| 1 | Supply, install testing and commissioning in repair factory madeout door typeLT panel board of size not less than 1.5 mtr X 1.2mtr X 1 mtr, 440 volts , 3 phase , 4 wire system with powder coating providedto make it dust /vermin proo,f manufactured from CPRI approved manufacturer, The panel shall be made with 3.15 mm thick CRCA sheet for outer shell and inner shell made out of 1.6 mm thick CRCA sheet,double door with front openable with locking arrangement, provision of threaded earthing stud at bottom, inner shell be compartmentalized, front openable single door system lockable. Inner shell completely vermin proof and to accommodate incoming/outgoing ACB\"s, MCCBs, MCBs, and TPN aluminium bus and extension links. Aluminium bus bar of capacity 1000 Amps- 4Nos,including neutral duly insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size/rating of epoxy resininsulator all housed in suitable bus bar chamber.All control wires shall be as per the OEM recommendations and shall be properly bunched,tied, ferrulled for proper indentification and crimped with adequate size of lugs andprovision and fixing of Voltmeter,Ammeter with built in selector switch, CTs of suitable ratio, and pilot indication lamps completealong with provision of necessary cable entry/exit boxes for all incoming and out going cables with suitable size of cable glands etc. Computer cut shelf adhesive vinyl danger notice plate having conventional symbol of bone & skull be provided. The panel shall consists of following accessories complete all as specified and directed:- Location :- Near Md Accn Sub Stn No- 2 &3 Aundh Camp. |
| 2 | Note : (i) Electrical connection from switchgear to bus bar shall be through copper strips of suitable size.(ii) The internal electrical connection for measuring instruments shall be through multi-stranded PVC insulated copper conductor cables of suitable size.(iii) The termination of incoming and outgoing cable into and from switchgear would be through properly crimped aluminumlugs of suitable rating incommensurate with that of switchgear.(iv)Cable glands would be provided for incoming & out going cables in panels.(v)The cost of fixing of the panel on suitable PCC (1:3:6) type C-1(using 20 mm graded black trap/basalt/granite stone aggregates) foundation as directed by Engineer-in-Charge is deemed to be included in the quoted rates by the contractor for the above item.(vi)The panel is to be fixed with Angle Iron Frame of size 65mm x 65mm x 6mm with bottam of panel having minimum 60cm height from existing ground/floor level.(vii) The operation of all MCCBs should be of Rotary handle type, the cost of rotory handles is deemed to be included in the quoted cost. |
| 3 | Aluminium bus bar strips with proper colour code -04 No, 1000 A cap, insulator, nuts bolts etc complete. |
| 4 | Indicator Lamp-01 Set (Set of three) |
| 5 | IncommerACB 630 Amps Manual draw out type , 50 KA 4 pole 415 volts - 01 NosMake :- Legrand cat no -DMXS106N3MD4N or Havells Cat No- IHAFE21060080 |
| 6 | Outgoing, MCCB 4P320 amp with thermal magnetic release , 415V, 36 KA- 01 No (for APFC panel) Make Legrand cat no-4220 06 or Havells Cat No- IHLLSEE40320 |
| 7 | Outgoing, MCCB 4P125 amp with thermal magnetic release , 415V, 25 KA- 07 No (for Feeder panels of Md accn) Make Legrand cat no-4200 56 or Havells Cat No- IHTT1DBF0125 |
| 8 | Outgoing, MCCB 4P63 amp with thermal magnetic release , 415V, 25 KA- 01 No (for Street light panel) Make Legrand cat no-4200 53 or Havells Cat No- IHTTHDB40063 |
| 9 | Digital Voltmeter 0 V to 500 Vand Digital Amps meter0 A to 1000 A. with selector switch |
| 10 | Connection with Aluminium bus bar strip duly insulated with coloured sleeves /stranded copper cable of suitable size with thimbles. |
| 11 | Supply, install, testing and commissioning out door type 100 KVAR APFC PanelFloor/Wall mountedfront operated totally enclosed vermin proof, weather proof and dust proof made out of 3.15mm thick CRCA sheet steel for housing all components of 8 stage, 100kVARAutomatic power factor correction panel including incoming MCCB 250 Amps 4 pole , Capacitor duty contactors, step protection MCB\"s, indicating lamps, APFC relay, 100 KVAR (4(20KVAR)+1(10KVAR)+1(5KVAR)+1(3KVAR)+1(2KVAR)) capacitor MPP-H in steps,ammeter, voltmeter with selector switches and all accessories complete all as specified and directed. Make of APFC Panel - Havells cat no- QHXTCB5100X0 or equivalentin Legrand/Schneider/BCHNote :- The size of panel should not be less than (1.1x0.7x0.250)mtr.Location :- Near Md Accn Sub Stn No- 2 &3 Aundh Camp. |
| 12 | Supply, install testing and commissioning in repair factory madeout door typeLT panel board of size not less than 1.5 mtrX1mtrX0.450 mtr, 440 volts , 3 phase , 4 wire system with powder coating providedto make it dust /vermin proo,f manufactured from CPRI approved manufacturer, The panel shall be made with 3.15 mm thick CRCA sheet for outer shell and inner shell made out of 1.6 mm thick CRCAsheet,double door with front openable with locking arrangement, provision of threaded earthing stud at bottom, inner shell be compartmentalized, front openable single door system lockable. Inner shell completely vermin proof and to accommodate incoming/outgoing MCCBs, MCBs, and TPN aluminium bus and extension links. Aluminium bus bar of capacity 500 Amps- 4Nos,including neutral duly insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size/rating of epoxy resininsulator all housed in suitable bus bar chamber.All control wires shall be as per the OEM recommendations and shall be properly bunched,tied, ferrulled for proper indentification and crimped with adequate size of lugs andprovision and fixing of Voltmeter,Ammeter with built in selector switch, CTs of suitable ratio, and pilot indication lamps completealong with provision of necessary cable entry/exit boxes for all incoming and out going cables with suitable size of cable glands etc. Computer cut shelf adhesive vinyl danger notice plate having conventional symbol of bone & skull be provided. The panel shall consists of following accessories complete all as specified and directed:- Location :- Near Ph- I Md Accn,Aundh Camp. |
| 13 | Note : (i) Electrical connection from switchgear to bus bar would be through copper strips of suitable size.(ii) The internal electrical connection for measuring instruments would be through multi-stranded PVC insulated copper conductor cables of suitable size.(iii) The termination of incoming and outgoing cable into and from switchgear would be through properly crimped aluminumlugs of suitable rating incommensurate with that of switchgear.(iv)Cable glands would be provided for incoming & out going cables in panels.(v)The cost of fixing of the panel on suitable PCC (1:3:6) type C-1(using 20 mm graded black trap/basalt/granite stone aggregates) foundation as directed by Engineer-in-Charge is deemed to be included in the quoted rates by the contractor for the above item.(vi)The panel is to be fixed with Angle Iron Frame of size 50mm x 50mm x 6mm with bottam of panel having minimum 60cm height from existing ground/floor level. |
| 14 | Aluminium bus bar strips with proper colour code -04 No, 500 A cap, insulator, nuts bolts etc complete. |
| 15 | Indicator Lamp-01 Set (Set of three) |
| 16 | Incommer MCCB 4P250 amp with thermal magnetic release , 415V, 36 KA- 01 No (for Feeder panel) Make Legrand cat no-4220 49 or Havells cat no- IHLLSEE40250 |
| 17 | Outgoing, MCCB 4P125 amp with thermal magnetic release , 415V, 25 KA- 05 No (for Feeder panels of Md accn) Make Legrand cat no-4200 56 or Havells Cat No- IHTT1DBF0125 |
| 18 | MCBTPN 32A,10KA C CURVE - 01 Nos for Street lightMake Legrand |
| 19 | Digital Voltmeter 0-500 Vand Digital Ampmeter0-400 A.with selector switich Make-Legrand/Minilac |
| 20 | Connection with Aluminium bus bar strip duly insulated with coloured sleeves /stranded copper cable of suitable size with thimbles. |
| 21 | Taking down unserviceable street lightpanel and Supply, install, commissioning and testing of street light panel outdoor type for load upto 6 kW, three phase 415 V/440 Volts of size not less then 0.6 mtr x 0.6 mtr x 0.3 mtr , confirming to IEC 61439 with IP-65 protection made out of 3.15 mm thick CRCA sheet with locking arrangement and complete panel should be powder coated with having neoprene rubber gasket for sealing door, doors of the panel should be removable type,3 phindicators lamp etc with provision for Incomer MCB TPN 40 Amps, contactor rating 32 Amps with Analog type street light timer, control wiring with suitable size of copper wire the panel shall be mounted on 50mm x 50mm x 6mm MS angle iron and 60 cm above the normal ground level & embedded 30 cm below ground level in PCC foundation (1:2:4) type B 1, (20 mm graded stone aggregate) connect new UG cable for Incoming from LT panel cable shall enter through cable glands for safety of cable where enter through panel complete all as specified and directed. Make of Street light Panel - Havells cat no- IHXTS03060 or equivalentin L&T/Schneider/BCH |
| 22 | Taking down unserviceable street lightpanel and Supply, install, commissioning and testing of street light panel outdoor type for load upto 12 kW, three phase 415 V/440 Volts of size not less then 0.6 mtr x 0.6 mtr x 0.3 mtr, confirming to IEC 61439 with IP-65 protection made out of 3.15 mm thick CRCA sheet with locking arrangement and complete panel should be powder coated with having neoprene rubber gasket for sealing door, doors of the panel should be removable type,3 phindicators lamp etc with provision for Incomer MCB TPN 63 Amps, contactor rating 63 Amps with Analog type street light timer, control wiring with suitable size of copper wire the panel shall be mounted on 50mm x 50mm x 6mm MS angle iron and 60 cm above the normal ground level & embedded 30 cm below ground level in PCC foundation (1:2:4) type B 1(20 mm graded stone aggregate), connect new UG cable for Incoming from LT panel cable shall enter through cable glands for safety of cable where enter through panel complete all as specified and directed. Make of Street light Panel - Havells cat no- IHXTS09120 or equivalentin L&T/Schneider/BCH |
| 23 | Supply, laying, jointing, commissioning and testing XLPEinsulated screened PVC bedded, armoured,heavy duty underground electric cable in repair with stranded aluminium conductor 1100 volts grade confirming to IS-7098 (Part-I-1988) laid in trenches/ducts/wall / floor / pipes/ poles including cable glands and aluminium lugsof appropriate size, PVC sleeve etc complete all as specified and directed for following sizes . Make :- Havells / Gloster / Finolex / Polycab |
| 24 | 240 Sqmm 3.5 core |
| 25 | 185 Sqmm 3.5 core |
| 26 | 150 Sqmm 3.5 core |
| 27 | 70 Sqmm 3.5 core |
| 28 | 25 Sqmm 3.5 core |
| 29 | NOTE :- Earth work , bricks , riddled earth , GI pipe for protection of cable will be measured & paid under under relevant items of schdule . |
| 30 | Supply and errect in vertical position Steel tubular swaged poles,type 410 SP- 31 (09 mtr long) in repair with 300mm x 300mm x 6mm mild steel plate continiusly welded to pole, final taper plug, bolts,nuts and screws and making holes as per requirementall as specified including factory painted with two coats ofblack bituminous paint internally through out and externally for embeded portion and applying one coat fo red oxide primer, making 05 Nos strip each 30 cmhigh with super enamel paint ( Black and yellow) from ground level / coping upto 1.5 mtr, painting with two coats of aluminium paint for the remaining height complete all as specified and directed.Note :- PCC in foundation, copping, excavation and earth work shall be measured and paid separately under relevent items of sch. |
| 31 | Material and Labour in repair for Earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6 mm thick, buried directly in ground vertically (earth pit not less than 2.25 mtr deep below ground level) with top edge of the earth plate not less than 1.5 mtr below ground level , connected to 32mm x 6mm GI stripas earthling lead by means of blots and nuts check nuts and washers of galvanized iron and connected to main switch board including watering arrangement with PCC chamber , MS funnel, wire gauge.CI cover with frame , 50 MM dia GI pipe light grade for protection of wire/strip etc including necessary excavation in any type of strata , returning, fillingremoval of soil outside MD land ,filling ofcharcoal andsalt complete all as shown in electrical plate No. 3 of MES Sch Part I , connected to Earthing test point complete all as specified and directed on testing on completion. |
| 32 | Material and Labour for cleaning of MES electric supply installations/campus by surface dressing or trimming of natural ground to remove small unequalities not exc 15 cm deep (including removing vegetation/ shrubs/brush wood/under growth) and carrying away the rubbish to a distance of not exc 50 mtr away complete at an interval of every 30 daysforthe various sub stations complete all as specified and directed. Note: Spray of herbsitedeemed included in quoted rate. |
| 33 | Material and Labour forhardcore of gauge n.exc 63mm ,deposited, spread, and levelled in layers n.exc15 cm thickness (below or above ground level) ,water and rammedto a true shape with broken stone or boulders complete all as specified and directed. ( Sub Station Yard) |
| 34 | Material and Labour for detection of street lightLT UG cable fault with the help of cable faultdetecting machine with experinced engineer andhelper including necessary earth work complete & jointing the fautly cable with new joint , testing etc complete all as specified and directed.Note :- Cable joint kit will be measured and paid separately under relevent item of schedule . |
| 35 | Decarbonizing of LT indoor/outdoor Panel/feeder pillar box any type removing unserviceable MCCBs, burnt busbars, unserviceable indicator lamps, unserviceable Ammeter,unserviceable Volt meter , replacing burnt, damaged bus bar of any size and fixing proper hanging front and rear openings, welding of hinges including welding of brokieng MS sheet using extra sheetsreplace burnt thimbles with new existing size thimbles replacing with new MCCB,incluidng dismantling the existing connected cables and re-connecting the same cablescomplete all as specified and directed. Note : (i)MCCBs,Bus bars,indicator lamps,Ammeter, Volt meter, will be measured & paid separately as supply only . |
| 36 | Excavation in trenches not exceeding 1.5 mtr wide and not exceeding 1.5 mtr in depth for foundation of poles stays laying of electric cables, pipes etc and getting out in soft/loose soil complete all as specified and directed. |
| 37 | Ditto item no 13 but in hard/dense soil complete all as specified and directed. |
| 38 | Material and Labour for removing excavated material soil to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding1.5 mtr above the starting point complete all as specified and directed |
| 39 | Returning, filling in,including spreading, levelling watering and well ramming in layers not exceeding25cm in soft/loose soil complete all as specified and directed. |
| 40 | Material and Labour for riddled earth forcushioning to under ground electric cable including spreading , levelling and hand punning complete all as specified and directed.Note - Punned thickness shall only be measured & paid . |
| 41 | Material and Labour for road cutting / foot path and making good with PCC 1:3:6 TYPE C-2 ( using 40 mm graded stone aggregate ) of 150 mm thick complete all as specified and directed. |
| 42 | Supply and laying un-reinforced precast concrete cable cover LV, Type I, flat, size 250mm x 150mm x 40mmfor Under ground cable complete all as specified and directed. |
| 43 | Supply and laying GI tubes light grade, galvanized, 40 mm borein repair ,laid in trenches or under floor or fixed with poles/walls for protection of electric cable complete all as specified and directed. |
| 44 | Ditto item no -20 but 80 mm bore complete all as specified and directed. |
| 45 | Material and Labour for Plain cement concrete 1:3:6 (PCC) type C2 using 40mm graded stone aggregate for making foundation of Pole/stay assembly complete all as specified and directed |
| 46 | Material and Labour for Plaincement concrete 1:3:6 (PCC) type C1 using 20mm graded stone aggregate for making copings of Poles etc including dismantling the old coping from poles complete all as specified and directed. |
| 47 | Supply only straight through joint kit , heat shrinkable type suitable for LT UG electric cable 1100 volts grade of size25 Sqmm to 50 Sqmm 3.5 core / 4 core cable complete all as specified and directed. |
| 48 | Supply only straight through joint kit , heat shrinkable type suitable for LT UG electric cable 1100 volts gradeof size from 70 Sqmm to 120 Sqmm 3.5 core / 4 core cable complete all as specified and directed. |
| 49 | Supply only straight through joint kit , heat shrinkable type suitable for LT UG electric cable 1100 volts grade of sizefrom 150 Sqmm to 185 Sqmm 3.5 core / 4 core cable complete all as specified and directed. |
| 50 | Supply only straight through joint kit , heat shrinkable type suitable for LT UG electric cable 1100 volts grade of sizefrom 240 Sqmm to 300 Sqmm 3.5 core / 4 core cable complete all as specified and directed. |
| 51 | Supply and fixing MCCB, 4 pole, 36 KA breaking capacity, with Adjustable type, optimum 2.0, 315 amps, incl dismentling and taking down unsv one, making cutting of existing panel for fixing MCCB on suitable fitting , including fabrication work and make panel good and complete all as specified and directed.Make- Indoasian(optimum 2.0)/Legrand/L & T |
| 52 | Supply and fixing MCCB, 4 pole, 415 V, 16 KA breaking capacity,with Thermal magnetic release, optimum 1.1, 63 amps, incl dismentling taking down unsv one, making cutting of existing panel for fixing MCCB on suitable fitting and make panel good and complete all as specified and directed.Make- Indoasian/Legrand/L & T |
| 53 | Ditto as above item no -29 but of capacity 100 Amps complete all as specified and directed. Make- Indoasian/Legrand/L & T |
| 54 | Ditto as above item no- 29 but of capacity 125 Amps complete all as specified and directed. Make- Indoasian/Legrand/L & T |
| 55 | Ditto as above item no- 29 but of capacity 160 Amps complete all as specified and directed. Make- Indoasian/Legrand/L & T |
| 56 | Servicing of APFC panel cleaning, tightning of connections, setting programme, testing of CT\"S including caliberation of APFC panel and replacing unserviceable capacitors, capacitor contactor, breakers, power factor controller after servicing testing panel and achive power factor of 1.00 complete all as specified and directed. Note: Capacitors, capacitor contactor, power factor controller measered and paid separately. |
| 57 | Notefor item no 33 :(i)Quoted rate includes replacement of damaged panel locks as per existing as per site requirement. (ii)Painting of panels with mounting stand(with two coat of paint as specified by Engr in charge ) included in quoted rate . (iii) suitable size of lugs and cable gland for panel deemed to be included in quoted rate. (iv)Necessary MS sheet,Hingesand welding included in coated rate. (v) Rate includes cleaning of panel by using high speed air blower to remove dust. |
| 58 | Supply and fix in repair Power factor controllers (96x96), 5 steps,with timer, 415 volt, AC, 50 HZ power supply including suitable wiring complete all as specified and directed. Make: L&T Scheider/EPCOS |
| 59 | Supply and fix in repair Power factor controllers (144x144),8 steps,with timer, 415 volt, AC, 50 HZ power supply including suitable wiring complete all as specified and directed. Make: L&T /Scheider/EPCOS |
| 60 | Supply in repair and , test, commissioning of LT capacitor upto 5 KVAR to 15 KVAR , 440Volt of Heavy duty for non-linear loads up to 440 Vcylinderical type on existing APFC panel and necessary panel wiring , complete all as specified and directed. Make: For capacitorL & T /Legrand/Schneider |
| 61 | Ditto as above item no-36 but rating of 20 KVAR to 25 KVAR, 440 volt complete all as specified and directed.Make: For capacitorL & T /Legrand/Schneider |
| 62 | Supply in repair and, test, commissioning ofcapacitor duty contactor of capacity of 15 KVAr on existing APFC panel and necessary panel wiring complete all as specified and directed. Make L & T/Legrand /Schneider |
| 63 | Ditto as above item no -38 but of25 KVAR contactor complete all as specified and directed. Make L & T / Legrand /Schneider |