| 1 | Supplying and drawing 3 x 1.5 sq.mm sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/recessed steel/ PVC conduit as required. ( for pole wiring ) |
| 2 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)a) 6 way, Double door |
| 3 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)a) 8 way, Double door |
| 4 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) a) 4 way (4 + 12), Double door |
| 5 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. a) Single pole |
| 6 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. b) Double pole |
| 7 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 8 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 9 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 10 | Providing and fixing 6 SWG dia G.I. wire on surface or in recessfor loop earthing as required. |
| 11 | Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required. |
| 12 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. Upto 35 sq. mm |
| 13 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. Above 35 sq. mm and upto 95 sq. mm |
| 14 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.(3.5 x 25 sq. mm (28mm) |
| 15 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.(3.5 x 50 sq. mm (35mm) |
| 16 | Providing, laying and fixing 100mm dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required |
| 17 | Supplying and Laying of size 63 mm dia(OD-63 mm & ID-51 mm nominal) DWC HDPE pipe ISI marked along with all accessories like socket,bend,couplers etc.conforming to IS 14930, Part II completed with fitting and cutting jointing etc.direct in ground(75 cm below ground level)including excavation and refilling the trench but excluding sand cushioning and protective covering etc, complete as required |
| 18 | Installation, testing and commissioning of pre-wired, fluorescent fitting / compact fluorescent fitting of all types, complete with all accessories and tube etc. directly on ceiling/ wall, including connection with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required. |
| 19 | Earth work in excavation by mechanically means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth,1.5m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth, lead up to 50 m and lift upto 1.5 m, disposed earth to be levelled and neatly dressed. All kinds of soil ( .70 mtr width X .70 mtr length X 1 mtr depth =0 .49 cum for each pole) |
| 20 | Providing and laying in position specified grade of reinforcedcement concerte, excludilng the cost of centering ,shuttering, finishing and reinforcement-all work up to plinth level:1:1.5:3 ( 1 cement: 1.5 coarse sand: 3 graded stone aggregate 20 mm nominal size)( .60 mtr width X .60 mtr lenth X 1.6 mtr depth = .576 cum for each pole) |
| 21 | Centering and shuttering including stutting, propping etc. and removal of form of : Foundations, footings, bases of columns, etc. for mass concrete ( for one side .60 mtr width X 1.60 mtr lenth = .96 sqmtr for four sides .96x4 = 3.48 sqmtr for each pole) |
| 22 | Steel reinforcement for R.C.C. work including straightening , cutting, bending, placing in position and binding all complete above plinth level. (Thermo Mechanically Treated bars)a) 12 mm steel for vertical of 08 nos x 1.6 mtr lenth = 12.8 mtr Weight 12.8 x 0.88 kg/mtr = 11.264 kg b) 08 mm steel for horizontal of 06 nos x 2.5 mtr lenth = 15 mtr Weight 15 x 0.39 kg/mtr = 5.85 kg Total weight for each pole a + b = 17.11 kg |
| 23 | Supplying and errection ofHot dip galvanised 7 mtr GI octagona l(8 side) pole with 01 mtr bracket, Material of Octagonal pole-Grade ISH430LA as per IS:5986:2017 latest,No of section (in Nos.) -01,Cross section of Octagonal pole (no of sides) -8 sided polygon,Internal distance between parallel faces at the base of pole (in mm)-130,Internal distance between parallel faces at the top of pole (in mm)-70, Octagonal pole sheet thickness (in mm) -3 mm,Type of welding-Seamless Single longitudinal Saw weld (No circumference weld allowed), No of longitudinal welds (in Nos-01 Nos, Metal protection treatment of fabricated mast section-Hot dip Galvanised, as per IS:4759 latest: 460 g/m2, Luminaire carriage / brackets -Fabricated suitably and hot dip galvanized for fixing and holding, required no. of light fixtures, Door opening on base of the pole (opening permits clear access to equipment like MCB, Switches, cables, etc.-Door opening: 500 mm height from base plate, Size: 100 mm x 500 mm with Gasket, Type of locking arrangement for door-Pad lock with key,Base plate material-Grade: E250, Quality:BR (as per IS:2062:2011 latest), Base plate size - ( Length in mm x Width in mm x Thickness in mm)-200x200x12, Necessary accessories on each pole -Suitable foundation Bolts - 4 nos., Foundation Bolt type -J-Type, Conformity of specification for Bolts and Nuts -as per IS:1367 (Part 2) , Grade B,Galvanization of foundation bolts and nuts and octagonal pole shall be Galvanized-As per IS:4759 latest, Earthing terminals on the base of the pole, for lightning and electrical protection-Using 12 mm dia SS Bolts of suitable length,Compliance to wind velocity test for the pole structure -IS 875:1987 part 3 latest, Regional wind withstand capacity which the pole structure support is suitable to withstand (in m/s)-50, Gust Factor -1.15, The designed Life of the Pole shall be (in Years) -25 years. |
| 24 | Supplying and fixing of C curve 1 Nos MCB 6-32 Amp on din bar along with6 mm thick backelite sheet of suitable size(as per drawing issued by engineer in charge)and 4way heavy duty connector or 2 way brass connector (02 Nos hole type) mounted on 6mm thick bakelite sheet & making holes to fix the sheet & should be provided for incoming and outgoing cables connection in the existing chamber/Din Bar of pole. |
| 25 | Installation testing and commissioning 45 watt LED street light in existing 7 Mtr hight ocogonal pole and making connection etc as per site requirement |
| 26 | SITC of various sizes water protected outdoor (Water proof)huttype compartmentalized type double door cubical panelboth side opening havingdepth up to 450 mmsuitable for 415 Volt, 3 phases, 50 Hz made out of 2mm thick CRCA sheet with required hardware duly painted with powder coated .Panel having separate detachable gland plate, angle iron base frame made out of 50mmx50mmx5mm angle iron of suitable size of the feeder pillar (minimum height 60cm), hinged door, both side opening with locking arrangement, earth bar/stud, led pilot light for phase indicator (R,Y,B) on top, 400A/415V 4 strip aluminum bus bar duly PVC sleeved, connection inter–connection with 25% extra current carrying capacity ofMCCBs and solid copper conductor cable 10 sqmm/ solid aluminium rod for MCBs (approved by Engg in charge) for incoming/Outgoing cables, links forspare MCCBs, heavy duty connectors/ terminals for three and single phase cable connections for MCCBs where as required and marking of location for incoming and out going distribution i/c grouting the legs in existing floor with 1:3:6 cement concrete foundation and dsimantling the existing panel, incoming/outgoing cable connections etc complete as required i/c dismentling the existing feeder pillar and UG cable. (Panel should beas per design &drawing approved by Engg in charge).LED light min 5 watt with on/off switch to be provided in the panel. |
| 27 | Supplying and fixing 63 Amp TPC Curve, 415 volts, MCB in the existing MCB DB complete with connections, testing and commissioning etc. as required |
| 28 | Providing and fixing following rating and breaking capacity Triple Pole 415 VMCCB with thermomagnetic release (With Thermal Magnetic Trip Unit (TMD) with terminal spreaders link in new cubicle panel(item no.22) including drilling holes in cubicle panel, making connections, interconnection with busbar spreader links etc. as required. of approved make by engg in-charge.(A) 125 Amp/415V, breaking capacity 25 KA |
| 29 | Providing and fixing following rating and breaking capacity Triple Pole 415 VMCCB with thermomagnetic release (With Thermal Magnetic Trip Unit (TMD) with terminal spreaders link in new cubicle panel(item no.22) including drilling holes in cubicle panel, making connections, interconnectionswith busbar spreader links etc. as required. of approved make by engg in-charge.(A) 100 Amp/415V, breaking capacity 25 KA |
| 30 | Supply, Installation , testing and commissioning of set of01 Nos of150 watt (Variation of more than +/- 5% would not be allowed) outdoor type LED flood light luminaryhavingminimum efficency120 Lumen/ watt outdoor type Non integralLEDluminary lightshould be Main housing/heat sink material of high pressure dia cast aluminium, Front cover material- clear toughened glass,Lences-LEDIL secondary asmmetric lens along with heat sink fins to dissipated heat effectively with adjustable mounting brackets on pole , Ingress protection-IP66 & above, Impect resistance-IK08, input operation voltage range & frequency140 to 270 Volt AC at 50 Hz +/- 2Hz , Rated voltage 240 volt AC 50Hz ,PF not less than 0.95, operating teperature range -10 deg C to +50 deg C, working life of LED is minimum 50,000 hrs burning hrs @L70 , surge protection 5KV Internal &10 KV SPD, Correlated color tem- 3000K (as per ANSI) , with Gears of Electronic constant current potted driver (CC driver) efficiency with >85%,Short & Open circuit Protection, No Load, Overload EMI Envoirmental equivalent & Phase to phase protection 320V for 48Hrs & 350V for 24Hrs &all accessoriesetc as per specification etc . LED light suitable for mounting on the existing pole bracket & drilling of holes as required, making connectionwith 3 X 1.5 sqmm FRLS grade PVC insulated copper conductor cable from loop box to fitting i/c providing and fixing suitabe size of flexible pipe /insulaiton sleave with accessories from top slot of pole to fitting connections, interconnection etc.as per specification complete required. |
| 31 | PITC of Onload Four Pole Changeover Switchwith sheet encloures,Eurolad/Ambidex, Ue-415 Volt, Ui-1000 Volt, AC,50 Hz 160 Amp, AC-23A, on wall with (25x300x 3 mm ) x4 nosMS iron Strip with fastner,Connection, interconnection with existing cable itc as required. |
| 32 | Supplying & fixing of 9 W LED Bollard of length 1000mmwith opal PC diffuser and IP 65 protectionincluiding excavation including refilling as required for base for installation of LED Bollard Light with Cement concrete 1:3:6 (1 cement: 3 coarse sand : 6 graded stone aggregate 40 mm nominal size)and testing commissioning etc as required (Final approval issued by Engineer in Charge) |
| 33 | Providing and fixing of 25 W LED Post Top made in die cast aluminium bottom housing and spun aluminium top reflector with decorative PMMA opal and clear diffuse of makeformounting on 65 mm Heavy duty GI Pole , with FR SMC Loop Box with transparent lid with single pole 6 Amp C series MCB and all other acessoriesand similiar specificationwith 3 mtr GI Pole/Pipe of 65 mm dia Heavy duty(C Class) with suitable reducer 65 mm to 60 mm and similiar specifiactionwith single coat of red oxcide paint & two coat paint aluminium paint on pole before insttalation with nut, bolts and washers including with electrical connection with 1.5 sqmm FRLS copper wire from post top lamp to Loop box incluiding excavation including refilling as required upto 1 mtr depth for instalation of 65 mm GI Pole with Cement concrete 1:3:6 (1 cement: 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) for instalation & making of collar of 65 mm GI Pole and testing commissioning etc as required (Final approval issued by Engineer in Charge) |