| 1 | Disconnecting / taking down carefully existing unserviceable LT panel board / feeder pillar boxany type and capacity including all control switches, fitting and fixtures from different location complete all as specified and directed by the Engr-in-Charge. |
| 2 | Supplying, installing, testing & commissioning out door type cubical panel board outer shell made out of3.15 mm thick MS sheet including door and inner shell made out of 2 mm thick MS sheet and MS angle section 50x50x6 mm mounted on PCC 1:2:4 type B-1 platform 60 cm aboveand 45 cm below the ground level,frame factory fabricated with front & back openable, double door system and cable alloy (Each door hinged with body at 3 places with body and hinges should be welded with body and door) lockable/open able by Keyshaving chromium plated 19 mm dia fancy lock, “U” type gasket shall be used to make the outer shell completely vermin proof suitable for 3 phase 4 wire 415 Volt, 50 Hz, tested at factory approved from CPRI factory fabricatedhaving modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns provided with suitable gasket to make it dust/vermin proof and general construction confirming to IS:8623/93 comprising of the following :-system complete suitable for 3 phase 4 wire 415 Volt, 50 Hz, (for billets) a)Aluminium bus bar 600 Amps cap 4 wire fixed on insulator not less than 1.0 mtr long bus bar -1 set(b) Incoming MCCB 315 Amps 4 pole 415 Volts AC with thermal magnetic 36 KA, Ics=100%, Icu class-2 front face isolation with positive break indication with double break contacts with spreader and phase barrier complete all as directed. - 1 Nos.(c) Outgoing MCCB 160 Amps 4 pole 415 Volts AC with thermal magnetic 25 KA,with double break contacts with spreader and phase barrier complete all as directed. -1 Nos(d) Outgoing MCCB 100 Amps 4 pole 415 Volts AC with thermal magnetic 25 KA,with double break contacts with spreader and phase barrier complete all as directed. -2 Nos |
| 3 | (e) Outgoing MCCB 63 Amps 4 pole 415 Volts AC with thermal magnetic 16 KA,with double break contacts with spreader and phase barrier complete all as directed. - 2 Nosf) Digital Ammeter 0-500 A of size 96sqmm with selector switch-01 No.g) Digital Volt meter 0-500 V of size 96sqmm with selector switch-01 Noh) Indicator Lamp RYB 22.5mm dia LED type 240 volts AC with incoming including back up protection by 2 Amp MCB RYB with holder-01 set of threej) CT Coils of suitable ratio-01 Set. Note :-(i)The quoted rate shall includes minor items such as lugs, nuts & bolts, washers, top insulators, sleeves, provision of extra holes in bus bar etc.(ii) All internal wiring shall be done with suitable size of PVC insulated solid copper conductor FRLS cable conforming toIS-694.(iii) Panel drawing shall be got approved before placing of orderfrom Engr-in-Charge/GE.(iv)The bus connection for cable from main bus bar to outgoing MCCB will be connected through suitable rating bus bar strip type duly insulated.(vi) The Panel shall be surrounded with 9 inch brick wall upto 0.5 mtr height all around the panel and blank portion between panel and wall shall be filled with PCC 1:2:4incl masonry work leaving ducts for cables complete all as directed.(vii) All MCCBs have Ics= 100% Icu. |
| 4 | Supply, install commissioning and testing of cubical outdoor feeder pillar box of size 1x.8x.3 meter, platform mounted factory made totally enclosed dust and vermin proof (protection class IP-54) single shutter front opening with locking arrangement complete made of angle iron 50 mm x 50 mm x 6 mm thick frame work and 3.15 mm thick MS sheet duly painted with powder coated paint over a coat of red oxide primer over outside and inside complete.The panel board shall be suitable for 300 Amps capacity 415 volt 50 Hz, 3 phase, 4 wire system and includes necessary size of cable glands and following accessories :- (Sun shelter ParkingTech Area FIS.(a)4 way TPN DBs DPX 160 Amps MCCBas incomer and SP/TP MCBs as outgoing.(b)MCCB four pole 125 Amps, 36 KA 415 volts -01 No(c)MCB four pole 63 Amps, 36 KA 415 volts -01 No(d)MCB Single Pole 63 Amps -04 Nos(e) MCB single pole 6-32 Amps -08 Nos(f)Phase indicating lamp RYB neon type (Set of three ) -01 Set (g)Voltmeter Digital type 0-500 Volts capacity with selector switch.(h) Ammeter digital flush type 0-300 Amp capacity with selector switch and CT coils - 01 Nos |
| 5 | Note :-(i)The quoted rate shall includes minor items such as lugs, nuts & bolts, washers, top insulators, sleeves, provision of extra holes in bus bar etc.(ii) All internal wiring shall be done with suitable size of PVC insulated solid copper conductor FRLS cable conforming toIS-694.(iii) Panel drawing shall be got approved before placing of orderfrom Engr-in-Charge/GE.(iv)The bus connection for cable from main bus bar to outgoing MCCB will be connected through suitable rating bus bar strip type duly insulated.(vi) The Panel shall be surrounded with 9 inch brick wall upto 0.5 mtr height all around the panel and blank portion between panel and wall shall be filled with PCC 1:2:4incl masonry work leaving ducts for cables complete all as directed.(vii) All MCCBs have Ics= 100% Icu... |
| 6 | Supplying, installing, testing & commissioning out door type cubical panel board outer shell made out of3.15 mm thick MS sheet including door and inner shell made out of 2 mm thick MS sheet and MS angle section 50x50x6 mm mounted on PCC 1:2:4 type B-1 platform 60 cm aboveand 45 cm below the ground level,frame factory fabricated with front & back openable, double door system and cable alloy (Each door hinged with body at 3 places with body and hinges should be welded with body and door) lockable/open able by Keyshaving chromium plated 19 mm dia fancy lock, “U” type gasket shall be used to make the outer shell completely vermin proof suitable for 3 phase 4 wire 415 Volt, 50 Hz, tested at factory approved from CPRI factory fabricatedhaving modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns provided with suitable gasket to make it dust/vermin proof and general construction confirming to IS:8623/93 comprising of the following :- (Dutt Mess)a) Aluminium bus bar 600 Amps cap 4 wire fixed on insulator not less than 1.0 mtr long bus bar -1 set(b) Incoming MCCB 250 Amps 4 pole 415 Volts AC with thermal magnetic 36 KA, Ics=100%, Icu class-2 front face isolation with positive break indication with double break contacts with spreader and phase barrier complete all as directed. - 1 Nos.(c) Outgoing MCCB 100 Amps 4 pole 415 Volts AC with thermal magnetic 25 KA,with double break contacts with spreader and phase barrier complete all as directed. -2 Nos (d) Outgoing MCCB 63 Amps 4 pole 415 Volts AC with thermal magnetic 16 KA,with double break contacts with spreader and phase barrier complete all as directed. - 1 Nos |
| 7 | e) Digital Ammeter 0-500 A of size 96sqmm with selector switch-01 No. f) Digital Volt meter 0-500 V of size 96sqmm with selector switch-01 Nog) Indicator Lamp RYB 22.5mm dia LED type 240 volts AC with incoming includin back up protection by 2 Amp MCB RYB with holder-01 set of three.h) CT Coils of suitable ratio-01 Set.Note :-(i)The quoted rate shall includes minor items such as lugs, nuts & bolts, washers, top insulators, sleeves, provision of extra holes in bus bar etc.(ii) All internal wiring shall be done with suitable size of PVC insulated solid copper conductor FRLS cable conforming toIS-694.(iii) Panel drawing shall be got approved before placing of orderfrom Engr-in-Charge/GE.(iv)The bus connection for cable from main bus bar to outgoing MCCB will be connected through suitable rating bus bar strip type duly insulated.(vi) The Panel shall be surrounded with 9 inch brick wall upto 0.5 mtr height all around the panel and blank portion between panel and wall shall be filled with PCC 1:2:4incl masonry work leaving ducts for cables complete all as directed.(vii) All MCCBs have Ics= 100% Icu. |
| 8 | Supply & fixing GI tubing lightgrade 80 mm bore on poles, under floors, road crossing etc all as reqd at site complete all as specified and directed by the Engr-in-Charge. |
| 9 | Supply & fixing GI tubing lightgrade 50 mm bore on poles, under floors, road crossing etc all as reqd at site complete all as specified and directed by the Engr-in-Charge. |
| 10 | Taking out unserviceable over head ACSR conductor any size complete all as specified and directed by the Engr-in-Charge. |
| 11 | Supply, Laying, connecting, testing XLPE cable underground PVC insulated and over all sheathed with aluminium conductor heavy duty 1100 volts grade laid in trenches, floors, ducts passing through pipe forroad crossing etc of the following sizes :- Note: Excavation, earth work, brick protection sand cushioningand GI pipe etc shall be measured & paid separately. |
| 12 | Cross sectional area 35 Sqmm 3 ½ core |
| 13 | Cross sectional area 70 Sqmm 3 ½ core |
| 14 | Cross sectional area 95 Sqmm 3 ½ core |
| 15 | Cross sectional area 120 Sqmm 3 ½ core |
| 16 | Cross sectional area 240 Sqmm 3 ½ core |
| 17 | S & F of Cable jointing kit suitable for 1.1 KV grade cable end termination, heat shrinkable type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 25 to70 sq mm complete all as specified and directed by the Engr-in-Charge. |
| 18 | S & F of Cable jointing kit suitable for 1.1 KV grade cable end termination, heat shrinkable type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 70 to150 sq mm complete all as specified and directed by the Engr-in-Charge. |
| 19 | Excavation in trenches n.exc 1.5 mtr wide and n.exc 1.5 mtr deep in loose / soft soil and getting out for under ground cable / erection of poles, stays etc complete all as specified and directed by the Engr-in-Charge. |
| 20 | Returning, filling in including spreading, levelling, watering and well ramming in layers n.exc 25 cm complete all as specified and directed by the Engr-in-Charge. |
| 21 | Removing of excavated material n, exc 50 metre away and depositing where directed at a level n, exc 1.5 mtr above the starting point complete all as specified and directed by the Engr-in-Charge. |
| 22 | Supply and laying Un-reinforced precast concrete cable cover ,class LV,type-1 size 300X180X40mm Complete all as specified and directed by the Engr-in-Charge. |
| 23 | M&L for Plain Cement Concrete 1:4:8 type D-2 using 40mm graded aggregate, mechanically crushed stone for mass filling in polepit and foundation etc including provision of necessary form work to achieve fair finished surfaces complete all as specified and directed by the Engr-in-Charge. |
| 24 | M&L for Plain Cement Concrete 1:3:6 type C-1 using 20mm graded crushed stone aggregate as inpole foundation, coping, stay pits etc including provision of necessary form work to achieve fair finishes surfaces,complete all as specified and directed by the Engr-in-Charge. |
| 25 | Disconnecting & taking out defective under ground cable from trenches, pole, pipe, floor, wall etc locate the fault, rectify the defect and relaying the XLPE cable under ground PVC insulated and overall sheathed aluminium conductor heavy duty 1100 volts/11000 volts connecting and testing for any size complete as directed by Engineer-in-Charge.Note : Excavation, earth work, brick protection sand cushioningand GI pipe etc shall be measured & paid separately. |
| 26 | S & F cable route indicator made out of 25 x 25 x 3 mm angle iron, 300 mm long embedded in PCC block of suitable size with moulded letterLT CABLEsuitably inscribed on CI circular plate 8 mm thick 100 dia complete incl necessary PCC 1:3:6, type C-2 (using 40 mm graded aggregate)block of suitable size and necessary earth work and excavation complete all as specified and directed by the Engr-in-Charge. |
| 27 | Taking out Unserviceable earthing complete all as specified and directed by the Engr-in-Charge. |
| 28 | M & L for earthingcomplete with galvanized steel earth plate electrode60 x 60cm x 6 mm thick buried directly in ground vertically to a depth not less than 2.25 mtr deep below GL with top edge of the plate not less than 1.5 metre below normal GL and connected to earth plate surrounded by 15 cm thick packed layers of charcoal dust and common salt and connected to earth lead galvanised iron strip 25×4mm by means of bolts, nuts, check nuts and washers of galvd iron or steel and thimbles and other end of the earth wire connected to DB and protected by galvd iron or steel pipe light grade 15 mm bore and water pipe 20mm bore GI light grade with funnel and wire mesh, including all necessary excavation and earth work PCC chamber in cement concrete 1:3:6 type C-2 and RCC cover and all as shown in electrical plate No 3 of MES schedule Pt I of2009 complete all as specified and directed by the Engr-in-Charge. Note : RCC pit cover shall be pre-cast of RCC (1:2:4) type B-I , 80mm thick reinforced with XPM weighting not less than 4 KG/sqmmin lieu of CI cover. |
| 29 | Taking out Unserviceable DPX distribution Board any type/capacity including removal of unserviceable cable connections complete all as specified and directed by the Engr-in-Charge. |
| 30 | Supply and fixing 4 way TPN DBs VTPN DPX 160 Amps MCCBas incomer and SP/TP MCBs complete all as specified and directed by the Engr-in-Charge. |
| 31 | Supply and fixing MCCB four pole 125 Amps, breaking capacity 36 KA 415 volts complete all as specified and directed by the Engr-in-Charge. |
| 32 | Supply and fixing 6 wayDBs VTPN DPX 160 Amps MCCBas incomer and SP/TP MCBs complete all as specified and directed by the Engr-in-Charge. |
| 33 | Supply and fixing MCCB four pole 160 Amps, breaking capacity 36 KA 415 voltscomplete all as specified and directed by the Engr-in-Charge. |
| 34 | Supply and fixing MCB single pole 6-32 Amps breaking capacity 10/16KA complete all as specified and directed by the Engr-in-Charge. |
| 35 | Supply and fixing MCB single pole 40-63 Amps breaking capacity 10/16KA complete all as specified and directed by the Engr-in-Charge. |
| 36 | Supply and fixing MCB triple pole 63 Amps breaking capacity 10/16KA complete all as specified and directed by the Engr-in-Charge. |
| 37 | S & Frigid non metallic PVC conduit 25 mm exclusives of boxes but incl all Tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles and pipe hooks etc complete all as specified and directed by the Engr-in-Charge. |
| 38 | Taking down carefully the existing aluminium/copper point sun Main wiring of any size and capacity and type by disconnecting from the either terminals complete with switches, sockets, ceiling rose, regulators etcby unscrewing and taken away from site complete all as specified and directed by the Engr-in-Charge.Note : (i) Old dismantled wiring and accessories will be contractors property and credit will be charged against schedule of credit. |
| 39 | M & L for sub main wiring with two single core FRLS, PVC insulated, stranded, unsheathed cable copper conductor with size 06 Sqmm and drawing through& including Non metallic PVC conduit concealed in wall including earth continuity conductor of size 06 Sqmm PVC insulated unsheathed stranded copper conductor cable and connected to earth dolly to be drawn in concealed PVC conduit including connecting to main board complete all as specified and directed by Engineer-in-Charge.Note:- PVC Conduit will be measured and paid separately. |
| 40 | M & L for sub main wiring with two single core FRLS, PVC insulated, stranded, unsheathed cable copper conductor with size 04 Sqmm and drawing through& including Non metallic PVC conduit concealed in wall including earth continuity conductor of size 04 Sqmm PVC insulated unsheathed stranded copper conductor cable and connected to earth dolly to be drawn in concealed PVC conduit including connecting to main board complete all as specified and directed by Engineer-in-Charge.Note:- PVC Conduit will be measured and paid separately. |
| 41 | Supply and fixing MCB SPN 6-32 Amps breaking capacity 10/16KA complete all as specified and directed by the Engr-in-Charge. |
| 42 | Supply and fix LED post top lantern light fitting 25 watts complete with all accessories complete all as specified and directed by the Engr-in-Charge. |
| 43 | Supply and fix LED post top lantern light fitting 40watts complete with all accessories complete all as specified and directed by the Engr-in-Charge. |
| 44 | S&F in repair Cable junction box with provision for one No MCB SPN and one MCB single pole IP 66 Halogen free and weather proof including for outdoor installation(with metric knockouts for cable entry- Black colour) cable size 10/16sqmm, Box dimensions- 200x160x98mm complete including taking out of loop of cable from ground by necessary excavation earthwork complete all as specified and directed by the Engr-in-Charge. |
| 45 | Supply and Fixing GI tubing Medium grade 40mm dia along the wall/in trenches/in duct/in culvert/road crossing and including provisioning of suitable mild steel flat iron clamps and bolts, nuts and double washers etc for holding of GI pipe alongwith poles including taking out old broken Gi pipes, complete all as specified and as directed by Engr-in-Charge. |
| 46 | Supply and fixing Indus series Powder coated pressure die cast alluminium compact high power LED street light fittings with heat resistant toughned glass with lense having36 Watt including provisioning of suitable mild steel flat iron clamps and bolts, nuts and double washers etc complete all as specified and as directed by Engr-in-Charge. Note :(i) Any touch up of the existing surface due to changing of fittings shall be done by contractor with similar surface finish without extra cost to the department. |
| 47 | Supply and laying & testing UG cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (Heavy duty) 1100 Volts grade with stranded aluminium conductor of size 10 sq mm, 4 core, complete including disconnectingall as specified and directed by Engr-in-Charge. |
| 48 | Taking out of old serviceable / unserviceable PVC under ground LTof any size and type fixed on pole, wall or laid in floors, trenches, across road crossing etc ,including taking out of cable covers of precast PCC / RCC slab or brick cover etc |
| 49 | Supply and laying of DWC (Double Wall Corrugated) HDPE Pipe, ISI Marked IS 16205 Part-II, of outer dia of 63 mm and inner dia 50 mm with smooth internal and profiled external surface for non pressure under ground cable including all connected accessories like coupler, \"O\" Ring etc, for protection of cablecomplete all as specified and as directed. Make: Rex-Polyextrusion/Gemini |
| 50 | Supply & fixing Sub main wiring with two single core PVC insulated unshesthed cable copper conductor(FRLS-H) of size 4.0 sqmm multistrandedand one run of 4.0sqmm PVC insulated unsheathed copper conductor(FRLSH) as earth continuty conductor drawing in and including non-metalic PVC rigid conduit 25mm dia ISI marked with all conduit accessories concealed in wall, cutting of chases in walls, floors, ceilings, beams etc and making good the disturbed surfaces as directed including taking down old unservicable wiring complete all as specified and directed.(i) Any touch up of the existing surface due to changing of fittings shall be done by contractor with similar surface finish without extra cost to the department. |