| 1 | Supplying, laying, jointing and testing and commissioning 120 sqmm, 3.5core XLPE insulated, screened, PVC bedded galvanised steel strip or wire armoured electric power cable heavy duty multi stranded aluminium conductor andPVC sheathed LT cable 1100 volts grade conforming to IS-7098 laid in trenches/ ducts/ fixed on poles/wall/laid under roads/paths/drain/culverts or passing through pipes complete all as specified and directed by Engineer-in-Charge. |
| 2 | Supplying, laying, jointing and testing and commissioning 95 sqmm, 3.5core XLPE insulated, screened, PVC bedded galvanised steel strip or wire armoured electric power cable heavy duty multi stranded aluminium conductor andPVC sheathed LT cable 1100 volts grade conforming to IS-7098 laid in trenches/ ducts/ fixed on poles/wall/laid under roads/paths/drain/culverts or passing through pipes complete all as specified and directed by Engineer-in-Charge. |
| 3 | Supplying, laying, jointing and testing and commissioning 50 sqmm, 3.5core XLPE insulated, screened, PVC bedded galvanised steel strip or wire armoured electric power cable heavy duty multi stranded aluminium conductor andPVC sheathed LT cable 1100 volts grade conforming to IS-7098 laid in trenches/ ducts/ fixed on poles/wall/laid under roads/paths/drain/culverts or passing through pipes complete all as specified and directed by Engineer-in-Charge. |
| 4 | Supplying, laying, jointing and testing and commissioning 25 sqmm, 4 core XLPE insulated, screened, PVC bedded galvanised steel strip or wire armoured electric power cable heavy duty multi stranded aluminium conductor andPVC sheathed LT cable 1100 volts grade conforming to IS-7098 laid in trenches/ ducts/ fixed on poles/wall/laid under roads/paths/drain/culverts or passing through pipes complete all as specified and directed by Engineer-in-Charge. |
| 5 | Supplying, laying, jointing and testing and commissioning 16 sqmm, 4 core XLPE insulated, screened, PVC bedded galvanised steel strip or wire armoured electric power cable heavy duty multi stranded aluminium conductor andPVC sheathed LT cable 1100 volts grade conforming to IS-7098 laid in trenches/ ducts/ fixed on poles/wall/laid under roads/paths/drain/culverts or passing through pipes complete all as specified and directed by Engineer-in-Charge. |
| 6 | Supplying, laying, jointing and testing and commissioning 10 sqmm, 4 core XLPE insulated, screened, PVC bedded galvanised steel strip or wire armoured electric power cable heavy duty multi stranded aluminium conductor andPVC sheathed LT cable 1100 volts grade conforming to IS-7098 laid in trenches/ ducts/ fixed on poles/wall/laid under roads/paths/drain/culverts or passing through pipes complete all as specified and directed by Engineer-in-Charge. |
| 7 | Supplying, laying, jointing and testing and commissioning 10 sqmm, 2 core XLPE insulated, screened, PVC bedded galvanised steel strip or wire armoured electric power cable heavy duty multi stranded aluminium conductor andPVC sheathed LT cable 1100 volts grade conforming to IS-7098 laid in trenches/ ducts/ fixed on poles/wall/laid under roads/paths/drain/culverts or passing through pipes complete all as specified and directed by Engineer-in-Charge. |
| 8 | Excavation in trenches, not exc 1.5 m wide and n. exc 1.5 m depth; or n exc 10 Sqm on plan and n exc 1.5 m in depth for foundations of poles, struts, stays etc. or layingunderground cable etc.in soft/loose soil,& getting out complete all as specified and directed by Engineer-in-Charge. |
| 9 | Returning, filling in, including spreading, levelling, watering and well ramming in layers n.exc 25cm thick complete all as specified and directed by Engineer-in-Charge. |
| 10 | Removal of excavated surplus soil to a distance n.exc 50m and depositing where directed at level not exceeding 1.5 m above the starting point complete all as specified & directed by Engineer-in-charge . |
| 11 | Supply and Laying DWCof pipe size 120 mm OD/ 93 mm IDfor cable protectioncomplete all as specified and directed. |
| 12 | Supply and Laying DWCof pipe size 50 mm OD/38 mm IDfor cable protectioncomplete all as specified and directed. |
| 13 | M & L forboring hole under road, pavement, hard standing by trenchless technology method for laying DWC pipe of outer dia upto 120mm suitable for cable passing without damaging Road / Plinth /Floor complete all as specifid. |
| 14 | M & L for 200 mm dia cable route indicator made of CI plate 8 mm thick with spike to angle iron 25 X 25 X 5mm, 60 cm long marked as LT/HT cable jointing on conductor coil plate complete including fixing and excavation in soft/loose/hard/dense soil, PVC embedded block size 300 X 300X 300 mm (1:3:6) type C-1 using 20 mm graded stone aggreggate complete all as specified and as directed. |
| 15 | Supply and erecting factory made 7 m long hot dip galvanised octagonal pole with 130 mm dia including 1.5 Mtr single Arm HDG OD-48.3 at bottom and 70 mm dia at top A/F made up of 4 mm thick HT sheet along with foundation type base plate of size 220X220X12 mm foundation bolt 4 nos of M20X750 high J type EN8 Grade with inbuilt junction box suitable for incoming 3 phase LT cable 16sqmm 4 core having 6A SP B class MCB fixed on bakelite sheet and stud type connector inside the pole, the pole shall be adequetly strengthened at the location of the door to compensate for the loss in section including excavation and RCC/PCC (1:2:4) type B1 for foundation and grouting the bolts as per manufactures instructions including marking pole numbers in letters and figures of size radium tape not less than 10cm height with red colour enamel paint complete all as specified and as directed. |
| 16 | S & F motion sensor based auto ON-OFF or dimming/brightness new generation energy saving & environmental friendly long life versatile pressure die cast aluminium IP-66 roadway luminaire 60 watt with heat resistant PC Cover ,better optics for uniform distribution street/Roadway luminaire, with driver complete fitting with all accessories and following specifications, complete all as specified and as directed :-(a) Lumen system efficacy of luminaire should be minimum 120 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 10°C to Plus 50°C (d) Power factor : Minimum 0.95 (e) THD : Max10%. (f) IP rating : Minimum IP66. (g) IK rating : Minimum IK07 (h) Built in potted LED Driver of the make as of the luminaire. (j) LED driver should be complete with all protections viz open/short circuit protection, over voltage protection, all as per standard design of manufacturer. (k) Surge protection 10 kV (inbuilt + extended) (l) CCT : 5700 K. (m) CRI : Morethan 70 (n) Lens - High Efficiency wide angle lens. (o) BIS Approved fixtures and driver (p) Rated life time : 50000 burning hrs @L70 (Average 10 to 12 hrs daily) Note :- Arm/Bracket for fixing of light will be measured and paid under Item No 15 above. |
| 17 | Supply, install, testingand commisioningof LT panel duly powder coated of suitable size outdoor cubical type factory made, weather & vermin proof made out of cold rolled close annealed sheet of 3.15 mm thick powder coatingwith bottom frame made out of angle MS 50mm x 50mm x 6mm and 600mm long 4 legsgroutedin PCC 1:2:4 type B1 using 20mm graded stone aggregate blocks of size 30cm x 30cm x 60cm and 100mm thick PCC (1:2:4) type B1 floor over 100mm thick sub base of brick hardcore extended 100mm on all sides below panel body complete and suitable for 415 Volt AC 3 phase, 4 strip having insulated Copper bus bar 400 Amps 9 way from pole with openable double shutter on both sides (rear and front side) with locking arrangment duly pre-wired with suitable size of copper conductor cable fitted with Incomingproper size copper lugs/thimbless and connecting the incoming and outgoing MCCBs with suitable size strip duly bended and drilled and fixed with nuts, bolts & washers from bus bar to MCCBs etc duly fitted with and including the following accesories & all connected iems complete.Incoming (i) Microprocessor MCCB 250 Amps, four pole with Adjustableoverload short circuit ground fault, 415 V AC supply,having rupturing capacity 25 KA-01 NoOutgoing(ii) MCCB 63Amps,Four pole with Adjustable thermal and fixed magnetic release, 415 volts having rupturing capacity 16 KA- 6 Nos (iii)MCCB 40Amps,Adjustable thermal and fixed magnetic release, 415 volts having rupturing capacity 16 KA- 1 No.(iv) MCB TPN25 Amp10 KA -02 Nos(iv) Indicating lamps set RYB - 01 Set (v) DigitalAmp Meter0- 250 A withCT , Digital Voltmeter 0- 500 V |
| 18 | Supply, install, testing and commisioningof LT panel duly powder coated of suitable size outdoor cubical type factory made, weather & vermin proof made out ofcold rolled close annealed sheet of 3.15 mm thickpowder coatingwith bottom frame made out of angle MS 50mm x 50mm x 6mm and 600mm long 4 legsgroutedin PCC 1:2:4 type B1 using 20mm graded stone aggregate blocks of size 30 cm x 30 cm x 60 cm and 100mm thick PCC (1:2:4) type B1 floor over 100mm thick sub base of brick hardcore extended 100mm on all sides below panel body complete and suitable for 415 Volt AC 3 phase, 4 strip having insulated Copper bus bar 250 Amps 8 way from pole with openable double shutter on both sides (rear and front side) with locking arrangment duly pre-wired with suitable size of copper conductor cable fitted with Incomingproper size copper lugs/thimbless and connecting the incoming and outgoing MCCBs with suitable size strip duly bended and drilled and fixed with nuts, bolts & washers from bus bar to MCCBs etc duly fitted with and including the following accesories& all connected itemscomplete .Incomming(i)Mircroprocessor MCCB 160 Amps, four pole with Adjustableoverload short circuit ground fault, 415 V AC supply,having rupturing capacity 25 KA-01 No Out going(ii)MCCB 40Amps,Adjustable thermal and fixedmagnetic release, 415 volts having rupturing capacity 16 KA- 04 Nos(ii) MCCB4 pole 25 Amp 16 KA -02 No, (iii) MCB SPN 25 Amp -01 Nos(iv) Indicating lamps set RYB - 01 Set (v)DigitalAmp Meter0- 160 A withCT , Digital Voltmeter 0- 500 V |
| 19 | S&F on pole/wal/in panel, Stainless Steel Sheet enclosure Bus bar chamber 3.15 mm thick consisting 04 pole 100 Amp 415 volts copper bus bar 4 way control with MCCB 100 Amp ,Adjustable thermal and fixed magnetic release, 415 volts having rupturing capacity 25 KA-4 Pole -01 No as out going and incoming connecting cables including mounting on angle iron frame made using angle iron 50 mm x 50 mm x 6 mm of new/existing cables withsuitable sizes aluminum thimbles.as per directed by Engr -in Charge. |
| 20 | M & L for Earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6 mm thick burried in ground (earth pit not less than 2.25 Mtr deep below normal ground level with top edge of the plate not less than 1.5 Mtrs below normal ground level, connecting to the Galvanised iron earth lead 25 x 4 mm size by means of bolts, nuts check nuts and washers of earth lead protection by provision of GI medium grade pipe 40 mm bore including provision of concrete pit in PCC (1:2:4) type B1 using 20mm graded stone aggregate with 40mm thick cover of RCC (1:2:4) reinforced with XPM (wieght not less than 4gs/Sqm) and frame of angle iron 25mm x 25mm x 6mm with lugs 02 Nos and with 6 mm dia MS bar handle made to shape, GI light grade 20mm bore pipe for watering perforated at the bottom 1.75 meter long placed on top edge of earth plate common salt and charcoal filling test point made out of 40mm x 8 mm FI with fixing arrangements, funnel, wire mesh and earth work in hard dense soil, returning filling in and removal of surplus soil to a distance not exceeding 50 Mtrs all as per electrical Plate No.3 ofPart I and connecting to earth test point all as specified or indicated including testing on completion. |
| 21 | M & L for Earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6 mm thick burried in ground (earth pit not less than 2.25 Mtr deep below normal ground level with top edge of the plate not less than 1.5 Mtrs below normal ground level, connecting to the Galvanised iron earth lead 4.0 mm size by means of bolts, nuts check nuts and washers earth lead protection by provision of GI medium grade pipe 15 mm bore including provision of concrete pit in PCC (1:2:4) type B1 using 20mm graded stone aggregate with 40mm thick cover of RCC (1:2:4) reinforced with XPM (wieght not less than 4gs/Sqm) , GI light grade 20mm bore pipe for watering perforated at the bottom 7.5 meter long placed on top edge of earth plate common salt and charcoal filling test point , funnel, wire mesh and earth work in hard dense soil, returning filling in and removal of surplus soil to a distance not exceeding 50 Mtrs all as per electrical Plate No.3 of SSR Part I and connectingto earth test point all as specified or indicated including testing on completion |
| 22 | Boring of holes under road/pavement/hard standing or any other situation by manual mean and includingpassing GI pipe 80/50mm bore and making good both the ends complete .Note : Pipe and cable will be measured and paid separately |
| 23 | Supply and fixGI pipe 80 mm bore light grade for protection of cable including provision of clamps, nut, bolts etcrequired for fixing pipe along pole / wall / laid under the road / laid under the floor or in trenches complete. |
| 24 | Supply and fix GI pipe 50 mm bore light grade for protection of cable including provision of clamps, nut, bolts etcrequired for fixing pipe along pole / wall / laid under the road / laid under the floor or in trenches complete. |
| 25 | M & L PVCinsulated,PVC sheathed Copper conductorelectric cable 1.5 Sq mm 3Core 1100 volts gradefor pole box to street light fitting Complete all as Specified and directed. |
| 26 | Dismanting ofACSR conductor/AAC conductor of any size and any type Complete all as Specified. |
| 27 | Dismanting of cross arm, clamps , bracing etc of MS section Complete all as Specified and directed. |
| 28 | Dismanting of insulator any type and size Complete all as Specified and directed. |
| 29 | Dismanting of old PCC Pole with and including required excavation/returning refilling of Soil/PCC found at site and making the surface ground even upto entire satisfaction of Engr-in-Charge. |
| 30 | S & F of Automatic Street Light Control Switch using Infrared Sensor based Nature Switch for automatic switching of street lights. Nature Switch operation should be based on Natural Lux Level. Required Illuminance level for switching On is <= 30 Lux and for switching OFF >=10 Lux. The Circuit should be suitable enough to take Three phase load of 12 KW with 3 nos Contactors, 3 nos incoming MCBs& 3 nos Outgoing MCBs of 32-40 Amps each & circuit wiring (Copper) of min 10 sqmm. complete all as specified and directed by Engineer-in-Charge. |
| 31 | Dismanting of GI bracket 1.2 Mtr long 40 mm dia with street light fitting complete all as specified and as directed.Note : Oldstreet light retrieved from poles to be deposit in MES Store. |
| 32 | M & Lfor repair of damange portions duringlaying of LT cable, including replant of existing arboriculture which disturbed during layingand repairs the same and making the good disturbed surfaces of wallin CM 1:3 with white wash or existing colour, complete all as specified anddirecedby the Engineer in charge. |