| 1 | Supplying and laying of one number ISI marked PVC Insulated and PVC sheathed / XLPE Copper armoured power cable of 1.1 KV grade of following size on surface as required. Complete as directed by the Engineer-in-charge. |
| 2 | 4x10 sq.mm |
| 3 | Supplying and making end termination with brass compression gland and copper lugs for following size as required. |
| 4 | 4x10 sq. mm (25mm) |
| 5 | Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing as required. |
| 6 | 1X4 sq.mm |
| 7 | Providing and fixing following rating and breaking capacity 4 pole MCCB with thermomagnetic release and terminal spreaders with MCCB enclosure sheet steel including drilling holes, duly factory painted as required, making connections etc. as required. |
| 8 | 63A, 25 kA |
| 9 | Supplying and fixing 40A rating, 415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 10 | Triple pole |
| 11 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator). |
| 12 | 4 way (4+12), Double door |
| 13 | Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 14 | 63A |
| 15 | Supplying & fixing 5A to 32A rating, 240/415 V, 10kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connection, testing & commissioning etc. as required. |
| 16 | Single pole |
| 17 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 18 | 4 X 10 sq. mm + 2 X 6 sq. mm earth wire |