| 1 | RMO of D.G. sets, Mechanical ventilation , Lift pressurization ,common area lighting, fire alarm system and fire fighting system and basement storm water pumps sets& clear water booster pump setsand compound/street lighting and dewatering pump sets etc. as per inventory andterms & conditions attached. (i) Pump Operator cum DG set operators Gr-II-- 3 Nos(1No round the clock)(ii) Wireman Gr-I -- 1 Nos( 1No in General shift ) (iii)Khallasi Gr-III- 2 Nos(1No each in morning and evening shift) Note:- The agency shall provide the Tower Wagon in the contract period for maintenance of compound lightings ofthis housing within the qouted rate. No extra payment for the same will be entertained by thisoffice . |
| 2 | Providing lift operators for rescue & coordinationwith OEM of lift as per inventory and terms & conditions attached.a) lift rescue Operator Gr-II -3 No. (1 No. round the clock). |
| 3 | Dismantling and repairingi/c S/R of following worn out parts of existing 20 HP clear water pumpof kirloskar make suitablefor operationon 415 volts , 3 phase ,50 hz ,AC supplyi/c re-assembling/re-installation the same, connection with suction and delivery line, valves, testing etc. completed as reqd (i/c Rebate on dismantle materials):- (i) S/R of Pump shaft- 1 No. |
| 4 | (ii) S/R of Bal bearing - 2 Nos. |
| 5 | (iii) S/R of Gland plate- 1 Set |
| 6 | (iv) S/R of Gland guide bush- 1 set . |
| 7 | (v) S/R of Neck Ring- 1 set . |
| 8 | (v) S/R of Gland sleeve-1 set . |
| 9 | Dismantling and rewindingi/c S/R of following worn out parts of existing 20 HPkirloskar make Induction motor(for clear water) i/c re-assembling/re-installation the same, connection with suction and delivery line, valves, testing etc. completed as reqd(i/c Rebate on dismantle materials):- (i) Rewinding of 20 HP motor - 1No. |
| 10 | (ii) S/R of Connection plate - 1 No. |
| 11 | (iii) S/R of Cooling fan- 1 No. |
| 12 | (iv)S/R of ball bearing - 2 Nos. |
| 13 | Servicing of 320KVA DG set (Kirloskar make engine)) model no. DV8TAGI i/c supply and replacement of following items (i/c Rebate on dismantle materials):-a) B\" Check Kit- 1 Kitb)Engine oil- 50ltrc) Hose pipe- 1 Kit d) Radiator Descaling- 1 Job e) S/R of control unit -1 no. |
| 14 | Supply & replacement of faulty control card of 320 KVA DG set i/c testing & commissioning etc complete as required. |
| 15 | Servicing of 82.5 KVA D.G. set (Ashok leylandmake engine) model no. AL4CTIDG3i/c supply and replacement of following items (i/c Rebate on dismantle materials):-a) B\" Check Kit- 1 Kit b)Engine oil- 15 ltrc) Hose pipe- 1 Kit d) Radiator Descaling- 1 Job |
| 16 | Servicing/repairing of 100 HP Fire Diesel engine (Kirloskar make engine) i/c supply and replacement of following items i/c testing etc complete as required(i/c Rebate on dismantle materials):-a)S/R of Mobile Oil Filter -1 No.b) S/R of Fuel Filter -1 set.c) S/R of Air cleaner filter-1 setd) S/R of Coolant-5 ltre) S/R of Battery terminal & lead- 2 Nof)S/R ofEngine oil-30 ltrg)S/R of fuel pump i/c calibration and repairing og governor,nozzle pumps,injectors etc as required--1 Job |
| 17 | Dismantling and rewinding of5 HPcapacity dewatering pump setkirloskar makesuitable for 3 phase 415 volts 50 Hz AC supply and duly varnishing baking , to &fro cartage chargesi/c S/R of ball bearing,impeller nuts & mechanical seal, reassembling and testing etc as regd. |
| 18 | Supplying, replacement,Testing and commissioningof LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85% ,Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV withShort & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED,Driver & electrical circuitary), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K/6000°K/6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/Embossing/ Screen printing on housing. complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast / Extruded aluminium Body (Thickness ≥ 1.20 mm) a) 18- 22 watt 4 ft LED batten light |