eachalternative strip upto 1.5 mtr height and writing pole numbers with black synthetic enameled paint after making circular basewith yellow synthetic enameled paint and applying two coats of white wash on existing PCC coping complete all as specified & directed. |
| 37 | Supply and erection (in truly vertical position) in replacement of LT Steel tublar swaged pole complete with cast iron base plate finial taper plug, bolt , nut and screwed type 410 SP -31, 09 mtrs long including painting of poles with two coats of synthetic enamel paint in black and white strips upto 1.5 mtr height from coping over a coat of red oxide primer including numbering of poles as directed by Engineer in charge.Note : PCC, Earth work and MS work as cross arms clamps etc will be measured and paid separately. |
| 38 | M&L for earthingcomplete with galvanised Iron earth plate electrode of size 60cm x60cmx6mm thick burried directly in ground vertically ( to a depth not less than 2.25mtr deep below normal ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, connected tostrip 32x 6 mm size with nuts, bolts , check nuts , washers, earth plate surrounded by packed layers of charcoal dust and common salt 15cm thick all around, top & bottom watering pipe 20mm bore of GI mediumgrade with funnel and wiremesh all as shown in electrical plate No. 5 of SSR -1991 Part I and connecting to arthingtest point,main switch board and testing oncompletion including PCC chamber concrete 1:3:6 typeC-2 and RCC cover 75mm thick with MS TMT bar 8mm dia @ 150mm c/c both ways in cement concrete(1:2:4) type B-1 all asshown in electrical plate in No 5 of SSR(Pt-I)1991 complete all as specified anddirfected by Engineer-in-charge. |
| 39 | Ditto as per srl item no 38.00 above but with GI earth lead wire of 4mm dia as earth conductor and protection pipe of 15 mm dia for earthing of poles and lightening arrester incl connection with the equipment complete all as specified and directed |
| 40 | Supply and fixing/laying of galvanized iron strip of size 32x6 mm as earth continuity conductor provided in between earth test point terminal and upto the equipment incl nuts, bolts and washers complete all as specified and directed. |
| 41 | M&L for Air termination single pointed , copper rod 12 mm dia and 300 mm longcomplete all as specified and directed. |
| 42 | M&L for Test point terminal block made up of Gun metal or phosphorus Bronze size 75x75X25 mm drilled and screwed including 3 Nos 8mm dia 25 mm long hex head screw complete all as specified and directed. |
| 43 | S&F in repair/replacement of aluminium strip 25x3.15mm with saddles and fixing screws etc for roof conductor and down conductors aboveground all as specified & directed by Engg-in-charge. |
| 44 | S & F in replacement of PVC DMC blocks with nut bolts in PCC blocks. Note: All additional items required for fixing and connecting to strip is included in the quoted rate. |
| 45 | M&L for repair to earth pit & earth pit cover & PCC chamberby usingconcrete 1:3:6 typeC-2 for PCC chamber and RCC cover 75mm thick with MS TMT bar 8mm dia @ 150mm c/c both ways in cement concrete(1:2:4) type B-1 and plastering in CM 1:3 complete including excavation, returning filling and removal etc and replacement offunnel of watering pipe complete all as specified and directed. |
| 46 | M & L for hardcore of broken stone or boulders gauge of 40mm to 63 mm , deposited, spread and levelled in layers n exc. 15cm thick around four pole/two pole structure and transformer area complete all as specified |
| 47 | Hiring of cable fault detector, to detect exact position of fault for XLPE /PVC LT/HT cable, 1100/11000 Volts grade heavy duty aluminium conductor of any size including to and fro transporting charges etc. complete all as specified and directed by Engr-in-Charge. |
| 48 | Providing services by deploying adequate number of manpower for attending day to day complaints/ breakdowns of \"NO LIGHT / SHORT CIRCUIT\"\" including general maintenance, cleaning and dusting ofall external electric supply installations from feeder pillar box to building including LT overhead lines & LT under ground cable jointing, distribution panel board,repairs/replacement of defective componenets, fittings & fixtures and depositing the defective/unserviceable dismantled materials in store yard of AGE E/M Ayodhya complete all as directed by Enginner in Charge |
| 49 | Note :- (i) The Electrician should have good working knowledge ofLT Supply.(ii) The Electrician should in possession of all requisite T&P as required at site. All the T&P and equipments to be provided by the contractor at his own cost and the rates shall be deemed to be included all expenses on this account.(iii)Vehicle, ladder,tools and plant as required at site for repair work shall be provided by the contractor at his own cost and arrangement.(v) The timing of shifts will be 0900 to 1700 Hrs and reliever shall be arranged by the contractor and the cost thereof shall be deemed to be included in the quoted rate (vii) The contractor\"s representative will report to Engineer-in-Charge / JE EM I/C Ext Electric Supply daily in forenoon and afternoon to collect routine/urgent works related to Ext Electric Supply till completion of the contract. The work shall be attended by the contractor immediately.(viii) The complaint shall be rectified within 24 Hrs or otherwise a panalty of Rs 500/- per complaint per day shall be imposed to the contractor for delayed period.(x) The contractor shall provide all the safety equipments to his workers at his own cost and all safety measures shall be adhered to strictly. The department shall not be held responsible for any lapse / mishappening due to lack of safety measures. |
| 50 | Labour for cutting/ trimming/lopping of tree branches up to 80mm thickness along the alignment of LT /HT over head electric line which are going/ touching or falling on ACSR conductor/ poles or near by sub stns etc at any height from GL and making clearance of atleast 1.5m form conductor and removing to a distance up to 100 mtr where directed by Engineer-In-Charge.Note:- (i) Trimming of the branches on one sides of the conductor.(ii) Actual length of cutting will be measured.(iii) The distance as mentioned above will be maintained during contract current period & same location subject to at least 6 months period between two trimming/lopping.(i) Measurement will be taken including all conductor as one only. |
| 51 | Cleaning of surrounding area of E&M installation around the bldg,transformer,GOD, LT panel, by grass cutting manually or mechanically (Brush Cutter) as per requirement basis and trimming & cutting of grass vegetation ,saplings, shrubs, brush wood undergrowth roots and removing rubbish upto a distance of 50 metres outside the periphery of the area under clearancesoft/loose soiland getting out including sprinkling/spraying of anti vegetation chemical from spray machine in complete area complete all as specified and directed. |
| 52 | S&F first AID kit box -wallmount,multi compartment of size height 32 cm,width 28 cm , depth 8 cm made from high grade GI metal with 6 way processed powder coating for anti rust proof with front glass fitted 3 shelf, security lock on door to accommodate allnecessary items mentioned below, complete all as specified and directed.(i) 1 Pc normal saline 100 Ml(ii) 2 Pcs snake bite Lancet(iii) 1 Pc suction pump set(iv) 5 Pcs antiseptic Wipes(v) 1 Pc Sterlile wound dressing(vi) 2 Pcs scalpel blade (vii) 1 Pcs syringe 10 Ml(viii) 2 pcs tourniquet(ix) 1 Pc razor(x) 1 Pc scissor(xi) 1 Pc adhesive Bandage(xii) 1 Pc Heavy Crepe Bandage width 7.5x3 cm etc |
| 53 | Supply and fixing LED flood light 200 watt 230 V, 50 Hz AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant made of Pressure die cast aluminum housing powder coated in graphite grey and heat resistant thoughned glass with excellent thermal management including PVC cable connector, LED\"s should have lens optics and vandal proof prismatic poly carbonate covers for ensuring efficient optics and uniform distribution of light in field , ground & park area. Fitting should have operating voltage range of120 - 270 VAC , THD <10% , P.F >.95, the fitting should have in built surge protector of 5 KV to 10 KVcomplete all as as specified & directed complete with driver and lamp. all as specified and directed by Engr-In-Charge. Make:- Cromption/Havells/ Philips/Surya. |
| 54 | S&F in replacement of 1100 Volts grade heavy duty cable twin core Aluminum solid conductor with inner seathed with PVC tapes of size 6 Sqmm complete all as as specfied & directed |
| 55 | All as per sr item No 54 here in before but 10 Sqmm twin core Aluminum solid conductor complete all as as specfied & directed |
| 56 | S & F in repair cable twin core PVC insulated and unsheathed solid copper conductor of size 1.50 Sqmmfor street light and security light connection from junction box to lights inside of the steel tubular poles complete all as specified and directed. |
| 57 | Supply and fixing 1.5 Sq mm PVC insulated unsheathed multistranded single core copper conductor cable FRLS H, ISI marked cable (Red/Black colour) for Post top lights and garden lights connections complete all as specified & directed. |
| 58 | M& L for fabricating and fixing of cross arms (any type) supports, bracting, stiffness etc made out of MS channel, angle iron , flat iron , GI sheet of any size including drilling of holes, making clamps, eye hooks, nuts, bolts and washers etc, welding if required including painting with two coats of aluminium paint over a coat of red oxide paint all as directed. |
| 59 | M& L for fabricating and fixing of Steel Wire Mesh made out of MS 4 mm wire,including ,making clamps, eye hooks, nuts, bolts and washers etc, welding if required including painting with two coats of aluminium paint over a coat of red oxide paint all as directed. |
| 60 | S&F for fabricating and fixing of Chequered plates(Fe 290 Gde E-165) cover on indoor electric subsation cable duct including channels, square cuts or notched (ordinary and countersunk) forming holes, without any attachments includingnuts, bolts and washers etc, welding if required including painting with two coats of aluminium paint over a coat of red oxide paint and PCC work if required at site complete all as directed. |
| 61 | M & L for Structural steel work using rolled mild steel section of Fe-290 (Gde E-165) like Angles, flat, square, round bars as in framing for cladding, glazing and the like fixed with angle cleats and connecting plates etc all as directed. |
| 62 | Labour for repair and painting of iron/steel structure/mesh and fencing of sub station after welding of broken hinges, latches and lock hook in iron gates as directed on site and Painting with rust resistant enamel paint of black colour after scratching out old rusted surface complete all as specified and directed by Engineer in charge . |
| 63 | Supply , laying,jointing & testing ofXLPE (XLPE cable confirming to IS 7098 Part I) insulated ,armoured heavy duty electric cable with alumnium conductor, 1100 volts grade, corss sectional area 10 Sqmm 2 core complete all as specified and directed. |
| 64 | Supply , laying,jointing & testing ofXLPE (XLPE cable confirming to IS 7098 Part I) insulated ,armoured heavy duty electric cable with alumnium conductor, 1100 volts grade, corss sectional area 16 Sqmm 4 core complete all as specified and directed. |
| 65 | Supply , laying,jointing & testing ofXLPE (XLPE cable confirming to IS 7098 Part I) insulated ,armoured heavy duty electric cable with alumnium conductor, 1100 volts grade, corss sectional area 50 Sqmm 3.5 core complete all as specified and directed. |
| 66 | Supply , laying,jointing & testing ofXLPE (XLPE cable confirming to IS 7098 Part I) insulated ,armoured heavy duty electric cable with alumnium conductor, 1100 volts grade, corss sectional area 95 Sqmm 3.5 core complete all as specified and directed. |
| 67 | Supply , laying,jointing & testing ofXLPE (XLPE cable confirming to IS 7098 Part I) insulated ,armoured heavy duty electric cable with alumnium conductor, 1100 volts grade, corss sectional area 150 Sqmm 3.5 core complete all as specified and directed. |
| 68 | Supply , laying,jointing & testing ofXLPE (XLPE cable confirming to IS 7098 Part I) insulated ,armoured heavy duty electric cable with alumnium conductor, 1100 volts grade, corss sectional area 185 Sqmm 3.5 core complete all as specified and directed. |
| 69 | Excavation in trenches, not exceeding 1.5 meter wide and not exceeding 1.5 meter in depth for foundation of poles, stays or for taking out/laying of cables and getting out in soft/loose soil complete all as specified and directed by Engr-in-Charge. |
| 70 | All as per Item No: 69 above but depth exceeding beyond 1.5mtr and not exc 3 metre all as specified and as directed by the Engineer in charge |
| 71 | Returning, filling in, any type of soil and spreading in layers n. exc 25 cm thick each layer including watering & well ramming complete all as specified & directed. |
| 72 | Removal of surplus soil to a distance n.exc 50 mtr & depositing where directed at a level n. exc. 1.5mtr above the starting point complete all as specified & directed. |
| 73 | M&L for providing of new sub class \"B\" bricks old sizes, well burnt laid flat dry for protection of under ground cable complete all as specified & directed. |
| 74 | M&L for sand cushioning fromlocal sand dry, filling in trenches around LT under ground cable complete all as specified & directed. Note: Punned thickness of sand will be measured. |
| 75 | Supply and fixing / laying in replacement of galvanized iron pipe of 80 mm nominal dia light grade fixed to poles with clamps nuts, bolts and washers or laid under road crossing or fixed to wall complete all or fixed in ground for garden & Post top lights as specified and directed. Note : The cost of MS clamp, nut, bolt, washer and GI fittings etc shall be inclusive in the item rate. |
| 76 | All as above item 75 here in before but for 50 mm nominal dia complete all as specified and directed. |
| 77 | All as above item 75 here in before but for 40 mm nominal dia complete all as specified and directed. |
| 78 | M& L for Horizontal boring in soft/loose soil/under roads of any width by manual arrangements for inserting GI pipe up to 100mm/80mm bore for passing of cables complete all as specified and directed by Engr-in-Charge. Note : GI pipe shall be measured and paid separately. |
| 79 | Supply and laying of DWC/HDPE pipe 40 mm bore medium class, ISI Marked double wall corrugated for open/underground laying cable, cut to size and making thetubing forcable protection including cutting of road etc/cutting of PCC and making the good surface complete all as specified and directed by Engr-in-Charge.Note: (a) The using of GI Clamp in the wall/drainage rate are deemed to be included in the quoted rate.(b) The insulation of DWC pipe should be of high that does not deteriorate withUV rays/ heavy sun rays/winter season etc.(c)Drawing existing cable through DWC pipe shall be deemed to be included in the quoted rates.as in cable protection pipe of outer dia 40 mm including all fittings complete all as specified and directed. |
| 80 | S&FHDPE Pipe heavy duty 25 mm dia of PN 10 incluuding connected elbow & union for service cable encasing along pole, walletc from Junction box to Lights including PVC saddle clamps ,nails etc all as specified and directed. |
| 81 | Supply and fixing in replacement LED street light fitting, 60 Watt 230 V AC, 50 HZ outdoor type IP-66 degree of protection, compact & robust design With minimum system efficiency as > 85 % ,made of Pressure die cast aluminum housing powder coated in graphite grey and heat resistant thoughned glass with excellent thermal management including PVC cable connector, LED\"s should have lens optics and vandal proof prismatic poly carbonate covers for ensuring efficient optics and uniform distribution of light. Fitting should have operating voltage range of120 - 270 VAC , THD <10% , P.F >.95, the fitting should have in built surge protector of 5 KV to 10 KVcomplete all as as specified & directed. Make:- Cromption/Havells/ Philips/Surya. |
| 82 | S&F in replacement LED Bollard light fittings (garden lights) long life aesthetically designed Aluminum landscape IP 65 luminarie of size not less than 600 mm height energy saving eco friendly robust bodyof capacity 8 watt to 10 watt 230 V , 50 HZ AC with PCC works , earth work and fixing arrangement complete all as directed. |
| 83 | S&F in replacement post top energy saving environment friendly long life aesthetically designed with symmetrical light distribution LED Post Top lantern /gate light of capacity 15 watt , 230 V , 50 HZ AC with spun aluminium landscape luminaire and die cast aluminum spiget with high power LED\"s as light source and clear acrylic diffuser withIP 65protection and fixed with suitable dia & height medium grade GI Pipecomplete all as specified and directed. |
| 84 | Supply and fixing in replacement of ALL-in-OneSolar LEDstreet light fittingmade up with High Efficiency Mono Crystalline Solar PV Module with suitable Wp, lithium Ferro Phosphate Battery with in built BMS technology , High Efficacy LED, MPPT Solar Charge controller and aluminium Extruded body & is specially programmed to automatically control the dimming and brightness of light , which increases the backup time complete of LED Power light capacity 20 Watt IP 66 Protection complete all as specified and as directed. Make- Havells ,Philips, Bajaj, Crompton |
| 85 | M& L for Cutting of floor/wall/road/footpath for removal of LT U/G cable of any size/description and making good the same as per existing specification after relaying the same or new cable and all as specified & directed. |
| 86 | Material and labour for PCC 1:3:6 type C-2,using stone aggregate 40mm graded as in foundation of stays and coping of polesincluding necessary form work where required and fair finish to the exposed surfaces including broken of existing PCC all as specified & directed. |
| 87 | Material and labour for PCC 1:4:8 type D-2, using stone aggregate 40mm graded as in foundation for electric poles and making of cable duct including necessary form work where required and fair finish to the exposed surfaces all as specified & directed. |
| 88 | Supply and fixing in replacement of danger notice plate of 1.6mm thick, MS sheet, vitreous enamelled white, with letters, figuers and conventional skull and bones in signal red colour and fixed with MS clamps made out offlat iron 25x3 mm, nuts-bolts, of approved size for LT 20 x 15 cm and all as directed. |
| 89 | Supply and fixing in replacement of danger notice plate of 1.6mm thick, MS sheet, vitreous enamelled white, with letters, figuers and conventional skull and bones in signal red colour and fixed with MS clamps made out offlat iron 25x3 mm, nuts-bolts, of approved size for HT 25 x 20 cm and all as directed. |
| 90 | S&F portable fire extinguisher, dry powder type (gas catriage) mild steel with cylinder internally fully charged with dry chemical powder (ABC type fire class) of 6 Kg complete with standard discharge valve with tube, discharge range 6 meter includingCI bracket for wall mounting etc all as specified and direcetd. |
| 91 | Supply and laying in replacement of LT synthetic rubber insulation mat size 2MX1M made of elastomeric polymers material having a high insulation resistance thus imparting total safety to human being from any leakage current having high insulation resistance of class A of size 2 mm thick ,2M length and 1M width suitale for 3.3 KV confirming to IS-15652 : 2006 including pasting of mat with SR-998 by adding thinner as per requirement suitable for electrical shock safety complete all as specified and directed. |
| 92 | Supply and laying in replacement of HT high voltage insulation mat size 2MX1M made of elastomeric polymers material having a high insulation resistance thus imparting total safety to human being from any leakage current having high insulation resistance of class A of size 2.5 mm thick and 1 m width suitale for 11 KV confirming to IS-15652 : 2006 (superseding IS5424) including pasting of mat with SR-998 by adding thinner as per requirement suitable for electrical shock safety complete all as specified and directed. |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2025 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail