| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. Group C |
| 2 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface /recessed steel/ PVC conduit as required.(a) 3x4 sqmm |
| 3 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. (a) 5/6 amp switch |
| 4 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as req..(a) 3 pin 5/6 amp socket outlet |
| 5 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. (a) 15/16 amp switch |
| 6 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as req. (a) 6 pin 15/16 amp socket |
| 7 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existingsurface /recessed steel/ PVC conduit as required.(a) 3x2.5 sqmm |
| 8 | Supplying and fixing metal box of180mmx100mmx60mm deep (normal size)of surface or in recess with suitable size phenolic laminated sheet cover in the front i/c providing and fixing 6pin,5/6 amps and 15/16amps socket outlet and 15/16amps piano type switch connection painting etc as required. |
| 9 | Supplying and fixing following way, single pole and neutral,sheet steel, MCB distribution board, 240 V, on surface/ recess,complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)(a) 8 way, Double door |
| 10 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single Pole |
| 11 | Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.(a) 63 amps |
| 12 | Laying of one no PVC insulated and PVC sheathed/XPLE Al Conductor armoured power cable of 1.1KV grade of following sizeon wall surface as required. Up to 35 sq,mm (clamped with 1mm thick saddle) |
| 13 | Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal (Aluminum alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, remote (preferably mobile app based) for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Ceiling Fan compliant to IS 374:2019 fan Supply , earthing etc. complete as req 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |
| 14 | Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required. Upto 450 mm sweep |
| 15 | Supply of 15\" (380mm) sweep 1400 rpm exhaust fan heavy duty complete with shutter,blade etc as required |
| 16 | Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85% ,Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range - 15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection,THD < 10% ,P. F.≥0.95, IP20, CRI >80 , Flicker free (flicker should be below 5 %), life time (LED,Driver & electrical circuitry), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6000 K/6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate (T.C.).Manufactures Name Engraved/ Embossing/ Screen printing on housing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineerin-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminum Body (Thickness ≥ 1.20 mm) a) 18- 22 watt |
| 17 | Supplying, installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminum body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage:140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5,Driver efficiency >85%,THD< 10% as per IEC 61000-3-2 , P.F.≥0.95, IP-66,IK-10, CRI >80 , under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle 30 deg- 120deg as per the application and the project requirement deg suitable tilt able fitting,life time(LED,Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K(As per ANSI Bin) SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable & earthing etc. as required with Minimum 5 year OEM warranty.System lumen efficacy >120<135 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). 70Watt |
| 18 | P/FHot press sheet mouldedcompound (SMC) fire retardant (Temp. resistance up to 200 C), IP 55 weather proof polebox of innerdimension 200x160x98mm (NS) complete with suitable arrangement for fixing of 2 nosof 6 to 32 amp single pole MCB & 63 Amp. Doublepole isolator (MCB/Isolator excluded) withneutral link duly shorting on DIN Channel with2 Nos of MS clamps with SS back plateofsuitable size with danger monogram property printed on the coveretc asreqd. |
| 19 | Supply of 9 Watt LED retrofit lamp suitable for B22 holder |
| 20 | Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1KV grade conforming to IS-7098 of size:-2C*6 sqmm |
| 21 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduitreq 25 mm |
| 22 | Earthing with GI Earth pipe 4.5longx40mm dia i/c accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc (but without charcoal or coke and salt) complete as req. |
| 23 | Providing and fixing 25mm x 5mm GI strip on surface or in recess for connections etc as req. |
| 24 | Supplying and fixing following size/ modules, Gl box alongwith modular base & cover plate for modular switches in recess etc. as required.(a)12 Module (200mmX150mm) |
| 25 | Supplying and fixing following size/ modules, Gl box alongwith modular base & cover plate for modular switches in recess etc. as required.(a)1 or 2 Module (75mmX75mm) |