| 1 | Taking down old unsv LT control panel board of any size of bus bar capacity and deposited to MES store yard , taken on charge in salvage ledger as directed by Engr-in-charge |
| 2 | Supply installation, commissioning and testing LT panel board, indoor type, floor mounted, dust and vermin proof, CPRI approved factory made , fabricated out of 3 mm thick CRCA sheet suitable for accommodate the followings and for 3 phase 415 volts 50 Hz, AC supply, bus bar chamber with aluminium bus bar of 400 amp rating for 3 phase and 4 wire system duly insulated with heat shrinkable sleeved as per colour code, supported on epoxy insulators-01 set common earth bus of suitable size at bottom in side panel board with two earth terminals out side panel board, cable alley, cable glands with independent plates at bottom and complete panel board painted with powder coating in siemens grey colour all as approved & comprising as under:- |
| 3 | Incomingi)MCCB TPN, 200A, , breaking capacity 36 KA-01 NoOut Goingi)MCCB TP, 63A, , breaking capacity 36 KA-03 Nosii) Digital type voltmeter (0-500 Volts) -01 Noiii) Fully Automatic Star Delta Starter type ML-2 complete set-02 Nosiv) Fully Automatic Star Delta Starter type ML-1.5 complete set-01 Nov)Copper wound CTs with CTR 30/5-(Set of 3)-01 setvi) Indicator Lamps(LED type) for motor ON/OFF indication-01 set |
| 4 | Supply installation, commissioning and testing LT panel board, outdoor type, floor mounted, dust and vermin proof, CPRI approved factory made , fabricated out of 3 mm thick CRCA sheet suitable for accommodate the followings and for 3 phase 415 volts 50 Hz, AC supply, bus bar chamber with aluminium bus bar of 800 amp rating for 3 phase and 4 wire system duly insulated with heat shrinkable sleeved as per colour code, supported on epoxy insulators-01 set common earth bus of suitable size at bottom in side panel board with two earth terminals out side panel board, cable alley, cable glands with independent plates at bottom and complete panel board painted with powder coating in siemens grey colour all as approved & comprising as under:- |
| 5 | Incoming(i)MCCB TPN, 630 Amps, breaking capacity 50 KA-01 NosOut Going(i) MCCB TP 200 Amps,breaking capacity 36 KA :- 01No.(ii) MCCB TP 415 V, fixed type, 100 Amps, 36 KA - 03 No(iii) Fully Automatic Star Delta Starter type ML-4 complete set - 03 No(iv) Digital type voltmeter (0-500 Volts) -01 No(v) Copper wound CTs with CTR 30/5-(Set of 3)-01 set(vi) Indicator Lamps(LED type) for motor ON/OFF indication-01 set |
| 6 | Supply and fixing in replacement, installation, testing and commissioning of feeder pillar box ,outdoor type cubical shape,three phase, 4 wire, Al bus bar for phases and neutral made out of CRCA sheet 3.15 mm thick ,factory fabricated , CPRI approved , powder coated ,dust and vermin proof , provn for ventilation , angle iron frameand four legs of 50x50x6mm thick angle iron ,2 ft long grouted on PCC foundation of height not less than 30 cm from the ground level , grouting properly and of suitable size to accommodate the items mentioned belowand having separate compartment /chambers for cable gallery busbar ,switch gear etc all as specified and comprising of following including necessary cable connections to the MCCBs, voltmeter, Ammeter and cable lugs etc . |
| 7 | (a) Albus bar with PVC sleeve suitable for 200 amps for phase & 200 Amp for neutral- 01Set.(b) Voltmeter,digital type 0- 500 volt,with selector switch - 01 set (c) Ammeter Digital type 0-100Amps, with selector switch and CT\"-1set(d) Phase indicating lamps LED type ( red , yellow, blue) 01 set(e) Incoming MCCB100 Amp 3 pole 25 KA with adjustable thermal and fixed magnetic release -01 No(f) outgoing MCCB63 Amp 3 pole 16 KA with adjustable thermal and fixed magnetic release -02No(g) FASD StarterML 1.5 FASD with MS sheet enclosure-01 NosMake-L&T(h) Analog time switch -01 No (j) Single phase preventer-01 No(k) Phase sequence corrector for complete three phase system - 01 Set |
| 8 | Excavation in trenches not exc 1.5 Mtr wide and not exc 1.5 Mtr deep for pipe line in ordinary soft/loose soil getting out and levelling of bottom surface to required level complete all as specified and directed. |
| 9 | Returning filling in, including spreading, leveling, watering and well ramming in layers not exc 25 cm thick complete all as specified and directed. |
| 10 | Removing excavated material from site to a distance not exc 50mtr away and depositing where directed not exc 1.5mtr from the starting point complete all as specified and directed. |
| 11 | Supply & laying cable LT XLPEinsultated screened PVC bedded, galvanized steel strip or wire, armoured, electric power cables (heavy duty) with stranded aluminum conductor, 1100 volts grade of size 3.5 core 25 Sq mm including taking down the existing from site complete all as specified and directed. |
| 12 | Supply & laying cable LT XLPEinsultated screened PVC bedded, galvanized steel strip or wire, armoured, electric power cables (heavy duty) with stranded aluminum conductor, 1100 volts grade of size 3.5 core 35 Sq mm including taking down the existing from site complete all as specified and directed. |
| 13 | Supply & laying cable LT XLPEinsultated screened PVC bedded, galvanized steel strip or wire, armoured, electric power cables (heavy duty) with stranded aluminum conductor, 1100 volts grade of size 3.5 core 50 Sq mm including taking down the existing from site complete all as specified and directed. |
| 14 | Supply & laying cable LT XLPEinsultated screened PVC bedded, galvanized steel strip or wire, armoured, electric power cables (heavy duty) with stranded aluminum conductor, 1100 volts grade of size 3.5 core 95 Sq mm including taking down the existing from site complete all as specified and directed. |
| 15 | Supply & laying cable LT XLPEinsultated screened PVC bedded, galvanized steel strip or wire, armoured, electric power cables (heavy duty) with stranded aluminum conductor, 1100 volts grade of size 3.5 core 120 Sq mm including taking down the existing from site complete all as specified and directed. |
| 16 | Supply & laying of Sub Class \"B\" brick laid across the cable above the sand cushioning for protection of cable complete all as specified and directed |
| 17 | M/L for sand filling in cable ducts/ trenches with and including removing old sand to a distance not exceeding 50 mtr away and depositing where directed by Engineer-in-charge. |
| 18 | Supply & installation of High mast light Poles 15 Meter height suitable upto 8 Nos lantern symmetrically fitting allong with their control gear and having two point suspension system with steel wire rope of 6 mm dia 97/19 gauge and double drum winch with luminaire mounting arm, pully assembly, aviation, obstruction light, lightning arrester spike, suitable LT Panels,including PCC foundation as per manufacturer drawing including taking down of existing high most light poles and fittings complete all as speciied and as directed by Engineer-in-charge.(Note:- (i) Old U/s material obtained from demolition shall be taken on charge in demolition/salvage register and enter page number in demolition statement. Necessary RVin weight (KG) shall be taken into account and attach with RAR/F Bill. (ii) Flood light fitting shall be measured and paid seperately under respective items). |
| 19 | M&L earthing complete with galvanised steel earth plate electrode 60x60 cmx 6 mm thick burried directly in ground (earth pit not less than 2.25 mtr deep below nominal ground level) with top edge of plate not less than 1.5 mtr below normal ground level connected to galvanised iron strip 32x6 mm as earthing lead by mean of bolts, nuts, check nuts and washer of galvanised iron or steel all as shown in Electrical plate No-3 connected to earthing test point all as specified or indicated including testing on completion complete all as specified and directed.(Note:- GI strip 32x6mm upto 7.5Rm shall be included in quoted unit rate and if extra required the same shall be measured and paid seperately under respective items.) |
| 20 | S&F GI Strip 32 x 6 mm earth continuty including necessary connection, nuts, bolts, washers complete all as specified and directed |
| 21 | Supplying and laying synthetic Rubber insulated mats 2.5 mm thick for voltage upto 11 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m. |
| 22 | Supply and fixing LED luminaire 600 mm x 600 mm,35/36 watt, 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roofceiling including connecting up with driver threecore flexible copper conductor cases of suitable size complete. |
| 23 | Supply and fixing LED flood light 170 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp. |
| 24 | S&F in replacement 3 pole power contactor ML-12 ,300 Amps coil voltage 415 volts, 50 HZ Make L&T No SS-91010 suitable for fixing in existing panel or equivalent in Havell\"s/ABB/Siemens as approved by GE. |
| 25 | All as per srl item No 21 above herein above but type ML-6, 110 Amps Make L&T cat No SS-90921 or equivalent in Havell\"s/ABB/Siemens as approved by GE. |
| 26 | All as per srl item No 21 above herein above but type ML-4, 70 Amps Make L&T cat No SS-90910 or equivalent in Havell\"s/ABB/Siemens as approved by GE. |
| 27 | All as per srl item No 21 above herein above but type ML-3, 40 Amps Make L&T cat No SS-90721or equivalent in Havell\"s/ABB/Siemens as approved by GE. |
| 28 | All as per srl item No 21 above herein above but type ML-1.5, 25Amps Make L&T cat No SS-90851 or equivalent in Havell\"s/ABB/Siemens as approved by GE. |
| 29 | Supply and fixing in replacement of FASD star delta starter type ML-1.5 |
| 30 | Supply and fixing in replacement of FASD star delta starter type ML-2 |
| 31 | Supply and fixing in replacement of FASD star delta starter type ML-3 |
| 32 | Supply and fixing in replacement of FASD star delta starter type ML-4 |
| 33 | Supply and fixing LED flood light 120 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp. |
| 34 | Supply and fix in replacement, errecting of steel tubular poles with cast iron base plate of size 300mm x 300mm x 6mm, finial taper plug, bolts, nuts & screws for type 410 SP-31 (9.0 metres long)including inclined angle of GI pipe of size 40 mm dia with suitable \"U\" clip connected nut and bolts for fixing street light and painting with two coats of aluminium paint over one coat of redoxide primer on all exposed surfaces and tarring with black bituminous paints to embedded portion in PCC and providing 3 Nos of 30cm wide circular bands with black & yellowpaint starting from plinth level at a gap of 30 cm in between 2 bands and numbering of poles, in yellow paint over black painted back ground at a height of 2m from bottom of pole with 5 cm large bold letters 2\" (inch) wide complete all as specified and directed. (Note: Excavation, earth work, PCC in foundation and coping shall be measured and paid separately under relevant item of this schedule. |
| 35 | M&L for Providing PCC (1:4:8) type D-2 using 40mm graded crushed stone aggregate as in foundations filling mass concrete bed of pipe etc complete allas specified and directed at site. |
| 36 | M&L for Provinding PCC (1:2:4) type B-1 using 20mm grded crushed stone aggregate as in coping bed plate including weathering slightly rounded or chamfered angles and throating etc complete allas specified and directed at site. |
| 37 | Supply and fixing in replacement 60 watt LED lumens street light 115 Lm/watt new generation energy saving and environmental friendly long life LED street light made up of pressure die cast aluminium housing with high efficient LED as lighting source and PC cover having TOP Opening seperate driver compartment with IP-66 protection and impact resistance of IK07including making connections with GI pipe 0.6 mtr angle bracket fixing on wall using suitable fastners and connectng to ceiling rose with appropriate copper wire complete all as specified and directed. |
| 38 | Taking up existing CI/DI water mains ofthe followingbore size including all fittingscomplete all as specified andas directed :- |
| 39 | 100 mm bore pipe. |
| 40 | 150 mm bore pipe. |
| 41 | 200 mm borepipe. |
| 42 | Supplying, Laying, jointing, testing and commmisioning of DI Pipe of following sizes, with spigot and socketed ends centrifugally castClass K-7 Push on joint confirming to IS 8329laid in trenches with andincluding rubber tyton joints complete all as specified :- |
| 43 | 100 mm bore pipe. |
| 44 | 150 mm bore pipe. |
| 45 | 200 mm borepipe. |
| 46 | M&L for MS Pipe header 600 mm dia 3 m longwith making arrangement all as required at site including cutting , welding and finishingof pipe with flanged ends closed with dead plate not less than 10mm thick and including makingPCC (1:2:4) support pillars of RCC as per site requirement andincluding provision of following incoming & outgoing connection of MS pipe, heavy duty, class ‘C’ of length 600mmwith two coats of rust proof synthetic enamel paint over one coat of red oxide primer and all T & P and highly skilled trademan required at site to fix the header (JCB, Hydra ) etc all as specified and directed by engineer-in-charge with andincluding all incoming and outgoing suction and delivery pipe line of length each as mentioned below and taking out oldrusted MS header 600 mm bore |
| 47 | (i) 250mm dia incoming : 03Nos(ii) 400mm dia outgoing: 02 Nos(iii) 300 mm dia outgoing :- 02 Nos(iv) 150mm dia outgoing :-02 Nos(v) M.S flange 600 mm bore 10 mm thick : 02 Nos. MS flange 150mm thick 10 mm : 02 Nos(vi) M.S flange 400 mm bore 10 mm thick : 02 Nos, MS flange 300 mm bore 10mm thick : 02 Nos(vii) Dummy plate of size 600 mm dia , 10mm thick-02 Nos |
| 48 | Supply, laying , jointing and testing M S Pipe heavy duty of size 600 mm bore and thickness not less than 20mm confirming to lS 3589 all as specified and directed by Engr-in -charge |
| 49 | Supply, laying , jointing and testing M S Pipe heavy duty of size 400 mm bore and thickness not less than 20mm confirming to lS 3589 all as specified and directed by Engr-in -charge |
| 50 | Supply, fixing, in replacement cast Iron Sluice Valve 400 mm dia class-1, ISI Marked, flanged ends drilled pressure rating PN-1.6, PD Short body,Confirming to IS 14846 -2000, having stainless steel spindle with cast iron operation wheel at top complete with nuts, bolts, washers and rubber gasket including jointing and testing complete all as specified and directed |
| 51 | M&L for Painting of LT Panel after complete removing of old paint by paint removers or burning off by blow lamps and cleaning with scrapers, any number of coats, any width or girth from the existing MS Base frame ofCentrifugal Motor and Pumps of Cap of10HP to upto 200 HP and Painting of LT Panel by applying two coat of syenthetic enamel paint over a coat of red oxide primer complete all as specified and directed |
| 52 | Supply and fixing cotton synthentic fabric circular woven jacketted rubberised fabric fire hose RRL 15 Mtrs long with coupling Stainless Steel 63 mm size male and female instantenous type complete all as specified and directed |
| 53 | Supply and fixing in replacement instaneous type copper alloy (gun metal) branch pipe 63 mm dia of suitable length fitted with 16 mm dia nozzle complete all as specified and directed |
| 54 | Supply and fixing in replacement Fire hose real drum suitable for 20 mm dia rubber hose pipe upto 30 mtr length complete all as specified and directed. |
| 55 | Supply and fixing in replacementmanual call point break glass type enclosed in aluminium cast alloy body of 3 mm thickness complete with chain and harmer and incl inscriber in case of fired break glass complete all as specified and directed |
| 56 | Supply and fixing in replacement 2 way fire brigade hydrant including nuts, bolts, washer and rubber flanges etccomplete all as specified and directed |
| 57 | Supply and fixing in replacment weather proof standerd fire hose box made out of 18 SWG gauge MS sheet of MS Sheet 800mm X 600mm X 250mm with double door with 4 mm thick glasses and door frame made of 16 gauge MS sheet painted fire red out side and brilliant white inside yard for external use alongwith door opening and lock including painting with two coat of syenthetic enamel paint over a coat of red oxide primer complete all as specified and directed. |
| 58 | Supply and fixing fire hydrant post/stand post made out of 80 mm dia MS Pipe heavy duty class \"C\" both ends flanged 1.5 mtr heightcomplete all as specified and directed. |
| 59 | Supply, fixing, in replacement cast Iron Sluice Valve 100 mm dia class-1, ISI Marked, flanged ends drilled pressure rating PN-1.6, PD Short body,Confirming to IS 14846 -2000, having stainless steel spindle with cast iron operation wheel at top complete with nuts, bolts, washers and rubber gasket including jointing and testing complete all as specified and directed |
| 60 | Supply, fixing, in replacement cast Iron Sluice Valve 150 mm dia class-1, ISI Marked, flanged ends drilled pressure rating PN-1.6, PD Short body,Confirming to IS 14846 -2000, having stainless steel spindle with cast iron operation wheel at top complete with nuts, bolts, washers and rubber gasket including jointing and testing complete all as specified and directed |
| 61 | M&L prepration of painting to existing steel surface for fire cabinet box with one coat primer and two coat of synthetic enamel paint including scratching old paint complete all as specified and directed |
| 62 | M&L for welding work for existing door, hinges, handels and locking arrangement complete all as specified and directed (Note:- Each butt weld not exe 2cm shall be measured and paid as one unit.) |
| 63 | Supply and fixingMS Pipe heavy duty class C of size 100 mm boreheavy grade including necessary nut and bolts with washers required at site condition complete all as specified and directed. |
| 64 | Supply and laying in replacement of MS Pipes \"Heavy grade\" with all fittings as required at site laid in floors or fixed to walls and ceilings including welding as required at site and removing old rusted pipe of size 150mm bore complete all as specified and directed |
| 65 | Supply and fixing in replacement flanges duly welded on ends of MS pipe, flange size not less than 20 mm thick incl nuts and bolts and washer etc reqd at site complete all as specified and directed of following sizes |
| 66 | 100 mm bore |
| 67 | 150 mm bore |
| 68 | An amount of Rs 2,18,460.00 shall be deducted from BOQ on account of schedule of credit |