| 1 | Supply,testing and commissioning of Silent/containered Diesel Engine Generating set with standard AMF panel 415 volts 100 KVA/80 KW 3-Phase 0.8 power factor 50Hz . 1500 RPM self Exicited self regulated brushless AC generator installed including accoustlic enclosure suitable for ambient condition at site and confirming to condition under IS 4722/1460, IS 10001/10002, BS 5514/2613/5000 ISO 8526/3046 with and including following :-(A)Alternate :- Standard Design alternator rated at 100 KVA net output at site after considering derating as per site conditions at .8 (lag) power factor AC, 3-phase 4-wire 415 volts 50Hz , 1500 RPM,self exicited self regulated screen protected drip proof IP 23 Enclosure Brushless design with winding in pole faces, insulating class \"H\" and voltage regulation of +1% at rated voltage from no load to full load The alternator shall be confirming to BS 2613/5000 and shall be inposition to generate supply with frequency regulation with in + % tolerance. The alternator will be suitable for tropical climate and shall generally confirm to BS-2613/5000/ IS -4722. (i) Insualation class - \"H\"(ii) Temparature rise class - \"H\" (iii) Excitaion : Self Excited (vi) regulation performance : The voltage is kept constant with + 1%, manual voltage adjustment within +5%.(v) Frequency regulation + 1% (B) Diesel Engine :- Adquate capacity diesel Engine suitable for 100 KVA coupled Drive independently above alternator and after considering derating as per site conditions after generating and reducing power consumed by accessories , directly coupled through flexible coupling , multi cylinder multi strokedirect injection, cold starting 1500RPM, as per relevant ISI/BS-5514 with an overload capacity of 10% for one hour in 12 hours continuous running complete with standard accessories all as per specified and required for safe handling and operation. Salient features & other outer accessories of DG Set shall be as per under:- |
| 2 | (i) Fly wheel with housing (ii) Cooling system :- Mounted radiator with fan & belts.(iii) Cooling water Pump :- Centrifugal type belt driven (iv) Exaust System shall be as per designof manufature and mounting of exhaust pipe shall be as per site requirment.(v)Exhaust manifoldSilenser : Residential typeBellows (vi) Fuel System :- Fuel injection system with fuel injector, fuel injection solenoid switch/ nozzles/ governer electronic type capable 1% speed /frequency regulation. fuel filttersfuel hoses (vii) Lub oil system:- lubricating oil filtter lubricating oil pump.(viii) Air intake system :-Air intake manifold Air cleaner dry type(ix) Governer :- Hydro Mechanical /Electronic Governer(x)Starting system:- Electric self Starter with maintenace free batteries including battery charging alternator.(xi) Batteries:-01 No Maintenece free Battery of 12Volts 180 AH capacity complete with copper conductor multistrnded leads of suitable length from self starterto the battery terminals complete with initial charge and initial fill of electrolite all as specified.Make Starter gear ring Start/stop shall be as per manufacturer design with latest technology. Handling and operation : Salient features of accessories shall be as under : Radiator with blower fan Corrosion inhibitor coolant Paper element filters for fuel, lub oil Fly wheel housing and fly wheel. |
| 3 | (xii) Generator Monitoring Panel: comprising of following (a). Microprocessor based genset controller for metering, monitoring, governing and protection (b).Engine protection for low lub oil pressure, high coolant temperature (alarm & shutdown) (c).Alternator protection parameters like under voltage, over current, under frequency, over freqency (alarm & shutdown)(d). Relay drivers for remote annuciations (e). Cyclic cranking (f). Auto/manual start/Stop(g). Alternator trim adjustment from the front key pad(h).Operators within a temperature range 0-50 celsius and humidity upto 95% (j). Remote monitoring capability through separete modules(k).Genset metering parameters like lube oil pressure, coolant temperature, engine speed(rpm), run hours , DC voltage, 3 phase volts and 3 phase amperes, frequency, KW, KVA, Power, power factor(xiii) Safety controls:- Engine low lube oil pressure, high water temperature and over speeding of engine. (xiv) Coupling arrngment :- Flexible coupling/close coupling as per manufacturer design.(xv) Accessories :- AVM pads as per manufactrer design.(xvi) Base frame made out of MS channel as per manufacturer design. (xvii) Fuel Tank :- Daily Services fuel tank of capacity suitable for 8 hrs continous operation made out of 3mm thick (Heat Retardant) sheet top and bottom with caliberated level including arrangement, stop cock, drain plug, fuel pump of suitable capacity and connected pipe line shouldbe installed with inbuilt tank inside accoustic enclosure is inclusive of the cost ofDG set and as per manufacurer design. |
| 4 | (xviii) Deliveriables:- confirms the norms established by CPCB. Note: Making of plinth as suitable for fixing of DG Set.NOTE:- The following items are deemed to be include in the rate quoted for DG set (i) The capacity of generator set shall be net after all due derating factors as per relevant ISI standard. (ii) The quoted rate shall be deemed to br inclusive of first fill of lubricant oil and final successful acceptance test.(iii) The qouted rate shall be deemed to be inclusive of 12 hours test run at site including of one hour on 10% overload in presence of representative detailed by accepting officer, all arrangements are to be made by the contractor for tests. (iv) DHPP for testing purpose shall be supplied by the contractor without any extra cost to govt. (v) The contractor shall arrange for artificial load for testing for final testing of DG set at site and the cost is deemed to be including in above offer.(vi) Sound Proofing System: The sound proofing system shall be designed to achieve noise reduction as per relevant norms. (vii) Standard documents as per manufacturer specification such as maintenance & operation manual, parts calalogue, display charts such as maintanance and oil change chart/board (for generator and diesel engine ) and log book as directed by Engineer-In-charge.Note:(a) Testing and commissioning of DG shall be carried out by SEI/EI (as decided by HQ CE (AF) SZ) from HQ CE (AF) SZ before issue of completion (as applicable)(b) Factory test before delivery of DG from the Manufacturer Unit must be needed and necessary test certificates shall be produced after satisfying visit. Contractor shall be forwarded a letter for such visit before the visit to nominate a suitable person for such visit as decided by GE in writing.(b) The contractor shall produced printed GST purchase voucher alongwith all such tests as specified here-in-before and after for necessary payment |
| 5 | Excavation in trenches not exc. 1.5 m wide not exc. 1.5 m in depth; for laying of cables not exc. 10 Sqm on plan and getting out , trimming sides, forming bottom surface to required level complete in soft/ loose soil all as specified and as directed. |
| 6 | Returning filling in soft/loose soil, including, spreading, levelling, watering and well ramming in layers not exc. 25 cm complete all as specified and directed. |
| 7 | Removing of surplus soil to a distance not exceeding 50 metre and deposited where directed at a level not exceeding 1.50 metre above the starting point all as specified. |
| 8 | Supply and filling for dry sand in cable protection trenches before and after the cables are laid, for sand cushioning to cables complete all as specified and directed. NOTE : thickness after punning of sand shall be (minimum as specified in SSR) measured and paid in this item. |
| 9 | Material and labour for brick protection for UG XLPE cable with burnt clay old size sub class \"B\" bricks laid dry and flat abutting each other with gaps between adjacent brick not more than 10mm and width equal to length of brick in trenches across the cable complete all as directed by Engineer-In-Charge.Make: Best quality locally available which is duly approved by GE. |
| 10 | Supply and laying, connecting, testing, commissioning LT UG cable XLPE Insulated,armoured,electric powercables (heavy duty) 1100 Volts grade conforming to IS 7098 withaluminium conductor multi-strand of cross-sectional area 120 Sqmm 3.50 Core laid in trenches / ducts/ inside protection pipe including cable glands, lugs and suitable size of MS saddle clips etc. alsoall as directed by Engr-In-Charge.Note:-(a) Excavation, sand cushioning, bricks shall be measured and paid separately |
| 11 | Supply and laying, connecting, testing, commissioning LT UG cable XLPE Insulated,armoured,electric powercables (heavy duty) 1100 Volts grade conforming to IS 7098 withaluminium conductor multi-strand of cross-sectional area 35 Sqmm 3.50 Core laid in trenches / ducts/ inside protection pipe including cable glands, lugs and suitable size of MS saddle clips etc. alsoall as directed by Engr-In-Charge.Note:-(a) Excavation, sand cushioning, bricks shall be measured and paid separately |
| 12 | Supply and laying, connecting, testing, commissioning LT UG cable XLPE Insulated,armoured,electric powercables (heavy duty) 1100 Volts grade conforming to IS 7098 withaluminium conductor multi-strand of cross-sectional area 50 Sqmm 3.50 Core laid in trenches / ducts/ inside protection pipe including cable glands, lugs and suitable size of MS saddle clips etc. alsoall as directed by Engr-In-Charge.Note:-(a) Excavation, sand cushioning, bricks shall be measured and paid separately |
| 13 | Supply and laying, connecting, testing, commissioning LT UG cable XLPE Insulated,armoured,electric powercables (heavy duty) 1100 Volts grade conforming to IS 7098 withaluminium conductor multi-strand of cross-sectional area 16 Sqmm 4.00 Core laid in trenches / ducts/ inside protection pipe including cable glands, lugs and suitable size of MS saddle clips etc. alsoall as directed by Engr-In-Charge.Note:-(a) Excavation, sand cushioning, bricks shall be measured and paid separately |
| 14 | Supply and laying, connecting, testing, commissioning LT UG cable XLPE Insulated,armoured,electric powercables (heavy duty) 1100 Volts grade conforming to IS 7098 withaluminium conductor multi-strand of cross-sectional area 16 Sqmm 2.00 Core laid in trenches / ducts/ inside protection pipe including cable glands, lugs and suitable size of MS saddle clips etc. alsoall as directed by Engr-In-Charge.Note:-(a) Excavation, sand cushioning, bricks shall be measured and paid separately |
| 15 | Supply and laying, connecting, testing, commissioning LT UG cable XLPE Insulated,armoured,electric powercables (heavy duty) 1100 Volts grade conforming to IS 7098 withaluminium conductor multi-strand of cross-sectional area 04 Sqmm 2.00 Core laid in trenches / ducts/ inside protection pipe including cable glands, lugs and suitable size of MS saddle clips etc. alsoall as directed by Engr-In-Charge.Note:-(a) Excavation, sand cushioning, bricks shall be measured and paid separately |
| 16 | Material and labour for horizontal boring for 100/150 mm bore GI pipe under road/ pavement/ hard standing at 0.60 mtr to 1.50 mtr depth from top of road level and insert 100/150 mm light grade GI pipe for laying XLPE UG cable with all necessary fittings and without any damage of road/ pavement/ hard standing surface complete all as specified and directed.Note: (a) Necessary Earthwork shal be measured and paid including this item.(b) GI pipe shall be measured and paid including this item. |
| 17 | Material and labour for horizontal boring for 20 mm bore GI pipe under road/ pavement/ hard standing at 0.60 mtr to 1.50 mtr depth from top of road level and insert 20 mm light grade GI pipe for laying XLPE UG cable with all necessary fittings and without any damage of road/ pavement/ hard standing surface complete all as specified and directed.Note: (a) Necessary Earthwork shal be measured and paid including this item.(b) GI pipe shall be measured and paid including this item. |
| 18 | Supply, lay and fix 20 mm bore galvanized iron tubing (light grade) including all fittings and laid in trenches, walls and ceilings or laid in floors complete all as specified and directed.Note: Excavation shall be measured and paid in separate item |
| 19 | Supply, lay and fix 50 mm bore galvanized iron tubing (light grade) including all fittings and laid in trenches, walls and ceilings or laid in floors complete all as specified and directed.Note: Excavation shall be measured and paid in separate item |
| 20 | Supply, lay and fix 100 mm bore galvanized iron tubing (light grade) including all fittings and laid in trenches, walls and ceilings or laid in floors complete all as specified and directed.Note: Excavation shall be measured and paid in separate item |
| 21 | Material and labour as in replacement for outdoor type heatshrinkable cable end termination jointing kitfor LT 1100 Volts (Earthed) grade cable of 70 to 150 sqmm 3.50 core size complete with jointing material and accessories complete all as directed by Engineer-In-Charge. |
| 22 | Supply and fix ON LOAD Manual Change over switch 415 V in sheet steel enclosures 4 pole of capacity of 200 Amp Conforms to IEC 60947-3 , IS/IEC 60947-3) Suitable for horizontal as well as vertical mounting complete, all as specified and directed. |
| 23 | Material and labour for earthing with galvanised steel earth plate electrode60 cm X 60 cm X 6 mm thick burried directly in ground (earth pit not less than 2.25 mtr below ground level) with top edge of the plate not less than 1.5 mtr below ground level connected to 25 mm x 4 mm thick GI strip protected by 50 mm bore light grade galvanised iron pipe and other end connected to test point as directed including funnel with wire mesh and watering pipe 20 mm bore medium grade galvanised iron pipe with charcoal and common salt in alternaterlayers of 15 cm thickness all around the GI plate electrode with concrete pit in PCC 1:3:6 type C-1 with cast iron frame including cast iron cover10mm thick hinged to CI frame and 8mm MS rod for handle including painting with synthetic enamel paint of approved colour and put number marked with GI plate above 45 cm from ground level as per colour code in AF station, necessary excavation and earth wok in soft/loose soil and disposal of spoil to a distance n exc 50 m and necessary testing complete all as shown in electrical plate No 3 of SSR part-I ncluding taking out old earthing all as specified.Note: (i) The cost of GI strip and GI protection pipe upto 7.5 mtr is deemed to be included in the quoted rate.(ii) The cost of excavation, earth work are deemed to be included in the quoted rate. |
| 24 | Supply and fixCPRI approvedOUTDOOT MAIN LT DISTRIBUTION PANEL- IP55/65 RATING / FLOOR MOUNTED/CUBICAL DESIGNFABRICATION : 14 SWG/1.6MM CRCA Sheet PRE TREATMENT: TANK PROCESSPAINTING: POWDER COATED WITH SIEMENS GREY SHED (RAL 7032) TYPE: OUTDOOR TYPE, FREE FLOOR RESTING, FIX TYPE, BOTH SIDE OPENABLEDESIGN, DOUBLE DOOR SYSTEM OF BUSBAR - 300 AMP COPPER BUSBAR . CABLE ENTRY: TOP / BOTTOM (DETACHABLE GLAND PLATE UNDRILLEDINCOMMER1. MCCB 4 Pole 36kA, 200 Amp Thermal Magnetic Release for O/L & S/C Protection - 1 NOS2.Spreader Links 4 Pole for above MCCB OF 200 Amp: 1 SET3.Extended Rotary Handle for above MCCBOF 200 Amp :1 NOSMetering Module1. R/Y/B Phase Indicating Lamps : 1 SET2. 3 phase Digital Ammeter: 1 NOS3. 3 phase Digital Voltmeter : 1 NOS 4. CT Class I, 15VA for Metering 200/5 Amp : 03 Nos 5. MCB SP 10kA C Curve for protection 6Amp : 03 Nos6. Neutral Link For Control Protection 32 Amp : 03 Nos.OUTGOING 011. MCCB 4 Pole 25kA Thermal Magnetic Release for O/L & S/C Protection of 125A :1 NOS 2. Spreader Links 4 Pole for above MCCB INDICATOR R Y B of 125A : 1 SET 3. Extended Rotary Handle for above MCCB OF 125 AMP - 1 NOSOUTGOING 021.MCCB 4 Pole 25kA Thermal Magnetic Release for O/L & S/C Protection oF 100 Amp : 1 NOS 2. Spreader Links 4 Pole for above MCCB INDICATOR R Y B of 100 A : 1 SET 3. Extended Rotary Handle for above MCCB OF 100 AMP - 1 NOS |
| 25 | OUTGOING 031.MCCB 4 Pole 25kA Thermal Magnetic Release for O/L & S/C Protection OF 63 Amp : 02 NOS 2. Spreader Links 4 Pole for above MCCB INDICATOR R Y B of 63 A : 2 SET 3. Extended Rotary Handle for above MCCB OF 63 AMP - 2 NOS OUTGOING SPARESpace for Spare Feeder OF 63 A - 1 NOSTECHNICAL & QUALITY PARAMETER1. CONSTRUCTION: - Load Bearing member will be Fabricated by CRCA steel thickness 3.15 mm2. MOUNTING: - The panel shall have wall or floor grouting system. The panel shall have minimum 250 mm bottom stand (if necessary for bottom cable entry).The panel operation height shall not exceed 2100 mm structural reinforcement with suitable angle/channel/T/flat sections including lifting hooks and GI earth strip of required.3. PAINTING: - Powder coated paint finish of approved shade over metal surface cleaned and treated with all anticorrosive process and 9 tank process before painting, with 2 coats of zinc chromate primer upto 75-micron thickness and color RAL7035 SIEMENS GREY of enameled paint as per manufacturer instruction4. LABELLING: - All Panels shall be duly metal labeled with feeder section rating /function and Danger mark with 415V AC operation,Manufacturer\"s Name,Manufacturer\"s Serial no , Year of manufacture.5. BUSBAR: - Busbar shall be sized with current density of Amperage 1A/sq.mm for Aluminum E91E Grade Busbars and 1.5A/sqmm for electrolytic copper Busbars. Heat Shrinkable Color-Coded PVC Sleeves for all Busbars, minimum bus bar gap of 25mm shall be maintained.6. WIRING –FRLS multistand wires of suitable rate as per manufacturer instruction 7. TESTING FACILITIES AVAILABLE IN FACTORY -HV Test (5kV ) / Insulation Test(5kV) / Visual Test /Function Test ( Only for Departmental Engineers ) . |
| 26 | 8. PANEL DESIGN & MANUFACTURING - All components used in the manufacture of the Panels shall confirm to the relevant IEC/BIS standard specification. Few of the standards are mentioned as follows:-a) PARTIALLY TYPE TESTED - As per IS : 8623 (Part 1),1993/IEC pub 439-1 (1985) for short circuit IP rating & temperature raise . b) IS:13947-1993/IEC:60947 General arrangements for switchgear and control gear for voltage not exceeding 1000 V. c) IS: 732/1989 Code of Practice for Electrical Wiring Installations. The Foundation complete as per OEM manufacturer\"s design directed by Engr-in-charge. Note: Contractor shall be submitted panel drawing to the Engineer-In-Charge for approval before placing of order. |
| 27 | Supply and fix CPRI approved 100 HP Motor Starter VFD ( Variable Frequency Drive) PanelPanel : Indoor type, Floor Mounted, Distribution Control Panel Board, 1.6 mm CRCA Sheet made, painted with SIEMENS GREY Powder Coat Paints after Pretreatment through 9 Tank (Cold Processing), Switchgear : 01 Nos. VFD : 75Kw VFD for Pump Application : 02 Nos MCCB : Incomer MCCB 250 Amps 4P : 01 Nos Spd. Link : Spreader for above MCCB :01 NosHandel : Ex Rotary Handel :01 NosMCB :3P MCCB for VFD 160A : 02 Nos Meter : Analog Voltmeter : 01 Nos.Meter : Analog Ammeter: 01 Nos.Push Buttons : Start/Stop Push Buttons: 04 Nos Push Buttons : Speed INC/DEC Push Buttons : 04 Nos Push Buttons : Reset push button : 02 NosLED : RYB Indication : 03 NosLED : Start/Stop Indication : 04 Nos LED : VFD Trip Inication : 02 NosMCB SP :6 A SP Control MCB : 02 NosContactor : Aux ContactorBus Bar : Bus bar Arrangement Accessories : Panel accessories Complete all as specified and directed by Engineer-in-Charge.Note: Contractor shall be submitted VFD drawing to the Engineer-In-Charge for approval before placing of order. |
| 28 | Supply and fix Microcontroller based programmable Timer for Acs for server room (Auto switching of 2 Acs at 4 Hours/ 8 Hours interval).Brand: Carrier Material : Metal Dimensions : 15 cm * 10 cm * 8 cmNumber of settings : 2 (i.e 2 Acs can be operated with one controller) Features(i) 2 Acs can be operated with one controller.(ii) Protection Againist Under/over voltage protection. (iii) Featured with Auto & Manual mode selection.(iv)Automatic AC Switching complete all as specified and directed by Engineer-in-Charge. |
| 29 | Supply and fixCPRI approved INDOOR DISTRIBUTION PANEL BOARD - IP42 RATING / FLOOR MOUNTED/CUBICAL DESIGNFABRICATION : 14 SWG/1.6MM CRCA Sheet PRE TREATMENT: TANK PROCESSPAINTING: POWDER COATED WITH SIEMENS GREY SHED (RAL 7032) TYPE: INDOOR TYPE, FREE FLOOR RESTING, FIX TYPE, SINGLE FRONT COMPARTMENTLISED DESIGN, SINGLE DOOR/ BUSBAR - 400A ALUMINIUM BUSBAR . CABLE ENTRY: TOP / BOTTOM (DETACHABLE GLAND PLATE UNDRILLEDINCOMMER1. 400A 4P MCCB + SPDL + ROH - 1 NOS MAKE L& T (INCOMMER) OUTGOING1.400A 4P MCCB + SPDL + ROH - 4 NOS MAKE L& T (OUTGOING)2. INDICATOR R Y B3. VOLT + AMMETER - 1 SET TECHNICAL & QUALITY PARAMETER1. CONSTRUCTION: - Load Bearing member will be Fabricated by CRCA steel thickness 3.15 mm.2. MOUNTING: - The panel shall have wall or floor grouting system. The panel shall have minimum 250 mm bottom stand (if necessary for bottom cable entry).The panel operation height shall not exceed 2100 mm structural reinforcement with suitable angle/channel/T/flat sections including lifting hooks and GI earth strip of required.3. PAINTING: - Powder coated paint finish of approved shade over metal surface cleaned and treated with all anticorrosive process and 9 tank process before painting, with 2 coats of zinc chromate primer upto 75-micron thickness and color RAL7035 SIEMENS GREY of enameled paint as per manufacturer instruction. |
| 30 | 4. LABELLING: - All Panels shall be duly metal labeled with feeder section rating /function and Danger mark with 415V AC operation,Manufacturer\"s Name,Manufacturer\"s Serial no , Year of manufacture.5. BUSBAR: - Busbar shall be sized with current density of Amperage 1A/sq.mm for Aluminum E91E Grade Busbars and 1.5A/sqmm for electrolytic copper Busbars. Heat Shrinkable Color-Coded PVC Sleeves for all Busbars, minimum bus bar gap of 25mm shall be maintained.6. WIRING –FRLS multistand wires of suitable rate as per manufacturer instruction 7. TESTING FACILITIES AVAILABLE IN FACTORY -HV Test (5kV ) / Insulation Test(5kV) / Visual Test /Function Test ( Only for Departmental Engineers ) .8. PANEL DESIGN & MANUFACTURING - All components used in the manufacture of the Panels shall confirm to the relevant IEC/BIS standard specification. Few of the standards are mentioned as follows:-a) PARTIALLY TYPE TESTED - As per IS : 8623 (Part 1),1993/IEC pub 439-1 (1985) for short circuit IP rating & temperature raise . b) IS:13947-1993/IEC:60947 General arrangements for switchgear and control gear for voltage not exceeding 1000 V. c) IS: 732/1989 Code of Practice for Electrical Wiring Installations. The Foundation complete as per OEM manufacturer\"s design directed by Engr-in-charge. |
| 31 | Material and labour for point wiring (Surface Type) with 1.50 Sqmm PVC insulatedmulti stranded unsheathed FRLSH copper conductor cable 1100 Volts grade drawn through with and including PVC casing caping with all fittings and accessories of PVC casing caping (like Tee, Bend etc) complete fixed to walls /ceiling etc with annd including 1.5 sqmm (nominal area) PVC insulated unsheathed, steranded, single core FRLSH copper cable as earth continuity wire connecting to common earth point with 3mm thick PVC /plastic laminated sheet, top cover suitable sizes of brass screws and washers etc, for mounting switches, sockets, regulators etc complete all as specified and as directed for the following :-Note:-(a) Red coloured cable shall be used for live connection, black coloured cable shall be used for neutral connection and green coloured cable shall be used for earthing.Separate cable for earthing and neutral to be used for each individual circuit from the distribution board.(b) Quoted rates shall be deemed for \"N\" capping and box of suitable module. |
| 32 | One 5 pin 6 Amps switch socket outlet point controlled by one switch on independent board. |
| 33 | One light/ fan/ exhaust fan/ bell point controlled by one nos, one way switch |
| 34 | All as per Item No 5.00 but One 3 pin socket outlet. 15 amps, independent, with cables 2.50 sq. mm size complete all as specified. |
| 35 | Supply and fix bell push flush type 6 Amps. |
| 36 | Supply and fix call bell ding dong type SP 230V. |
| 37 | Supply and fix switch socket combination, 2 in 1, 5 pin 6 Amps 240 V ,flush type. |
| 38 | Supply and fix switch socket combination, 2 in 1, 6 pin 6 Amps and 16 Amps 240 V ,flush type. |
| 39 | Supply and fixing sub-main wiring with PVC insulated & unsheathed two run of 10.00 Sqmm single core multistrand copper conductor cable (FRLSH), 1100 Volt grade alongwith single run of 16.00 Sqmm PVC insulated & unsheathed copper conductor cable (FRLSH) 1100 Volt grade, connected to common earth dolly as earth continuity conductor, drawn through minimum 32 mm PVC conduit complete all as specified and directed.Note:- (a)PVC conduit in concealed including accessories shall be measured and paid including the item.(b) 2 Run of line conductor and 1 Run of earth continuity conductor shall be measured as one unit length.(c) Cable requireds for connection to MCBs/DBs shall be deemed to be included in the unit rate.(d) Rate shall be included for cutting, pinning in, making good to facings where required for pointing in cement mortar 1:3 and cutting chases for concealed conduit wiring and making good, and cutting not exceeding 10 cm girth. |
| 40 | Supply and fix for 7.5/8 KVA/192 V ONLINE UPS for Uninterrupted Power Supply with Exide EP42/12 VAH Battery having battery back up 1 Hour Minimum with battery rack with connecting wire INPUT1.Nominal Voltage : 220V/230V/240V AC (1Ph+N+PE, 3 Wire)2.Operating Voltage Range : 110V~300V AC Load Dependent3.Operating Frequency Range: 50 / 60 Hz ± 10% (Auto Sensing)4.Power Factor >0.99 OUTPUT1.Output Voltage/Power Factor : 220V / 230V / 240V AC / ±1% / 0.8 Std., 0.9 Optional2.Output Frequency : Auto Sensing 50 / 60 Hz ± 1~10% Sync Mode (Configurable), 50/60 Hz ± 0.1 Hz Battery Mode3.Harmonic Distortion (THDv):≤1%4.Crest Factor:3:15.Efficiency : 94.0% Dual Conversion Mode, 99.0% ECO ModeBATTERY1.DC Voltage : 192-240V Configurable2.Charge Current 6.5 A Configurable3.Typical Recharge Time 4-5 Hours (90% of full capacity)SYSTEM FEATURES1.LCD Indication : Input Voltage/Frequency, Output Voltage/Frequency, Battery Voltage, Load Watt/VA and %, Inverter Temperature, Operation Mode such as “On Line”, “ON Batt” or On “Bypass”, Fault Codes, Battery & Load Bar graph2.LED Indication:Normal Operation, Bypass, Abnormal, Fault and Battery Mode3.Alarms / Protection :Batt. Low, DC High, Inverter Under/Over Voltage, UPS Over Load, 4.Short Circuit, Fan Failure and UPS Fault.5.Overload Capability:≤ 125% for 10 min, >125-150% for 1 min, >150% for 200 msTransfer Time:AC to Battery : 0ms, Inverter to Bypass : 4ms (Typical) |
| 41 | ENVIRONMENTAL1.Temperature Operating: 0~50°C*, Storage: -15ºC ~ 60ºC2.Humidity / Altitude 0~95% RH Non-condensing / <1500 M3.Noise ≤ 45dBA STANDARDS1.Quality ISO 9001, ISO 14001, ISO 27001, ISO 45001, ISO 50001, BIS, RoHS2.Safety IEC/EN62040-13.EMC / Performance IEC/EN62040-2; IEC/EN62040-3, Complying to CE COMMUNICATION INTERFACE1.Standard RS-2322.Optional SNMP / ModBus / Dry Contact / USB / RS-4853.Monitoring Software NetAgent Utility v5.8 / UPSilon 2000complete as specified and directed |
| 42 | Supply and fix sheet metal enclosure MCB DB SPN with din rail 8 way 240 V (double door type) with magnetic locking system including necessary provision for inserting the DBs in wall by cutting the brick/ stone masonry etc. and making good of disturbed surface to match with existing colour of wall complete all as specified.Note: (a) Quoted rates shall be deemed for brick wall / concrete wall cutting and making good as per existing surfaces. |
| 43 | Supply and fix sheet metal enclosure MCB DB SPN with din rail 4 way 240 V (double door type) with magnetic locking system including necessary provision for inserting the DBs in wall by cutting the brick/ stone masonry etc. and making good of disturbed surface to match with existing colour of wall complete all as specified.Note: (a) Quoted rates shall be deemed for brick wall / concrete wall cutting and making good as per existing surfaces. |
| 44 | Supply and fix as in repair MCB SP 240 volts, 50 Hz capacity 6-32 Amps \"B\" curve all as specified. |
| 45 | Supply and fix as in repair MCB SPN 240 volts, 50 Hz capacity 63 Amps \"B\" curve all as specified. |