| 1 | Excavation in trenches not exc 1.5 m wide and not exc 1.5mtr in depth for foundation (laying of under ground cables) in any type of soil and getting out complete all as specified and direced by Engineer-in-Charge. |
| 2 | Excavation in trenchesexc 1.5 Mtr wide and not exc 3 mtr depth and getting out in any type of soil complete all as specified and direced by Engineer-in-Charge. |
| 3 | Returning, filling in, including spreading, leveling, watering and well ramming in layers not exc 25cm in any type of soil complete all as specified and direced by Engineer-in-Charge. |
| 4 | Removal of surplus soil to a distance not exc 50 mtr and depositing at a level not exc 1.5mtr above the starting point complete all as specified and direced by Engineer-in-Charge. |
| 5 | M&L for sand cushioning for protection of PVC cable with approved sand of uniform thickness, laid dry, by filling in trenches and punning to proper required cover complete all as specified and direced by Engineer-in-Charge. |
| 6 | Supply and laying of fly ash bricks of best qualitylaid flat equal to width of bricks, perpendicular to underground cable over the dry sand cushioning, for cable protection complete all as specified and direced by Engineer-in-Charge. |
| 7 | Taking down old underground LT cable any size up to 240 sqmm 2/3.5/4 core retrieved complete all as specified and direced by Engineer-in-Charge. |
| 8 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 240 x 3.5 core complete all as specified and direced by Engineer-in-Charge. |
| 9 | All as per item No 08 above but size 185 sq mm 3½ core complete all as specified and direced by Engineer-in-Charge. |
| 10 | All as per item No 08 above but size 120 sq mm 3½ core complete all as specified and direced by Engineer-in-Charge. |
| 11 | All as per item No 08 above but but size 95 sq mm 3½ core complete all as specified and direced by Engineer-in-Charge. |
| 12 | All as per item No 08 above but size 70 sq mm 3½ core complete all as specified and direced by Engineer-in-Charge. |
| 13 | All as per item No 08 above but size 50 sq mm 3½ core complete all as specified and direced by Engineer-in-Charge. |
| 14 | All as per item No 08 above but size 35 sq mm 3½ core complete all as specified and direced by Engineer-in-Charge. |
| 15 | All as per item No 08 above but size 25 sq mm 4 core complete all as specified and direced by Engineer-in-Charge. |
| 16 | All as per item No 08 above but size 16 sq mm 4 core complete all as specified and direced by Engineer-in-Charge. |
| 17 | All as per item No 08 above but size 10 sq mm 4 core complete all as specified and direced by Engineer-in-Charge. |
| 18 | All as per item No 08 above but size 16 sq mm 2 core complete all as specified and direced by Engineer-in-Charge. |
| 19 | All as per item No 08 above but size 10 sq mm 2 core complete all as specified and direced by Engineer-in-Charge. |
| 20 | M&L for cutting existing road/hard standing not exc 30x30 cm in wide & depth getting out excavated material for laying cable/GI tube, returning filling & well rammaing watering finish suraface 15 cm from top using PCC 1:3:6 including removal of surplus soil complete all as specified and direced by Engineer-in-Charge. |
| 21 | Laying only 80mm bore GI Pipefor cable proction medium grade for road crossing/ on wall/ on pole complete all as specified and direced by Engineer-in-Charge. |
| 22 | All as per item No 21 above but 40 mm bore complete all as specified and direced by Engineer-in-Charge. |
| 23 | M&L for PCC 1:2:4 type B-1 (using 20 mm graded crushed stone agrregate) as in pedestal of pole/ strut and in copping including necessary form work and finishing exposed faces of concrete even and smooth using extra cement complete all as specified and direced by Engineer-in-Charge. |
| 24 | M&L for PCC 1:3:6 type C-2 (using 40mm graded crushed stone aggregate) as in foundations of poles, filling and mass concrete complete all as specified and direced by Engineer-in-Charge. |
| 25 | M&L for straight through joint/End Joint kit for 16 Sqmm to 35 Sqmmregin cast complete heat shrink outdoor type suitable for 2/3.5/4 core LT PVC / XLPE cable upto 1.1 KV complete with all accessories and generally conforming to IS 8438/1977 complete all as specified and direced by Engineer-in-Charge. Note-: Excvation & Earth work shall be mesured & paid sepreately in respective item of this schedule. |
| 26 | M&L for Straight through joint/End Joint kit for 50 Sqmm to 95 Sqmmregin cast complete heat shrink outdoor type suitable for 2/3.5/4 core LT PVC / XLPE cable upto 1.1 KV complete with all accessories and generally conforming to IS 8438/1977 complete all as specified and direced by Engineer-in-Charge. Note:- Excvation & Earth work shall be mesured & paid sepreately in respective item of this schedule. |
| 27 | M&L for Straight through joint/End Joint kit for 120 Sqmm to 185 Sqmmregin cast complete heat shrink outdoor type suitable for 2/3.5/4 core LT PVC / XLPE cable upto 1.1 KV complete with all accessories and generally conforming to IS 8438/1977 complete all as specified and direced by Engineer-in-Charge. Note:- Excvation & Earth work shall be mesured & paid sepreately in respective item of this schedule. |
| 28 | M&L for Straight through joint/End Joint kit for 240 Sqmm to 300 Sqmmregin cast complete heat shrink outdoor type suitable for 2/3.5/4 core LT PVC / XLPE cable upto 1.1 KV complete with all accessories and generally conforming to IS 8438/1977 complete all as specified and direced by Engineer-in-Charge. Note:- Excvation & Earth work shall be mesured & paid sepreately in respective item of this schedule. |
| 29 | Re-stretching of aluminium conductor any size and length complete including removing kinks and providing new binding wire /Jumper where required complete all as specified and direced by Engineer-in-Charge. |
| 30 | Dismantling steel pole and deposit to mes store with care for reuse complete all as specified and direced by Engineer-in-Charge. |
| 31 | Dismantling PCC pole alongwith GOD switch and deposit to MES store with care for reuse complete all as specified and direced by Engineer-in-Charge. |
| 32 | S&F for loop type insulator porcelain vitreous white, brown or green large size with overall dimension 90 x 140mm clearance of hole 25.5mm complete all as specified and direced by Engineer-in-Charge. |
| 33 | S&F shackle type vitreousbrown or white insulator includinggalvanised mild straps, washersinsulator,bolts wahsers and nuts of size 100mm height and 115 mm dia suitable for 1100 volts grade complete all as specified and direced by Engineer-in-Charge. |
| 34 | Supply, fixing, jointing and connectinggalvanisedwireof size 4 mmincluding proper binding complete all as specified and directed by Engineer-in-charge. |
| 35 | Supply, fixing, jointing and connecting aluminium conductor, steel reinforcement including proper binding complete all as specified and directed by Engineer-in-charge. |
| 36 | Supply errection and febrication of cross arms,bracings supports, clamp, and back plates febricated from structural steel section including nuts,bolts,washers welding,bending cold or hotdrilling holes for bolts in any shape or size as indicated complete all as specified and direced by Engineer-in-Charge. |
| 37 | Supply, fixing, jointing and errectinggalvanised stay wirestrand of size 7/4 mmcomplete all as specified and directed by Engineer-in-charge. |
| 38 | M&L for find out manually fault in any size of LT underground able including disconnecting of cable connectiion from both side panels/poles and necessary excavation to reach upto cable and making space for cable jointkit, including necessary accessories like Cable Jumper and thimble, cable lugs etc complete all as specified and directed by Engineer-in- Charge. |
| 39 | M&L for find out fault in LT line bring/call fault finding machine equipment and find out fault in any size of LT underground cable including disconnecting of cable connection from both side panels/poles and necessary excavation to reach upto cable and making space for cable joint complete all as specified and directed by Engineer-in-Charge. |
| 40 | Supply errect stay assembly complete with accessoriesas shown in electrical plate No 1 (loop type insulator,stay clamps, excavation and concrete measured and paid separately) dia meter of stay rod is not less than 16mm complete all as specified and direced by Engineer-in-Charge. |
| 41 | M&L for fixing of line seprator suitable for LT line two conductor in horizontal /vertical feeder complete all as specified and direced by Engineer-in-Charge. |
| 42 | M&L for fixing of line seprator suitable for LT line four conductor feeder complete all as specified and direced by Engineer-in-Charge. |
| 43 | M&L for earth testing, Identifying the earthings in system and recording the results on indicator board and producing three copies of test sheet complete all as specified and direced by Engineer-in-Charge.Note :- Cost of labour and tools required for testing is deemed to be included in quoted rates. |
| 44 | M&L cleaning of area around 2/4 /6 pole structure sub station, power house, pump house underground sump area by surface excavation not exc30 cm, averaging 15 cmdeep and getting outremoving shrubs, grass miniplants and other unwanted material, stones etc leveling complete all as specified and direced by Engineer-in-Charge. |
| 45 | Cutting the tree branches/ stem all around the over head line to mainten clear distance 2 mtr all around the conductor, of any size or girth and shifting it to nearest waste depot and cleaning area complete between the span of two poles length of not exc 50 mtrs complete all as specified and direced by Engineer-in-Charge. |
| 46 | Scraping of old paint from the street light steel tubular pole with out removing accessories and preparationof surfaces for repainting . Repainting the pole with one coat of alternative yellow and black straps of 30 cm each upto 1.5 mtr height using synthetic enamell paint . Repainting the remaining pole and clamps GI bracket etc above 1.5 mtr height by applying one coat of aluminum paintcomplete all as specified and direced by Engineer-in-Charge. |
| 47 | M&L for painting of street light PCC pole without removing accessories with one coat ofalternative yellow and black straps of 30 cm each upto 1.5 mtr height using synthetic enamell paint. Colour washing the pole above 1.5 mtr height using snowcem of approved colour including painting the steel parts i.eclamps GI bracket etc by applying one coat of aluminum paint complete all as specified and direced by Engineer-in-Charge. |
| 48 | Writing No of pole with letters/ figures of size not exc 30 mm with black painton a yellow circle of dia 75 mm complete all as specified and direced by Engineer-in-Charge. |
| 49 | S&F in replacement of 2 runs of 2.5 Sqmm PVC insulated stranded copper cable for connection of street light including PVC conduit 20 mm external dia medium grade fixed on pole with proper clamping, saddling etc complete all as specified and direced by Engineer-in-Charge. |
| 50 | M&L in repair of GIfunnels with wire mesh for earthing complete all as specified and direced by Engineer-in-Charge. |
| 51 | M&L for Servicing to Indoor/outdoortype LTpanel board single/ double door withcanopy by (i) Cleaning with blower, (ii) Cleaning with CTC/Petrol (iii) Replacement of damaged lugsif any(iv) Replacement of deteriorated copper wiring (v) Cleaning and tightening of MCCB terminal connections(vi) Replacement of sheared rubber beadings (vii) Rectifying of loose connections (viii) Replacement of door shutters of suitable size ,with 3.15mm thick CRCA sheet incl locking arrangement , door hinges- 2 Nos .(ix) writing feeder name with white paint on all incoming and outgoing feeders includingtwo coats of synthetic enamel paint over a coat of red oxide complete with existing colour allas shown & directed.(x) Cleaning surrounding area of LT Bus bar panel complete all as specified and direced by Engineer-in-Charge. |
| 52 | M&L for Servicing to Indoor/outdoortype LT busbarsingle/ double door withcanopy by (i) Cleaning with blower, (ii) Cleaning with CTC/Petrol (iii) Replacement of damaged lugs if any(iv) Replacement of deteriorated copper wiring (v) Cleaning and tightening of MCCB terminal connections(vi) Replacement of sheared rubber beadings (vii) Rectifying of loose connections (viii) Replacement of door shutters of suitable size, with 3.15mm thick CRCA sheet incl locking arrangement, door hinges- 2 Nos .(ix) writing feeder name with white paint on all incoming and outgoing feeders includingtwo coats of synthetic enamel paint over a coat of red oxide complete with existing colour allas shown & directed.(x) Cleaning surrounding area of LT Bus bar panel complete all as specified and direced by Engineer-in-Charge. |
| 53 | S&F in replacment of 3 phase digital multi function meter with suitable accessories and fixing arrangements complete all as specified and direced by Engineer-in-Charge. |
| 54 | S&F in replacement of selector switch suitable for 415volts complete all as specified and direced by Engineer-in-Charge. |
| 55 | S&F in replacment of voltmeter of range 0 to 500 Volts complete all as specified and direced by Engineer-in-Charge. |
| 56 | S&F in replacament of LED type phase indicator to be fitted on panel (R,Y, B as per site requirement) complete all as specified and direced by Engineer-in-Charge. |
| 57 | S&F in replacement of MCCB 3 pole 415 Volt, 50 Hz, 200 Amps ICS=100%ICU with breaking capacity 36 KA adjustable type with all accessories including taking down complete all as specified and direced by Engineer-in-Charge. |
| 58 | S&F in replacement of MCCB 3 pole 415 Volt, 50 Hz,160 Amps ICS=100%ICUwith breaking capacity 36 KA with all accessories including taking down complete all as specified and direced by Engineer-in-Charge. |
| 59 | S&F in replacement of MCCB 4 pole 415 Volt, 50 Hz,125 Amps ICS=100%ICUwith breaking capacity 25 KA with all accessories including taking down complete all as specified and direced by Engineer-in-Charge. |
| 60 | S&F in replacement of MCCB 4 pole 415 Volt, 50 Hz,100 Amps ICS=100%ICUwith breaking capacity 25 KA with all accessories including taking down complete all as specified and direced by Engineer-in-Charge. |
| 61 | Supply, install, connect & testing cubical outdoor type factory made double door , powder coated LT bus bar feeder pillar box for 150 amps 3ph and neutral arrangement of size 500mmx500mmx200mm complete weather proof and verminproof conforming to IP-54 made out of 2mm thick CRCA sheet including provisions for ventilation and cable termination alley all as per IS.It should be mounted on 40 x40 x 6mm angle frame with a clearance of at least 0.45mtrs above GL and 0.30mtrs below ground including required PCC for foundation and coping complete all as specified and direced by Engineer-in-Charge. Note:-LT Panel/ LT feeder box must be approved by CPRI. |
| 62 | Supply installation commission and testing of Out door LT Panel board of size 1200 x 1000 x 450 mm, (CPRI tested) LT415 Volts, 50 Hz , 3-phase,Bus Bar chamber comprising 4 Nos aluminium strip bus bars air insulated and PVC sheathed capacity 600 Amps with colour coding with main indication IA with selector switch 03 Nos, digital ammeter with selector switch, digital volt meter 500V with selector switch and LED type/Neon type Indicating lamps panel mounting type RYB-3 Nos,factory assembled, outdoor type weather and vermin proof (Protection Class IP-54) made out of not less than 60 X 60 X 6 mm angle iron frame and 3.15 mm thick MS Sheet CRCA sheet with front hinged opening, rubber lining, locking arrangement, painted externally and internally with two coats of synthetic enamel gray paint(First Quality) over a coat of red oxide primer complete comprising of following :-(a) Internal wiring with single core copper conductor cable/ PVC Insulated Copper Strip of suitable size incoming to bus bar and bus bar to outgoing MCCB/MCB-1Job. (b) Fine wiring with single core copper conductor cable for instruments/indicating lamps-1 Job. INCOMING : MCCB 400 Amp, 4 Pole , 415 Volts rating with Adjustable Thermal Magnetic Release (Breaking capacity 36KA) -1 NoOUTGOING: MCCB 350 Amp, 4 Pole , 415 Volts rating with Adjustable Thermal Magnetic Release (Breaking capacity 36KA) -1 No MCCB 100 Amps, 4 Pole , 415 Volts rating with,Adjustable overload setting (Breaking capacity 16 KA) Ics=100% of Icu- 4 Nos Spreader Terminal of both side -06 Nos Spreader complete all as specified and directed by Engineer-in-Charge. |
| 63 | Supply installation commission and testing of Out door LT Panel board of size 1200 x1000 x 450 mm, (CPRI tested) LT415 Volts, 50 Hz , 3-phase, Bus Bar chamber comprising 4 Nos Aluminium strip bus bars air insulated and PVC sheathed capacity 600 Amps with colour coding with main indication IA with selector switch 03 Nos,digital ammeter with selector switch, digital volt meter 500V with selector switch and LED type/Neon type Indicating lamps panel mounting type RYB-3 Nos, factory assembled, outdoor type weather and vermin proof (Protection Class IP-54) made out of not less than 60 X 60 X 6 mm angle iron frame and 3.15 mm thick MS Sheet CRCA sheet with front hinged opening, rubber lining, locking arrangement, painted externally and internally with two coats of synthetic enamel gray paint(First Quality) over a coat of red oxide primer complete comprising of following :-(a) Internal wiring with single core copper conductor cable/ PVC Insulated Copper Strip of suitable size incoming to bus bar and bus bar to outgoing MCCB/MCB-1Job. (b) Fine wiring with single core copper conductor cable for instruments/indicating lamps-1 Job.INCOMING: MCCB 350 Amp, 4 Pole , 415 Volts rating with Adjustable Thermal Magnetic Release (Breaking capacity 36KA)OUTGOING: MCCB 250 Amp, 4 Pole , 415 Volts rating with Adjustable Over load setting (Breaking capacity 25KA)MCCB 100 Amp, 4 Pole , 415 Volts rating with Adjustable Over load setting (Breaking capacity 16 KA)-02 Nos. MCCB 63 Amp, 4 Pole , 415 Volts rating with,Adjustable Over load setting (Breaking capacity 16 KA) Ics=100% of Icu- 2 Nos. Spreader Terminal of both side complete all as specified and directed by Engineer-in-Charge. |
| 64 | Supply installation commission and testing of Out door LT Panel board of size 1200 x 1000 x 450 mm, (CPRI tested) LT415 Volts, 50 Hz , 3-phase,Bus Bar chamber comprising 4 Nos aluminium strip bus bars air insulated and PVC sheathed capacity 750 Amps with colour coding and suitable for 200 amps with main indication IA with selector switch 03 Nos, digital ammeter 0 to 200 amps with selector switch, digital volt meter 500V with selector switch and LED type/Neon type Indicating lamps panel mounting type RYB-3 Nos,factory assembled, outdoor type weather and vermin proof (Protection Class IP-54) made out of not less than 60 X 60 X 6 mm angle iron frame and 3.15 mm thick MS Sheet CRCA sheet with front hinged opening, rubber lining, locking arrangement, painted externally and internally with two coats of synthetic enamel gray paint(First Quality) over a coat of red oxide primer complete comprising of following (Feeder pillar for parking terminals) :-(a) Internal wiring with single core copper conductor cable/ PVC Insulated Copper Strip of suitable size incoming to bus bar and bus bar to outgoing MCCB/MCB-1Job. (b) Fine wiring with single core copper conductor cable for instruments/indicating lamps-1 Job.INCOMING : MCCB 500 Amp, 4 Pole , 415 Volts rating with Adjustable Thermal Magnetic Release (Breaking capacity 36KA) -1 No. OUTGOING: MCCB 400 Amp, 4 Pole , 415 Volts rating with Adjustable Thermal Magnetic Release (Breaking capacity 36KA) -1 No. MCCB 100 Amps, 4 Pole , 415 Volts rating with,Adjustable overload setting (Breaking capacity 16 KA) Ics=100% of Icu- 3 Nos. MCCB 63 Amps, 4 Pole , 415 Volts rating with,Adjustable overload setting (Breaking capacity16 KA) Ics=100% of Icu- 2 Nos. Spreader Terminal of both side -07 Nos complete all as specified and directed by Engineer-in-Charge. |
| 65 | S&F 1100 volts grade heavy duty cable PVC insulated aluminiuim multistranded of size 16 Sqmmserved with inner sheathing of PVC tape and overall PVC sheathed in service connections with one twin core cable flat or circularincluding cable lugs, jointing materials ,GI pipe etc., laid in trenches fixed on poles or laid through GI pipes complete all as specified and directed by Engineer-in-Charge. |
| 66 | S&F 1100 volts grade heavy duty cable PVC insulated aluminiuim multistranded of size 10 Sqmmserved with inner sheathing of PVC tape and overall PVC sheathed in service connections with one twin core cable flat or circularincluding cable lugs, jointing materials, GI pipe etc., laid in trenches fixed on poles or laid through GI pipes complete all as specified and directed by Engineer-in-Charge. |
| 67 | M&L for outdoor type Busbar Chamber of size 750mmx500mmx350mmfabricated by CRCA sheet 3.15mm and 60mmX60mmX6mm angle iron frame with front and back side opening with locking arrangement suitable for 600 Amps aluminium Busbar 415 Volts, 3 phase, 4 wire AC supply system mounted on DMC insulators 1.0 mtr long , 0.7 mtr above ground level and 0.30 mtr embedded in PCC blocks of size 0.30x0.30x0.30 mtr -04 Nos, painted using powder coating technology complete all as specified and directed by Engineer-in-Charge. |
| 68 | Supply/ Installing testing & commissioning of street Light Pole Box of 63 Amp single phase Two wire having two no Aluminium Bus Bar including 6 Amp SP MCB.The Box should have auto Door lock facility with magnetic lock having size 260X120X230 mm and fixed to poles/ Wall using MS strip of size 20x3mm and nuts & bolts of required size all as required at site complete all as specified and directed by Engineer-in-Charge. |
| 69 | S&F on load change over switch of capacity 200 Amps415 Volts 4 Polefixing , in Panel type and making the good distrubed surface of panel complete with all accessories, including taking down of old Unsv on load change over switch and reconnecting the cables with proper lugs complete all as specified and directed by Engineer-in-Charge. |
| 70 | S&F on load change over switch of capacity 125 Amps415 Volts 4 Polefixing , in Panel type and making the good distrubed surface of panel complete with all accessories, including taking down of old U/S on load change over switch and reconnecting the cables with proper lugs complete all as specified and directed by Engineer-in-Charge. |
| 71 | S&F off load change over switch of capacity 200 Amps415 Volts 4 Polefixing , in walltype and making the good distrubed surface complete with all accessories, including taking down of old unserviceable change over switch and reconnecting the cables with proper lugs complete all as specified and directed by Engineer-in-Charge. |
| 72 | S&F off load change over switch of capacity 125 Amps415 Volts 4 Polefixing , in walltypend making the good distrubed surfacecomplete with all accessories, including taking down of old unserviceable change over switch and reconnecting the cables with proper lugs complete all as specified and directed by Engineer-in-Charge. |
| 73 | Supply, installation and erection in true vertical position or to be planted as strut steel tubular swaged welded poles complete with MS base plate of 6mm thick of size 300mmx300mm at bottom duly welded and MS pole cap at top, poles shall made out of ERW MS tubing conforming to IS-1161 part-II, type 410 SP -31 (9.0m long) including drilling of holes of required size and Nos for fixing of cross arms/clamps,poles shall be painted internally throughout using anti corrosive black bituminous paint conforming to IS: 158-1968 and externally painted with two coat of red oxide primer and two coats of aluminum paint for expose surfaceand two coats ofblack bituminous paint for portion embedded in concrete, painting three black/white bands at lower portion of pole each of 300mm height at 300mm spacing, writing pole no. with black paint in yellow paint circle 10cm dia at suitable height complete all as specified and directed by Engineer-in-Charge. |
| 74 | M&L for earthing complete with galvanized steel earth plate electrode 600x600x6 mm thick buried directly in ground earth pit not less than 2.25mtr deep below normal ground level with top edge of the plate not less than 1.5 mtr below ground level connected to galvanized iron or steel earth lead wire 4mm dia size by mean of nut/bolt and washer of galvanized iron or steel as shown in electrical plate no 3 of SSR part I including necessary excavation and earth work GI pipe 20mm dia light grade for watering and GI 15mm dia light grade pipe for protection of GI earth wire etc, PCC chamber with PCC cover in cement concrete 1:2:4 Type B-1 (using 20mmgraded crushed stone aggregate), funnel, wire mesh, charcoal dust, salt etc, connected to DB as indicated including testing complete all as specified and directed by Engineer-in-Charge. |
| 75 | M&L for earthing complete with galvanized steel earth plate electrode 600x600x6 mm thick buried directly in ground (earth pit not less than 2.25 m deep below normal ground level) with top edge of the plate not less than 1.5 m below normal ground level connected to galvanized earth strip 32 x 6 mm (up to 7.5 m in length from earth plate ) by means of bolts and nuts checknuts and washers of galvanized iron or steel all as specified and shown in electrical plate no 3 of SSR part I including necessary excavation and earth work in any type of soil PCC 1:3:6 type C-1 chamber with RCC 1:2:4 type B-1, using 40 mm thick cover with MS rod 8mm dia 150mm long reinforcement, watering funnel, 40 mm dia medium grade for protection of earth electrode 20 mm dia for watering all as specified and directed and tested on completion complete all as specified and directed by Engineer-in-Charge. |