| 1 | Supply of Horizontal Split casing single stage pump having flanged suction & delivery and suitable to handle potable water. The pump should have following duties:-Discharge Capacity :- 115 -130 m3/hrDuty Head :- 40 Mtrs.Speed :- 1450 RPMMaterial of ConstructionCasing : CIShaft : Stainless Steel EN-8Impeller : CISleeve : SS-410Wear ring : CI Make: Mather & Plate / Kirloskar/Jyoti/Beacon weir/DJB approved |
| 2 | Supply of 30 HP 1500 RPM (Syn) squirrel cage induction motor suitable to operate on 400±10% Volt, 3Ph , 50Hz , Horizontal foot mounted confirming to IEC:60034-1. SOR(E&M)-2024 Item Code 3.2.18. Make:- ABB/Kirloskar/Jyoti/Crompton/DJB approved |
| 3 | Supply of MS Base frame, flexible Tyre coupling, coupling guard suitable for above pump sets. |
| 4 | Providing & fixing LT Starter Panel Board of size 1400x1200x350 mm made out of 14 SWG CRCA sheet floor mounted type and suitable to fix below mentioned items, i/c provision for cable entry & base frame made out of MS channel. The panel should be duly painted with vermin proof paint and completely wired with suitable size copper wire. Incomer consisting of following:- 1 no. automatic Phase Sequence Correcting Power Switch Circuit with a provision for manual operation : 250 Amps 4P, 415 VAC 50 Hz Make:-L&T/ABB/Schneider/Siemens/Socomec/HP ,1 no. MCCB TP 250 Amps 36 kA Thermal Magnetic with adjustable Trip Setting for Overload and Short Circuit Protection Make:-Siemens/L&T/ABB/Schneider , 1 No. voltmeter with VSS 0-500 VAC Digital Type 96mm X 96mm Make:- Rishabh/AE/L&T/Schneider , 1 No. ammeter with ASS 0 - 250 Amps Digital type 96mm X 96mm Make:- Rishabh/AE/L&T/Schneider , 1 No. energy Meter (KwHr) Digital Type CT operated Class 0.5 Make:- Rishabh/AE/L&T/Schneider , 3 Nos. CT 250 / 5 Amps Class : 0.5 for metering Make:- Kappa / AE , 1 No. CT 250 / 5 Amps for Power Factor Control Make:- Kappa / AE , 3 Set R Y B Indication Make:- Teknic / L&T / ABB / Schneider , 3 Set On / Off / Trip Indication Make:-Teknic / L&T / ABB / Schneider , 1 No. CBCT based Earth Fault Protection System to trip the MCCB in case of Earth Fault, Make:- Prok Devices / Elmeasure / Siemens / Schneider / ABB / L&T , 1. No Earth Fault Trip Indication suitable for operation of 2P/set Make:- Teknic / L&T / ABB / Schneider.Control consisting of following:-1 No. Current Transformer 415 VAC / 220 VAC 500 VA Make:- Logicstat / Eq ,2 Nos. Control MCB DP 10 Amps Make:- Siemens/L&T/ABB/Schneider , 1 No. Control On Indication Make:-Teknic / L&T / ABB / Schneider.Starter Section consisting of following:-30 HP Star / Delta Starter (1W + 1S) with following total material for both2 Nos. MCCB TP 36 kA Motor Duty Suitable for 30 HP Make:-Siemens/L&T/ABB/Schneider, 4 Nos. Contactor TP 95 Amps AC3 Duty 220 VAC Make:- Siemens/L&T/ABB/Schneider , 2 Nos. Contactor TP 63 Amps AC3 Duty 220 VAC Make:- Siemens/L&T/ABB/Schneider, 2 Nos. Thermal Over Load Relay 45-63 Amps Make:- Siemens/L&T/ABB/Schneider , 2 Nos. Single Phase / Phase Reversal Protection Make:- Minilec / L&T / E1 , 4 Set Start / Stop PB Make:- Teknic / L&T / ABB / Schneider , 4 Set On / Off / Trip Indication Make:- Teknic / L&T / ABB / Schneider , 4 Nos. Star / Delta Timer Make:- Siemens/L&T/ABB/Schneider.DOL Starter up to 5 H.P for 2 nos. P/set. having 2 No. MCB TP 16 Amps Make:- Siemens/L&T/ABB/Schneider , 1 No. Contactor 16 Amps TP 230 VAC Make:- Siemens/L&T/ABB/Schneider , 1 No. Overload Relay 2.8 - 4 Amps Make:- Siemens/L&T/ABB/Schneider , 1 No. Single Phase / Phase Reversal Protection Make:- Minilec / L&T / E1 , 2 Set Start / Stop PB Make:- Siemens/L&T/ABB/Schneider , 2 Set On / Off / Trip Indication Make:- Teknic / L&T / ABB / Schneider.Lighting Section having 4 Nos. 10 Amps SP MCB for lights/Fans etcMake:-Siemens/L&T/ABB/Schneider.Power Factor Section of 50 KVAR APFC System having1 No. MCCB TP 160 Amps Thermal Magnetic 36 kA for APFC section isolation Make:- Siemens/L&T/ABB/Schneider , 1 No. Microprocessor based APFC Relay 6 Steps Make:- Epcos / L&T / ABB / Beluk , 4 Nos. Capacitor Heavy Duty MPP 10 KVAR 415 VAC Make:- Epcos / L&T / ABB / Beluk , 4 Nos. Capacitor Duty Contactor suitable for 20 KVAR or higher 220 VAC Make:- Siemens/L&T/ABB/Schneider , 4 Nos. MCB TP 40 Amps Make:- Siemens/L&T/ABB/Schneider , 4 Nos. Auto / Manual Selector Switch with LED Indication Make:- Teknic / L&T / ABB / Schneider , 8 Set Start / Stop PB in manual mode Make:- Teknic / L&T / ABB / Schneider , 2 Nos. Capacitor Heavy Duty MPP 5 KVAR 415 VAC Make:- Epcos / L&T / ABB / Beluk , 2 Nos. Capacitor Duty Contactor suitable for 10 KVAR or higher 220 VAC Make:- Siemens/L&T/ABB/Schneider , 2 Nos. MCB TP 20 Amps Make:- Siemens/L&T/ABB/Schneider , 2 Nos. Auto / Manual Selector Switch with LED Indication Make:- Teknic / L&T / ABB / Schneider , 4 Set Start / Stop PB in manual mode Make:- Teknic / L&T / ABB / Schneider.Miscellaneous Material having 1 No. Bus Bar with heak shrinkable sleeves Make:- Hindalco / EC Grade with certificate , 1 No. Powder Coated Panel Enclosure with accessories Make:- DJB Approved , 1 No. Control wire. Make:- DJB Approved , 1 No. Power Wire. Make:- DJB Approved , 1 No. Dismantling of existing panel, 1 No. Delivery and installation of new panel, 1 No. Lugs / Glands as required for connections. |
| 5 | Supply of PVC insulated PVC sheathed armored aluminum conductor power cable 1.1 KV as per IS-1554 ( Part-I) of following sizes.3½ Core x 120 mm². |
| 6 | Supply of PVC Insulated un armored single core Flexible Copper Cable for working voltage upto 1.1 KV as per IS:694/2010 of size 35 mm2.. Make :Grandley / Gloster/DJB approved |
| 7 | Supply of CI Sluice Valves non rising with SS spindle ISI PN 1.0 IS 14846 flanged end of following sizes(a) 200 mm dia. |
| 8 | (b) 150 mm dia. |
| 9 | Supply of CI non return valve without bypass swing type IS:5312 flange end of 150 mm dia.Make:- Kirloskar/IVC/DJB approved |
| 10 | Pipes &SpecialS/o M.S. Pipe of dia.200 mm. |
| 11 | S/o M.S flange of dia. 200 mm. |
| 12 | S/o M.S. D.F.90° Bend of 200 mm dia. |
| 13 | S/o M.S. D.F.90° Bend of 150 mm dia. |
| 14 | S/o M.S. Pipe of 150 mm dia. |
| 15 | S/o M.S flange of dia. 150 mm. |
| 16 | S/o MS All flanged 200 x 200 x 200 mm dia. Tee. |
| 17 | S/o M.S All flanged 150x150x150mm dia. Tee. |
| 18 | Welding and fitting of above item as per site requirement. |
| 19 | Supply of vacuum pump set DV-40 in standard construction with bronze impeller, stainless steel shaft, CI body, complete with base frame, coupling, coupling guard etc.Make:- Kirloskar/DJB approved. Supply of squirrel cage induction motor TEFC, 5 HP 1500 RPM, suitable to operate 400±10% Volts, 3 Phase 50Hz AC supply.Make: Kirloskar / Jyoti / Crompton/DJB approved. |
| 20 | Providing &Fixing of 40 mm dia G.I. medium class pipe , pipe fittings like socket ,elbow ,Tee ,union , x-nipple , GM gate valve 40 mm dia( 4 Nos.) 15 mm dia( 1 No) with required fittings and base frame , 500 Ltr PVC tank to be placed on roof.Make:-Pipe : Jindal / ISI marked ,Fittings:- R- Brand / ISI marked ,Gate Valve:- SANT/LEADER/ISI marked. |
| 21 | Supply of 19 mm thick high voltage insulation mats, Size 1M X 2M. |
| 22 | Supply of Pressure gauge 150 mm dia. 0-100 PSI , GI pipe fitting , stock cock , copper tube , wooden board on the suction & delivery of each pump. One complete set of 250 mm dia. pressure gauge 0-100 PSI on main header with all fittings etc. 150 mm dia.Make:- H Guru / Fiebig |
| 23 | Supply of fire extinguisher powder type 4.5 Kg capacity. Make:- Bharat / Nithi / ISI Mark |
| 24 | Supply of fire bucket 9 liter capacity with stand of 6 nos. bucket. Make:- Spink/Arihant/DJB approved |
| 25 | Supply of nut bolt as per site requirement. |
| 26 | Supply of Rubber Sheet for packing as per site requirement. |
| 27 | Supply of change over switch 320 Amp , 4 Pole . 415 Volts ,Confirms to IEC: 60974-III/IS : 13947-II Make:- Havells/ABB/ DJB Approved |
| 28 | Fabrication / Supply& fixing of retro reflective sign board made out of 40 x 40 x 6mm MS angle iron frame & 2 mm thick MS sheet & 50 mm dia. GI pipe for supporting the board. The size of board 4 mtr. X 1mtr. Including grouting of board in proper way. The board shall be duly painted & matter to be written as per the direction of engineer in charge. |
| 29 | Providing / fixing of ISMB 300 x 140 mm along the length (7 mtrs.) of pump house with ISI marked triple spur geared chain pulley block with greed 80 alloy steel load chain tested to 50% overload confirming to IS- 3832 - 9087 of 2 ton capacity with overhead monorail travelling trolley with 5 mtr chain mounted on ISMB 300 x 140 approx. 7 mtr long. SOR(E&M)-2024 Item Code-7.27.10. Make:-Indef / Morris / Avon / Hercules / Reva /DJB approved |
| 30 | Earthing with GI earth plate 600 mm x 600 mm x 6 mm thick including accessories & providing masonry enclosure with cover plate having locking arrangement & watering pipe of 2.7 mtr long etc with charcoal / coke & salt as required. |
| 31 | Making of RCC foundation for 2 nos. P/Sets with all material like steel, cement, concrete, Foundation Bolt& all other related civil work required to complete the pump house |
| 32 | Installation, testing & commissioning of all above E&M equipment. It includes laying of pipe line, Cable as per the instruction of engineer in charge. Itjob also includes cost of cartage, painting, watch & ward of the materials at site and minor items/Jobs required (reducer, socket etc.) for pump house operational &commissioning the same up to the satisfaction of engineer in charge with one year guarantee. Please Enable Macros to View BoQ information |