| 1 | SCHEDULE \"A\" PART IA (TO BE QUOTED BY THE CONTRACTOR) is not prepriced by MES and prepriced rates indicated as blank under col 5 signifies this fact only. Bidders shall insert their lumpsum amount of BOQ Ser item Nos. 1 & 2 in the Green coloured field under Col-6 only.Note: The quoted rates against the items under this schedule are deemed to include for the provisions contained in Scope of Work and Sch \"A\" Notes. Ref Sch \"A\" Notes complete before quoting these items. Structural designs and architectural/ structural drawings for structures and foundations for the buildings/ structures shall be prepared to comply with the provisions for design and analysis of RCC structures as per latest editions of relevant IS Codes. |
| 2 | Schedule ‘A’ Part IA BUILDINGS/ STRUCTURES (TO BE QUOTED BY THE CONTRACTOR) |
| 3 | Lumpsum price worked out for Design and Construction of One unit of Ground Run Point Pre Engineered Structure (PEB) including all services as listed in Schedule ‘A’ Part IA complete all as specified in scope of work, Sch \"A\" Notes, drawings, specifications and other parts of tender documents as directed. |
| 4 | Lumpsum price worked out for Design and Construction of 01 Block of Six Sun Shelters of Pre Engineered Structure (PEB) including all services as listed in Schedule ‘A’ Part IA complete all as specified in scope of work, Sch \"A\" Notes, drawings, specifications and other parts of tender documents as directed. |
| 5 | NOTE: Schedule ‘A’ Part IB to VIII under Ser No. 3.00to 9.00 are prepriced by MES. Bidders shall insert their lumpsum amount in the Green coloured field under Col-6 only. |
| 6 | Lump sum price worked out for FOUNDATION OF BUILDINGS/ STRUCTURES as listed in Sch \"A\" Part-IB. |
| 7 | Lump sum price worked outfor EXCAVATION, EARTH WORKas listed in Sch \"A\" Part II. |
| 8 | Lump sum price worked out for FLAME PROOF INTERNAL ELECTRIC SUPPLY as listed in Sch \"A\" Part III. |
| 9 | Lump sum price worked out forLIGHTENING PROTECTION as listed in Sch \"A\" Part IV. |
| 10 | Lump sum price worked out for TARMAC AND MISC WORKS as listed in Sch \"A\" Part V. |
| 11 | Lump sum price worked out for AREA DRAINAGE as listed in Sch \"A\" Part VI. |
| 12 | Lump sum price worked out for EXTERNAL ELECTRIC SUPPLY as listed in Sch \"A\" Part VII. |
| 13 | SCHEDULE \"A\" PART - VIII MISCELLANEOUS ITEMS is not prepriced by MES and prepriced rates indicates 0.0 under column 5 signifies this fact only. Bidder shall insert their rates in Green filed under Col-6. |
| 14 | FLAME PROOF INTERNAL ELECTRIC SUPPLY |
| 15 | S & F for Flame proof brass unions suitable for 20 mm ERW conduit, duly certified by CMRI Dhanbad complete all as specified and directed. |
| 16 | S & F for Flame proof brass bends suitable for 20 mm ERW conduit, duly certified by CMRI Dhanbad complete all as specified and directed. |
| 17 | S & F for Flame proof closing plugs suitable forERW 20 mm dia conduit duly certified by CMRI Dhanbad complete all as specified and directed. |
| 18 | S&F flame proof /Weatherproof 4 way junction box with 4 Nos terminal, 100 mm dia for looping in and looping out connections, duly certified by CMRI Dhanbad complete all as specified and directed. |
| 19 | S&F Flame proof switch socket & plug combined in LM6 cable termination box, 32 Amps, 415 Volts, 5 Pin (4P+earth), duly certified by CMRI Dhanbad complete all as specified and directed. |
| 20 | S&F flame proofSheet steel metal enclosure of size 480 X 480 X 250mm, CMRI certified distribution box , 8 Way 415 Volts with MCCB 4 Pole, 63 Amps-1 No, Outgoing MCB SPN, 240 Volts 5-32 Amps- 12 Nos complete with internal Bus Bar & wiring upto terminal, duly certified by CMRI Dhanbad complete all as specified and directed. |
| 21 | S&F flame proofSheet steel metal enclosure of size 420 X 480 X 250mm, CMRI certified distribution box , 4 Way 415 Volts with MCB 4 Pole, 63 Amps-1 No, Outgoing MCB SPN, 240 Volts 5-32 Amps- 06 Nos complete with internal Bus Bar & wiring upto terminal, duly certified by CMRI Dhanbad complete all as specified and directed. |
| 22 | S & F forFlameproof/ weatherproof LED flood light fitting 200 Watt , IP66 protection of Cast Aluminum alloy in LM6material and Heat and Impact resistance toughen \"A\" clear glass having Anti corrosive epoxy powder coated finish complete with all accessories pre wired duly certified by CMRI Dhanbad and including connecting up with three core flexible copper conductor cable with suitable size complete all as specified and directed.Note:- Design and scheme for illumination level of 500lux at working surface shall be submitted to GE by the contractor through OEM for approval. |
| 23 | M & L for surface flame proof Sub main wiring with under mentioned single core PVC insulated unsheathed multistrandedwith copperconductorcable, 1100Volts FRLS-Hgrade ISImarkeddrawnthrough in and including ERW steel conduit with flame proof accessories and including onerun ofFRLS-H PVCinsulated single core cable unsheathed strandedcopper conductor cablegreenin colour forearthcontinuityconductor complete all as specified and directed.Note :- (i)Four runs single core cableandtworuns single core cable ofearthwire and one run of ERW steel conduit pipe shallbemeasuredasonelength.(ii) Flame proof accessories such as Junction box, unions and bends shall be measured and paid seperately. |
| 24 | 4 run of 4.0 Sqmm single core cable and 2 run of 4.0 sqmm single core cable connected to common earth dolly. |
| 25 | 4 run of 6.0 Sqmm single core cable and 2 run of 6.0 sqmm single core cable connected to common earth dolly. |
| 26 | S & F for Flame proof LED aviation obstruction light fitting at ATC tower of Red colour 20 watts, 230 Volts, 50 Hz, Ac, IP 65 protection, vermin, dust & weather proof LM6 body self contained wire, duly certified by CMRI Dhanbad compartment complete all as specified and as directed. |
| 27 | M & L for maintenance free Chemical earthing of technology 3 mtr long 25 mm dia with 250-micron Copper coating and UL listed. There should be terminal for connection of 150 x 50 x 6 mm with 4 holes of 12 mm dia along with 2 bags of 25 Kgs each of earth enhancing compound. The chemical compound should be tested and certified by any NABL accredited laboratory with 95 percent carbon content. The testing laboratory should be an ISO 9001 and 14001 certified. The earth enhancing compound should be IEC 62321. The ph value of compound should be 7-8. Electrode should be duly tested and certified by CPRI, Govt of India for a min short circuit current of 25 kA rms for 1 Sec. including necessary boring of suitable dia upto required depth in any type of soil for inserting copper rod and filling of chemicals and Poly plastic pit cover of material- polymer body & cover dimensions- 308 mm (L) x 308 mm (W) x 214 mm (H) bearing capacity 7.5 Ton approved from NABL approved Lab complete all as specified and as directed. |
| 28 | M & L for maintenance free Chemical earthing of technology 3 mtr long 17.2 mm dia with 250-micron Copper coating and UL listed. There should be terminal for connection of 150 x 50 x 6 mm with 4 holes of 12 mm dia along with 2 bags of 25 Kgs each of earth enhancing compound. The chemical compound should be tested and certified by any NABL accredited laboratory with 95 percent carbon content. The testing laboratory should be an ISO 9001 and 14001 certified. The earth enhancing compound should be IEC 62321. The ph value of compound should be 7-8. Electrode should be duly tested and certified by CPRI, Govt of India for a min short circuit current of 25 kA rms for 1 Sec. including necessary boring of suitable dia upto required depth in any type of soil for inserting copper rod and filling of chemicals and Poly plastic pit cover of material- polymer body & cover dimensions- 308 mm (L) x 308 mm (W) x 214 mm (H) bearing capacity 7.5 Ton approved from NABL approved Lab complete all as specified and as directed. |
| 29 | Note for item no 20 & 21:-(i) Earthing is to be done infront of the Engr-in-Charge.(ii)Test Results of earthing to be submitted by the contractor for all earthings.(iii)The Contractor shall have to give written guarantee for maintenance earth resistance of less than 1.0 Ohm for the period of 10 (ten) years after certified date of completion and shall bdeposited 2000/- per earthing as security deposit for a period of Ten (10) Years.(iv)Failing to maintain resistance of earthing less than 1.0 Ohm , new earthing to be provided by the contractor with out any extra cost.(v)Necessary earth work, excavation shall be carried out in any type of soil strata, retuning, filling in and making good surrounding area complete. |
| 30 | TARMAC, AREA DRAINAGE AND MISC WORKS |
| 31 | M & L for cutting 10mm wide existing PQC Tarmac/ Runway/ Hardstanding by saw cut using diamond bit cutter of appropriate size, straight and smooth edges without damaging the existing Tarmac edges/ surfaces of depth exc 450mm & n. exc 500mm complete all as specified and directed. |
| 32 | M & L for scarifying or picking Gravelled Macadam, WBM, Soling, GSB etc any layers and surfaces in area exc 400 sqm and depth upto 350mm etc complete all as specified and directed. |
| 33 | EXTERNAL ELECTRIC SUPPLY |
| 34 | S & F for Cable route indicator / Marker made up of PCC Block in cement mortar 1:3:6 (20 mm graded aggregrate) of size 900 x 300x 100 mm thick with \"DANGER/ LT 433 VOLTS CABLE /MES or DANGER/ MES\" embossing on cable route Indicator / Marker including painting as per approved colour and buried in ground 45 Cms including necessary earth work (as required/ ordered at site) complete all as specified and as directed. |
| 35 | Supply ,fabrication, installation and testing of LT Panel factory made, TypeTest Assemble (TTA) Panel for working on 3 phase, 4 wire, 415 Volts, AC, 50Hz, cubical,out door type, weather proof, water proof, dust proof, vermin proof, shock proof IP 65 protectionmade out CRCA seet 3.15 mm thickness of suiitable size accommodate accessories with front and back double door opening/ lockable by the key from both side and provn of suitable bus bar chamber and switch gear compartments for MCCB incoming & out going feeders etc with copper extension links of suitable curent carrying capacitty not less than 1.5 times the rated current carrying capacity of MCCB individual feeder supported on DMC /Epoxy insulator including provison for termination with incoming and out going cables with cable glands. LT Panel shall be mounted on 50 x 50 x 6 mm size MS angle iron frame duly painted with two coats of black bituminus paint over a coat of red oxide primer including PCC foundation of suitable size with PCC 1:2:4 type B1(using 20 mm graded stone aggregate) .All extension link/ inter connection shall be insulated with heat shrinkable colour coaded sleeves to accomodate and including the following accessories:-. (Near MMPU Sub Station)Note:- Rate of earthwork and necessary PCC Plat form with PCC, B21:3:6 work with 1 Mtr clear space around the LT Paneletc are deemed to be inclusive in this item. |
| 36 | IN COMMING:-(a)Copper strip busbar of 400 amps rated capaacity wrapped with PVC sleeves with maintained the colour code and provision of making holes with Copper nuts, bolts & washers for cable connections including hydrograpic insulators with nuts & bolts at both ends= 04 Nos(b)4 pole MCCB 200 Amps with rotary handle, adjustable thermal magnetic release type 415 Volts,Ics = 100% Icu, breaking capacity 35 KA including all fixing accessories with both ends spreader links - 01 No.(c)LED Neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, AC -01 set (set of three).(d)Digital Ammeter of range (0- 250) Amps, flush mounting type with CT’s of ratio 250/5 and selector switch – 01 set.(e)Digital voltmeter of range (0-500) volts, flush mounting type with selector switch – 01 No. |
| 37 | OUT GOING:-(a)4 pole MCCB 160 Amps with rotary handle, adjustable thermal magnetic release type 415 Volts,Ics = 100% Icu, breaking capacity 18 KA including all fixing accessories with both ends spreader links - 01 No.(b)4 pole MCCB 32 Amps with rotary handle, adjustable thermal magnetic release type 415 Volts,Ics = 100% Icu, breaking capacity 18 KA including all fixing accessories with both ends spreader links - 01 No.(c)Enamelled iron danger notice plate of 1.60 mm thick mild steel sheet of size 200 mm X 150mm , white with letters , figures and conventional skull and bones in signal red and fixed with nuts and bolts on door / shutter of LT Panel -01 No. |
| 38 | Supply ,fabrication, installation and testing of LT Panel factory made, TypeTest Assemble (TTA) Panel for working on 3 phase, 4 wire, 415 Volts, AC, 50Hz, cubical,out door type, weather proof, water proof, dust proof, vermin proof, shock proof IP 65 protectionmade out CRCA seet 3.15 mm thickness of suiitable size accommodate accessories with front and back double door opening/ lockable by the key from both side and provn of suitable bus bar chamber and switch gear compartments for MCCB incoming & out going feeders etc with copper extension links of suitable curent carrying capacitty not less than 1.5 times the rated current carrying capacity of MCCB individual feeder supported on DMC /Epoxy insulator including provison for termination with incoming and out going cables with cable glands. LT Panel shall be mounted on 50 x 50 x 6 mm size MS angle iron frame duly painted with two coats of black bituminus paint over a coat of red oxide primer including PCC foundation of suitable size with PCC 1:2:4 type B1(using 20 mm graded stone aggregate) .All extension link/ inter connection shall be insulated with heat shrinkable colour coaded sleeves to accomodate and including the following accessories:-. (Near MMPU Sub Station)Note:- Rate of earthwork and necessary PCC Plat form with PCC, B21:3:6 work with 1 Mtr clear space around the LT Paneletc are deemed to be inclusive in this item. |
| 39 | IN COMMING:-(a)Copper strip busbar of 320 amps rated capaacity wrapped with PVC sleeves with maintained the colour code and provision of making holes with Copper nuts, bolts & washers for cable connections including hydrograpic insulators with nuts & bolts at both ends= 04 Nos(b)4 pole MCCB 160 Amps with rotary handle, adjustable thermal magnetic release type 415 Volts,Ics = 100% Icu, breaking capacity 35 KA including all fixing accessories with both ends spreader links - 01 No.(c)LED Neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, AC -01 set (set of three).(d)Digital Ammeter of range (0- 250) Amps, flush mounting type with CT’s of ratio 250/5 and selector switch – 01 set.(e)Digital voltmeter of range (0-500) volts, flush mounting type with selector switch – 01 No. |
| 40 | OUT GOING:-(a)4 pole MCCB 40 Amps with rotary handle, adjustable thermal magnetic release type 415 Volts,Ics = 100% Icu, breaking capacity 18 KA including all fixing accessories with both ends spreader links - 05 Nos.(b)4 pole MCCB 32 Amps with rotary handle, adjustable thermal magnetic release type 415 Volts,Ics = 100% Icu, breaking capacity 18 KA including all fixing accessories with both ends spreader links - 01 No.(c)Enamelled iron danger notice plate of 1.60 mm thick mild steel sheet of size 200 mm X 150mm , white with letters , figures and conventional skull and bones in signal red and fixed with nuts and bolts on door / shutter of LT Panel -01 No. |
| 41 | Supply, install, testing and commissioning of Diesel Engine driven generating set of capacity 100 KVA/ 80 KW, 3 Phase, 4wire, 415 Volts, 1500 RPM, 50 Hz power supply with power factor 0.8 coupled directly to alternator mounted on a common base plate complete with integral acoustic enclosure having silent features such as modular bolted construction with fabrication on imported CNC torret punch machines, nine tank treatment process with pure polyster based powder coating to ensure long life in all weather conditions and for out door application/ installation, integrated design there by facilitating / easy handling installation & shifting of the equipment at site. The design of integral acoustic enclosure should be any type approved by national Physical laboratory as per Central Pollution Control Board for latest norms/ regulation and lowest exhaust emissions meets with new generation with CRDI STD of CPCB-IV+, ISO 8728/ Noise pollution norms of MoEF & certified by ARAI, Punewith fuel tank, battery and standard accessories, acoustic enclosure, vibration pad, tools and spare,as provided by manufacturer, PCC foundation as per OEM all as specified and as directed with the following specifications :- |
| 42 | (A) ENGINE :- (a)Engine shall be Water cooled diesel engine of suitable capacity to match the 100 KVA, alternator under NTP conditions with prime rating as per ISO 8728,provision of 10% over load provision shall be available for intermittent periods confirming to BS-5514/ ISO 3046. The Engine shall consist of following :-(i) Fly wheel(ii) Close coupling (iii) Cooling fan (iv) Radiator with guard and water pump engine mounted(v) Battery charging alternator (vi) Air cleaner heavy duty dry type |
| 43 | (vii) Fuel injection pump (FIP) (viii) Radiator fan (blower type) with guard (ix) Precision governor(x) Fuel filter (xi) Lubricating oil fiters (mounted) (xii) 12 Volts self regulating alternator belt driven by engine(xiii) Exhaust silencer heavy duty residential type(xiv) Corrosion resister / scale inhabitor(xv) Starter 12 Volts DC (xvi) Lubricating oil cooler (xvii) Lubricating oil pump (gear type) (xviii) Exhaust piping as per manufacturer design.\" |
| 44 | (B) BRUSHLESS ALTERNATOR :-(i) Alternator coupled to engine through a flexible coupling to an indigenous alternator mounted on strong steel fabricated base frame suitable for mounting on a permanent foundation. Brush less alternator shall be confirming to BS 5000 or relevant of IS-4722.(ii) Type :- Self excited self regulated with automatic voltage regulator(iii) Rating:-100 KVA at 0.8 PF lagging 4 pole horizontal at NTP condition(iv) Speed - 1500 RPM(v) System -415 Volts - 2.5% AC 3 phase 4 wire 50 Hz(vi) Connection - 4 wire star connection(vii) Enclosure - Screen projected drip proof(viii) Ventilation - Self ventilated(ix) Insulation - Insulation, Class H, IP-23 |
| 45 | (C) CONTROL PANEL : The Control Panel shall be manufactured with 14/16 guage CRCA sheet duly powder coated for a weather proof and long lasting finish. The Control Panel shall consist the following parts :-(i) PSO 500 Controller :- Aluminium Bas Bars with suitable capacity with incomming/ outgoing terminals - Indicating Lamps for \"Load On\" and \"Set Running\" - MCCB of suitable rating with overload and short circuit protections.(ii) PSO 500: Genset Controller :-Control microprocessor based Generator set monitoring and control system. The control shall provide a simple operator interface to the Gererator set, manual and remote start / stop control, shutdown fauit indication and an LCD hour counter. The integration of all function into a single control system provides enhanced reliabity periormance compared to conventional generater set control system. The control shall be designed and tested to meet harsh environment in which gensets are typically applied. |
| 46 | Features, Functions, Protections :-(i) 16 character x 2 line alphanumeric LCD display with LED backlight.(ii) Operator interface(iii) Provide a record of most recent fault conditions. Fault history stored in the control non volatile memory.(iv) Provide alternator data - Voltage (line to line and line to neutral voltage) - current (1 ph. or 3 ph.) - KVA (3ph and total)(v) Provide Engine data - Starting battery voltage - Engine running hours- Engine Temp - Engine oil pressure.(vi) Control includes provision for service adjustment and calibration of DG control functions - voltage, frequency selection configurable input and output set up - Meter calibration |
| 47 | (vii) Engine Control :-(a) Powerstart operates on 12 Volts DC Batteries(b) Auto start mode accepts a ground signal from remote devices to automatically start the DG set. The remote start will also make up the control system from sleep mode.(c) Engine Starting :- The control system supports automatic engine starting, primary and backup start disconnects are achieved by battery charging alternator feedback or main alternator output frequency.(d) Controller provide configurable time delay of 0-30 sec to start after remote start signal and time delay of 0-60 secs prior to shutdown after stop signal.(e) Sleep mode increase battery life. Configurable current setting from low to minimize current draw when genset is not working. |
| 48 | (vii) Enigne Protective Functions includes :- (a) High engine water tempreature warning/ shutdown(b) Low coolant temp warning(c) Sensor failure indication(d) Low and high battery voltage warning(e) Weak battery warning(f) Fail to start shut down(g) Cranking lockout : Control will not allow the starter to engage or to crank the running engine(h) Cyclic cranking: Configurable for the number of starting cycle (1 to 7) and duration of crank and rest periods. |
| 49 | (D) Sub Base Fuel tank:-14 SWG MS Sheet and capacity to hold diesel sufficient for running 08 hours at full load including followingi-(i) Level indicator on fuel tank (ii) Drain Plug (iii Piping for fuel tank as per manufacturer design.(iv) Fuel stainer (v) Air vent, Fuel tank shall be mounted as per manufacturers instruction(E) Base Plate :- Fabricated out of MS Channels ISMC of suitable size for fixing DG Set all as specified by the manufacturers (Necessary permission / certificate from Central State Pollution Control Board shall be accomplished with DG Set) CPCB- IV+.(F) Foundation:-PCC Foundation not less than 4.0 mtr (L) x 2.0 mtr (B) and 0.3 mtr (H) above ground) to be provided or as per OEM recommendations complete all as specified and as directed. |
| 50 | (G) AMF Panel :- Indoor type AMF Panel made upto of 2.0 mm thick CRCA sheet power coated complete including following:- (i) Main switch gear 160 Amps 4 Pole 36 KA, 415 Volts, AC, MCCB with rotary handleand suitable spreader links -01 Nos (ii) Mains control gear 160 Amps 4 Pole, AC, 240 Volts AC contractor - 01 No(iii) Mains metering with RYB indication LED with necessary internal wiring of suitable size and din type connector and terminal connectors (iv) DG Swtich gear 160 Amps 4 Pole, 36 KA, 415 Volts, AC, MCCB with rotary handle and suitable spreader links - 01 Nos (v) DG control gear- 160 Amps 4 Pole, AC 240 Volts, AC contactor - 01 No (vi) DG metering with RYB indication LED with necessary internal wiring of suitable size and din type connector and terminal connectors |
| 51 | (vii) Common metering with RYB LED indication LED with necessary internal wiring of suitable size and din type connector and terminal connectors(viii)Common controlling system as per OEM :- (ix) AMF Controller to monitor and display thetemperature of engine, water, level of coolant, diesel, power consumption on main power consumption on DG, RPM, Hz. mains ON, DG ON, etc (x) Single phase preventer,(xi) Overload protection relays (xii) Under volt, relay (xii) Suitable cabling from DG set to AMF (xiv) Door opening on front and rear side complete.Note:- The cost of above provisions shall deemed to be included in quoted rate. |
| 52 | NOTE : Amount of credit of Rs. 1,79,724.30 for retrieved materials is mentioned in schedule of credit on Srl Page No. 50 of tender documents in PDF form which will be deducted offline while acceptance of tender. |