Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | SCHEDULE \"A\" : |
| 2 | Item No 01 :Surface excavation n.exc. 30cm deep and averaging 15cm deep and getting out in soft/ loose soil complete all as specified and directed. |
| 3 | Item No 02 : Excavation in trenches not exc. 1.5 metre wide and not exc. 1.50 metre in depth for foundation etc and for manholes etc n.exc. 10 Sqm on plan and n.exc. 1.5 metre depth and getting out in soft/loose soil complete all as specified and directed. |
| 4 | Item No 03 : Removing excavated materials (soils) to a distance not exc. 50 metre and depositing where directed at a level not exc. 1.50 above the starting point complete all as specified and directed. |
| 5 | Item No 04 : Returning filling in, including spreading, levelling, watering and well ramming in layers not exc. 25 cm thick as in soft/loose soil complete all as specified and directed. |
| 6 | Item No 05 : M & L for Moorum/red bajri filling in floors or pavings, laid in layers n exc. 15 cm thick, spread, levelled and rammed including watering |
| 7 | Item No 06 : Treating the backfill in contact with foundation at the rate of 7.5 litres of emulsion per square metre of vertical surface (Area of the substructure in contact with backfill to be measured) complete all as specified and directed. |
| 8 | Item No 07 : Material & labour for cement concrete (1:4:8) type D-2 (using 40mm graded stone aggregate) as in foundation filling and mass concrete and sub base of floor complete all as specified and directed. |
| 9 | Item No 08 : Use and waste of Formwork to sides of concrete foundations, footings, bases of columns, raft and raft beams, sides and soffits (if any) of foundation and plinth beams; and similar work; vertical or to batter complete all as specified and directed. |
| 10 | Item No 09 : Use and waste ofForm work of sides of pillars, posts, struts, piers, columns etcsquare or rectangular or polygonal rough surfaces of concrete complete all as specified and directed. |
| 11 | Item No 10 : M&L Form work to sides and soffits of beams lintels etc finishedroughcomplete all as specified and directed. |
| 12 | Item No 11 : Use and waste of Formwork to soffits of suspended slabs such as roof slabs, floor slabs, landings and similar work; not exceeding 200m thick flat fair finished surfaces of concrete complete all as specified and directed. |
| 13 | Item No 12 : M&Lfor form work to the edge of concrete flat n. exc 200 mm thickcomplete all as specified and directed. . |
| 14 | Item No 13 : Supply & fix mild steel TMT bars 10mm dia and over, cut to length, bent to shape required including cranking, bending spirally for hooping for columns, hooking ends and binding with mild steel wire (annealed) not less than 0.9mm dia complete all as specified and directed. |
| 15 | Item No 14 : Supply & fix mild steel TMT bars 6 to 8 mm dia and over, cut to length, bent to shape required as in stirrups complete all as specified and directed. |
| 16 | Item No 15 : M&L RCC 1:2:4 Tybe B1 using 20 mm graded stone aggregate as in Foundations, including rafts, footings, foundation beams; plinth beams; bases for columns, etc.; basement slabs, under reamed piles and mass concrete complete all as specified and directed. |
| 17 | Item No 16 : M & L RCC 1:2:4 Type B1 using 20 mm graded stone aggregate as in Columns, pillars etc complete all as specified and directed. |
| 18 | Item No 17 : M & L RCC 1:2:4 Type B1 using 20 mm graded stone aggregate as in beams, lintels over 1.5 m span etc complete all as specified and directed. |
| 19 | Item No 18 : M&L for RCC M 1:1.5:3type A-1 using 20 mm graded stone aggregate for roof slabs supported on walls, beams and the like complete all as specified and directed. |
| 20 | Item No 19 : Material & labour brick work with fly ash bricks in CM 1;6 brickstraight or curved on plain exeeding 6m mean radius complete all as specified. |
| 21 | Item No 20 : Material & labour for brick work with sub class ‘B’ bricks, straight or curved on plan, exc. 6 metre mean radius built in CM(1:4)as in half brick thick walls complete all as specified and directed. |
| 22 | Item No 21 : Supply only integral water proofing compound all as in specified & directed. |
| 23 | Item No 22 : Material & labour for 15 mm thick rendering in CM 1:6 on fair faces of brick work or concrete surfaces, surfacesfinished even and smooth without using extra cement complete all as specified and directed. |
| 24 | Item No 23 : Material & labour for 15 mm thick rendering on other than fair faces of brick work or concrete surfaces,inCM(1:4)surface finished even and smooth without using extra cement complete all as specified and directed. |
| 25 | Item No 24 : Material & labour for 5 mm thick plaster in CM 1:3 on ceiling surfaces, surfacesfinished even and smooth without using extra cement complete all as specified and directed. |
| 26 | Item No 25 :M/L 75 mm thick cement concrete 1:3:6 type C-2 using (40 mm graded stone agg) as in sub base complete all as specified and directed. |
| 27 | Item No 26 : M&L Machine cut kota stone slab flooring 20-25mm thick over incl 20mm thick cement screed base laid and jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing and polishing complete and incl screed bed of CM 1:6 complete all as specified and directed. |
| 28 | Item No 27 : M&L Kota stone slab 20-25mm thick in riser of steps, skirting, dado and pillar laid over cement screed and jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing and polishing complete and inclCM 1:4 complete all as specified and directed. |
| 29 | Item No 28 : M&L Non Skid ceramic tiles7 to 8mm thick (squares/rectangular) area of each tile exceeding 0.06 sqm but not exceeding 0.11 sqm,in floors etc. set and jointed in neat cement slurry and pointed in white or coloured cement to match 15mm thick screed bed in CM 1:6 complete all as specified and directed |
| 30 | Item No 29 : Material & labour for glazed coloured ceramic tiles of size450x300x7-8mm thick,on vertical surfaces set and jointed in neat cement slurry and pointed in white/ coloured cement to match with existing work over and including 10mm thick rendering in CM 1:4 complete all as specified & directed. |
| 31 | Item No 30 : M&L 50mm thick PCC 1:3:6 type C-1 (using 20mm graded stone aggregate) as in path /plinth protection , finish even & smooth without using extra cementall as specified and directed. |
| 32 | Item No 31 : Material & labour for preparation of new plastered surfaces of walls etcand applying two coats of cement base paint over a coat of primercomplete all as specified & directed. |
| 33 | Item No 32 : Material & labour for preparation of new plastered surfaces of walls with wall care putty and applying two coats of Oil bound distemper to match the existing surfaces as required, complete all as specified & directed. |
| 34 | Item No 33 : Material and labour for preparation of new plastered surfaces of ceiling and applying three coats of white wash complete all as specified & directed. |
| 35 | Item No 34 : Material and Labour for 20mm thick cement paster in CM 1:4 mixed with WPC @ 2 % by weight of cement finised even and smooth without using extra cement on roof surface and wall (WPC will be measured and paid seperately as supply only rate). |
| 36 | Item No 35 : Supply only liquid water proofing compound |
| 37 | Item No 36 : M&L for applying a coat of bitumen primer @ 0.3L/sqm on roof surfaces |
| 38 | Item No 37 : M&L for applying 3mm thick APP modified polymeric membrane over the bitumen coat surface weight not less than 3kg/sqm and over lap 100mm and sealed by torch application as per manufacture insteructions complte all as specified and directed |
| 39 | Item No 38 : S & F Solid PVC Door Frame of size 50mm x 47mm made out of 5mm plain colour PVC sheet reinforced with M.S. Square tube, suppling & fixing in opening as per specification & drawing |
| 40 | Item No 39 : Supply & fix factory made solid panel PVC door shutter 30mm thick (style) consisting of frame, made out of MS tubes for top and bottom rails MS frame shall be covered with heat moulded plain colour PVC , ‘C’ channel having a PVC sheet strip of 20mm width stuck inside with solvent cement for stiles and plain colour PVC sheets for top rail, lock rail & bottom rail on either side & as gap insert for to rail & bottom rail, paneling of plain colour PVC sheet to be fitted in the MS frame welded/sealed to the stiles & rails with suitable PVC sheet beading and jointed to getter with solvent cement, supplying & fixing in the frame at site as per specification & drawing for Item No. 08080 on page No 156 of SSR 2010 (Part-II). |
| 41 | Item No 40 : Supply & fix 125mm size aluminium alloy handles cast type anodized complete all as specified & directed. |
| 42 | Item No 41 : S&F aluminium tower bolts 150mm long, of extruded section. |
| 43 | Item No 42 : Supply & fix Aluminium. Sliding door bolts, plate type,complete, 250mm long complete all as specified and directed. |
| 44 | Item No 43 : S&FGun -metal,globe or gate valves,with iron wheel head ,screwed both ends for iron pipe and fixed. |
| 45 | Item No 44 : Supply & fixbib taps cast copper alloychromium plated with crutch or butterfly handle, screwed down, screwed for iron pipe of 15mm bore, complete all as specified & directed. |
| 46 | Item No 45 : Supply & fix invitreous china wash hand basin, white, flat back of size 550x400mm (excluding taps, waste chain and plug and porcelain stopper) but including brackets suitable for 15mm dia pipe complete all as specified & directed. |
| 47 | Item No 46 : Supply & fix angular valve, 15 mm dia, cast copper alloy, chromium plated, fancy type with long shank and cup, screwed down, high pressure screwed both ends for iron pipes or for unions and fixed in pipe complete all as specified & directed. |
| 48 | Item No 47 : Supply & fix rotational moulded polyethylene water storage tanks 500 liters capacity, (cylindrical, vertical in closed top) hoisted and fixed in position with all fittings all as specified directed. |
| 49 | Item No 48 : Supply & fix inPVC low level flushing cistern of 9-10 ltrs capacity, ISI Marked, white, symphonic action type with inlet, ball valve, float and handle including brackets and PVC flush pipe of 32 mm bore, suitable for low level cistern complete all as specified & directed. |
| 50 | Item No 49 : Supply, fix 15mm bore, tubes medium grade, galvanized with all fittings and fixed to walls and ceiling or laid in floors including testing complete all as specified & directed. |
| 51 | Item No 50 : Supply, fix 20 mm bore, tubes medium grade, galvanized with all fittings and fixed to walls and ceiling or laid in floors including testing complete all as specified & directed. |
| 52 | Item No 51 : Supply & fix Vitreous China wash down water closet pan (pedestal pattern), white (excluding fixing bolts, flushing cistern and flush pipe) including replacement of ‘P’ or ‘S’ trap, lime concrete bedding and making good floor complete all as specified and directed. |
| 53 | Item No 52 : Supply & fixpillar taps, fancy typecast copper alloy with capstan heads, chromium plated, screwed down, high pressure with or without lettered “hot” or “cold” with long screwed shanks and fly nut screwed for iron pipe of 15mm bore,complete all as specified & directed. |
| 54 | Item No 53 : S&F Flush pipe of polyethylene of low or high density of PVC, 32 mm dia, for low level cistern |
| 55 | Item No 54 : S&F PVC (SWR) pipes 110 mm bore single socketed, in any length with rubber ring joints laid in trenches or in floors |
| 56 | Item No 55 : S&F PVC (SWR) pipes 110 mm bore single socketed in any length with rubber ring joints fixed to walls |
| 57 | Item No 56 : PVC (SWR), junction single, (Single T) equal or unequal 110 mm bore |
| 58 | Item No 57 : S&F 600mmx750mm fancy type bevelled edge mirror of selected quality glass, mounted on 6mm thick AC building board or commercial plywood and fixed to wooden plugs with chromium plated brass screws and cup washers |
| 59 | Item No 58 : S&F Tubular towel rail 20mm dia, D type, 60cm long between flanges |
| 60 | Item No 59 : M&L Concrete bed to drain pipes 150mm, including packing under, and haunching against the sides of pipes after they are laid and tested; in PCC(1:4:8) Type D-2. |
| 61 | Item No 60 : M&L for Ultra plus PE, DWCPE (Double waal corrugated)pipe conforming to IS -16098 Part-2:2013 pertaining Structured wall plastics pining system for Non-Pressure drainage and sewage 150mm bore pipe and fittings with non smooth surface, typeB complete all as specified and diredted |
| 62 | Item No 61 : M & L Soakage wells excavation, in any type of soil, foundation in PCC 1:3:6, walls of honey combed masonry with top ring of M25 concrete including intercepting chamber and screen chamber made of Brick masonary in CM, RCC cover slab in M25/ SFRC cover, interconnecting pipes of RCC/DWC complete filled with brick bats of size 1.2m dia x 2.0m eff depth complete all as specified and directed |
| 63 | Item No 62 : M & L Septic tanks, exc in ordinary soil, foundation in PCC !:2:4,brick work in CM 1:4 RCC slab covers including RCC precast manhole cover having 6 mm plate embedded all round / fibre reinforced cover with iron frame Vent shaft and sludgechambers etc, complete for 25 users complete all as specified and directed. |
| 64 | Item No 63 : M&L Non Skid ceramic tiles7-8 mm thick (squares/rectangular) area of each tile exceeding 0.11 sqm but not exceeding 0.18 sqm, (400 x 400 x 10mm) in floors etc. set and jointed in neat cement slurry and pointed in white or coloured cement joint free non skid tiles.to match 15mm thick screed bed in CM 1:6 complete all as specified and directed |
| 65 | Item No 64 : Material & labour for glazed coloured ceramic tiles of size450x300x7-8mm thick,on vertical surfaces set and jointed in neat cement slurry and pointed in white/ coloured cement to match with existing work over and including 10mm thick rendering in CM 1:4 complete all as specified & directed. |
| 66 | Item No 65 : S&F Steel rolling shutters, thickness of laths 1.25mm, without ball bearing, as specified including top cover, anchoring rod, hasp and staple and one shop coat of primer; erected in position as indi cated, complete: push pull or manual type |
| 67 | Item No 66 : Safety lever locks mild steel with 4 levers for rolling shutters |
| 68 | Item No 67 : Ball bearing for rolling shutters |
| 69 | Item No 68 : M&L preparation of new or previously untreated steel surface of any description over 10cm width or girth and applying two coat of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed. |
| 70 | Item No 69 : Supply & fix mild steel framed work such as grills, grating etc with end of bars shouldered and/ or riveted forged into spikes, framed guard bars, railings and similar work complete conforming to Fe-410-0 or Fe-310-0. |
| 71 | Item No 70 : S&F 100 mm thickMachine pressed precast concrete colouredinterlocking paver block any shape and size confirming to IS 15658-2006 , M-50 Grade with grey cement and no pigment complete all as specified and directed. |
| 72 | Item No 71 : M/L 75 mm thick cement concrete 1:4:8 type D-2 using (40 mm graded stone agg) as in sub base complete all as specified and directed. |
| 73 | Item No 72 : M&L supply and laying of sand including spreading, levelling and ramming in layers n.exc. 25 Mm thick in each layer complete all as directed |
| 74 | Item No 73 : M & L Steel window box type using ERW \"P\" section comprising double frame for gauged and glazed skeleton shutter jointed internally with flat iron 40x3mm complete including hinges, handle tower bolts stops, lugs etc all as shown on drawing Note (i) For the purpose of measurement & payment double shutter with frame shall be considered as one unit (ii) Unit rate quoted against this item shall also include the iron mangeryas shown on drgs (iii) Guard bars glazing & wire mesh shall be measured & paid for separately complete all as specified and directed. . |
| 75 | Item No 74 : Supply & fix 3mm thick sheet glass, pin headed, and glazing with oil putty/beading in square not exceeding 0.50sqm each pane complete all as specified & directed. |
| 76 | Item No 75 : Supply & fix galvanized mild steel wire cloth with 0.56 mm nominal dia of wire and average width of aperture 1.18 mm and fixed with tinned tacks or galvanized wire staples complete all as specified & directed. |
| 77 | 33 kV Cable Work |
| 78 | Item No 76 : Supply, laying & testing cable XLPE insulated screened PVC bedded,galvanized steel strip armoured, electric power cables (heavy duty) with stranded aluminium conductor, 33000 volts grade, of size 3 core 300 sq mm. |
| 79 | Item No 77 : M&L Steel tubular swaged poles complete with cast iron base plate,finial taper plug,bolts,nuts & screws as specified type 410 SP-64 ( 12.00 Meters long) complete all as specified and directed at site rate include necessary excavation ,earth work & PCC work complete . |
| 80 | Item No 78 : Supply and fix cable jointing kit for 33 KV grade cable for outdoor terminationheat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of size300sqmm. |
| 81 | Item No 79 : Supply and fix cable jointing kit for 33 KVgrade cable for straight throughheatshrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured Al conductor cable of size 300 Sqmm, Indoor/Outdoor type. |
| 82 | Item No 80 : Supply and fixtouch proof cable jointing kit for 33 KVgrade cable for end termination of 33 kV RMU terminationshrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured Al conductor cable of size 300 Sqmm, Indoor/Outdoor type. |
| 83 | Item No 81 : M&L mild steel as in cross arms bracing supports clamps and back planes fabricated from structural steel section including nut, bolts washers welding welding drilling holes for bolts in any shape and size as indicated or directedand inclusive of one proimer coat one undercoat one finishing coat of aluminium paint complete. paint complete to support the cables all as specified. |
| 84 | Outdoor Substation Work |
| 85 | Item No 82 : M&L for stringing and fixing in position of ACSR conductor of any size as per site requirement including provision of aluminum binding wire complete all as specified and directed. |
| 86 | Item No 83 : Supply and installation of copper cylindrical hollow pipe for bus bar structure for R, Y, and B phases, size of the pipe will be desided as per current carring capcity and fault level, bus bar shall be fixed on the top of the structure using 33 kV insulators. The scope includes the supply, transportation, and installation of the copper bus bar, along with all required jointing connectors for seamless connectivity.Note:The cost of all jointing connectors of the copper bus bar is deemed to be included in the quoted rates. |
| 87 | Item No 84 : Supply and fix 33 kV Post type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut complete all as directed by engr in charge |
| 88 | Item No 85 : Supply and fix 33 kV Pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut complete all as directed. |
| 89 | Item No 86 : Supply and fix 11 kV Post type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut complete all as directed. |
| 90 | Item No 87 : Supply and fix 11 kV Pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut complete all as directed. |
| 91 | Item No 88 : S&F lightening arrestor non linear pole type MCOV 33KV, normaldischarge capacity 65KA and impulse current with all fittings suitable for 33 KV electric working pressure including strap bolts and nuts and washers etc complete all as specified and as directed. |
| 92 | Item No 89 : S&F air break switch (GOD) vertical/horizontal, double breaktype triple pole mechanically operated mounted on double insulartors and steel frame with operating mechanism linked with ground level operating GI rod 25mm dia medium grade.GOD suitable for current rating upto 400 amps and suitable for HT 33 KV including connecting complete with locking arrangement complete all as specified and as directed. |
| 93 | Item No 90 : S&F horn gap fuse unit assembly triple pole outdoor type suitable for HT 33 KV 400 Amps complete all as specified and as directed. |
| 94 | Item No 91 : S&F air break switch (GOD) vertical/horizontal, double breaktype triple pole mechanically operated mounted on double insulartors and steel frame with operating mechanism linked with ground level operating GI rod 25mm dia medium grade.GOD suitable for current rating upto 400 amps and suitable for HT 11 KV including connecting complete with locking arrangement complete all as specified and as directed. |
| 95 | Item No 92 : S&F horn gap fuse unit assembly triple pole outdoor type suitable for HT 11 KV 400 Amps complete all as specified and as directed. |
| 96 | Item No 93 : S&F lightening arrestor non linear, pole type MCOV 11 KV discharge capacity 65 KA, with all fittings suitable for 11 KV electric working pressure including strap, bolts, nuts and washers etc complete all as specified and as directed. |
| 97 | Item No 94 : Shifting of 33kV outdoor VCB with its indoor panel along with a set of CTs & PTs, including GI structure by disconnecting all electrical and mechanical connections of the VCB, indoor panel, CTs, and PTs. Removing and carefully handling the GI structure. Ensuring proper marking and labeling of control cables for reassembly. Transporting the dismantled equipment to the new substation 4 km away using appropriate vehicles and ensuring safety during transit. Fixing the GI structure at the new site, including all necessary earthwork and PCC work. Reassembling the VCB, indoor panel, CTs, and PTs as per the original setup. Reconnecting all electrical, mechanical, control, and auxiliary connections. Testing to ensure all equipment functions as per specifications.Note : (i) Cost of control cable is excluded and will be measured and paid separately. (ii) Any damage to equipment during dismantling, transportation, or installation must be repaired/replaced by the contractor at no extra cost.(iii) All work must be executed as per the directions of the Engineer-in-Charge and meet the required safety and technical standards.(iv) Earthwork and PCC Work included in the quoted rate for fixing the GI structure. (v) Testing to ensure all equipment functions as per specifications. |
| 98 | Item No 95 : Supply,laying,jointing,testing and commissioning XLPE insulated control solid copper conductor, armoured, heavy duty, 650/1100 volts grade cross sectional area 1.5 sqmm 10 core connected as per latest amendment of IS 7098 (Part 1) with copper lugs connected by cramping tools complete all as specified and directed. Note:- Excavation and earth work will be measured and paid separately. |
| 99 | Item No 96 : Supply,laying,jointing,testing and commissioning XLPE insulated control solid copper conductor, armoured, heavy duty, 650/1100 volts grade cross sectional area 1.5 sqmm 6 core connected as per latest amendment of IS 7098 (Part 1) with copper lugs connected by cramping tools complete all as specified and directed. Note:- Excavation and earth work will be measured and paid separately. |
| 100 | Item No 97 : Shifting of 33/11 kV, 3.15 MVA Power Transformer by disconnecting all HV, LV, and neutral connections, disconnecting and properly labeling control cables and auxiliary connections to ensure accurate reconnection later. disconnecting all existing connections of the transformer at the Main Receiving Station (MRS), safely lifting the transformer onto a suitable vehicle, transporting it to the new substation in Dipatoli Military Station within a 4 km, positioning the transformer on the foundation or plinth as required, and making all necessary reconnections under the supervision and as directed by the Engineer-in-Charge. Note : (i) The contractor shall be solely responsible for any damage to the transformer during disconnection, transportation, or reinstallation all damages must be repaired or compensated by the contractor at their own cost. (ii) All work must be executed under the supervision and as per the directions of the Engineer-in-Charge.(iii) The contractor must arrange all necessary tools, lifting equipment, vehicles, and safety gear.(iv) Energizing the transformer under the supervision of the Engineer-in-Charge to ensure proper operation. |
| 101 | Item No 98 : Shifting of 33kV 3 way RMU (Ring Main Unit) safely disconnecting all LT (Low Tension) connections, removing and properly isolating 33kV cables from the cable termination box. proper labeling and marking of cables for accurate reconnection, transporting the RMU safely to the new substation location witin 4 KM using suitable vehicles and handling equipment ensuring the RMU is secured properly during transit to avoid damage fixing the RMU at the new location as per the instructions of the Engineer-in-Charge reconnecting all 33kV cables, LT connections, and control cable connections ensuring proper alignment, grounding, and secure installation of the RMU.Note : (i) The contractor shall be solely responsible for any damage to the transformer during disconnection, transportation, or reinstallation all damages must be repaired or compensated by the contractor at their own cost. (ii) All work must be executed under the supervision and as per the directions of the Engineer-in-Charge.(iii) The contractor must arrange all necessary tools, lifting equipment, vehicles, and safety gear.(iv) Energizing the RMU under the supervision of the Engineer-in-Charge to ensure proper operation |
| 102 | Item No 99 : Material and labour XLPE insulated ,screened ,PVC bedded,galvanised steel strip or wire armoured,electric power cables (heavy duty) with aluminium conductor,11000 volts(Earthed),grade cross sectional area 95 sqmm |
| 103 | Item No 100 : Material & Labour cablejointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 70 sqmm to 95 sqmm completeall as specified and directed at site. |
| 104 | Item No 101 : Material & Labour cablejointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 70 sqmm to 95 sqmm completeall as specified and directed at site. |
| 105 | Item No 102 : Material & Labour cablejointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 70 sqmm to 95 sqmm completeall as specified and directed at site. |
| 106 | Item No 103 : Supplying, installing, testing and commissioning of Indoor arc flash protected Draw-Out with roll on floor type Vacuum Circuit Breaker Panel , rated for 11kV, 50 Hz, 3 Phase, Min rupturing capacity 350 MVA, 800 Amp, 26.3kA/3-sec, comprising of 03 Nos. Incomer andOutgoing VCB Panelsand floor-mounted Bus PTs for each bus section, confirming to IEC 62271-200, Internal Arc Classified IAC AFLR – 26.3kA for 1sec, Accessibility Class LSC2B-PM Class, comprising of 800 Amp, continuous rated Copperbusbars and droppers in all bus / breaker/ adaptor and and cable chambers, The busbars to be covered with insulating material, The earthing busbar is made of electrolytic copper and it runs longitudinally throughout the switchgear Encapsulated feeder connections IS3427 and IS12729. with 01no. . Rack-In-Rack-Out Handles, structure made from AluZinc/GI sheets to prevent corrosion and rusting.The complete panel incl. HT and LT chamber with FRLS wiring and acessoriesshall be manufactured by approved OEM at its own mancufacturing in house facility, and same will be verified via stage/final inspection. system house integrator / channel partner products arenot accepted complete all as specified and directed |
| 107 | (A) 03 x Incomer Panel, each comprising of :- |
| 108 | (i) 11kV, 800 Amp, 26.3kA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100 with roll on floor type Vacuum Circuit Breaker having 03 Nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24VDC). |
| 109 | (ii) Current Transformers 11kV, 400/200/5A Core1: Class 5P10, 5VA, Core2: Class 0.5, 5VA, Remote HMI, Digital electronic governor with temperture Core3: Class PS-X - Set of 03 No per breaker |
| 110 | (iii) Potential Transformers, Draw-out type for easy maintenance, 11kV/rt3:110V/rt3, 50VA, Cl.0.5 with associated gun-type HRC fuses and MCBs for HT/LT isolation - complete set per breaker |
| 111 | (iv) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04CT+05PT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) Directional over-current or earth-fault in any of the three phases, (b) Synchronism and Energizing Check before breaker closing to prevent un-syncronized mixing of supplies(c) circuit-breaker-failure alarm, (d) interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. |
| 112 | (e) Integrted arc flash protection with current and light sensingThe relay shall be communicable on IEC 61850 GOOSE platform over RJ-45/USB/FO port, and fully integrated with the feeder, internally capturing feeder statuses incl. various status, Line-Current, Line-Voltage, Breaker On/Off/Spring.Chrgd, Trip Circuit Failure (from TCS relay), AC Supply Fail, PT Fuse failure relay, Local-Remote etc. and display locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with power & frequency measurements and suitably labelled status LEDs.Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer. |
| 113 | (v) Metering Equipment including:-(a) 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), (b) 01no. Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring current, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on ModBus via RS485 port. |
| 114 | (vi) LED Indications :- (a) Breaker ON/OFF/TRIP/Spring-Charged, (b) R-Y-B, (c) DC Available LED with push-button(d) AC Supply Fail(e) Trip Circuit Healthy |
| 115 | (vii) 08-Window Annunciator with Hooter to indicate following alarms :- (a) OC Trip, (b) EF Trip(c) Trip Circuit Failure, (d) Inter-Tripping Fault, (e) Synchro-Check. (f) PT Fuse FailureThe Annunciator will be complete with required Acknowledge/Test buttons as required |
| 116 | (viii) Control Equipment incl. :-(a) 01 x TNC Switch, (b) 01 x Local/Remote Switch, (c) 01 x Emergency Trip Push Button, (d) MCBs for AC(e) MCBs for DC(f) Heater Switch with Thermostat - 01no.(g) 3-pin socket with ON/OFF switch - 01no.(h) LED Lamp with ON/OFF switch - 01no. |
| 117 | (ix) Flush mounted Auxillary Protection Relays incl:-(a) Trip Circuit Supervision Relay, (b) Master trip Relay, (c) PT Fuse failure relay.(d) DC Supervision Scheme |
| 118 | (x) Suitable Disconnecting Link type terminal arrangement shall be provided for interfacing PS-Class CTs installed in the panel for achieving the required protection. |
| 119 | (B) 11 x Outgoing Panel, each comprising of :-(i) 11kV, 630Amp, 26.3KA/3-sec, Draw-Out Vacuum Circuit Breaker as per IEC-62271-100. Vacuum Circuit Breaker having 03nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (24VDC). |
| 120 | (ii) Current Transformers 11kV, 150-75/5A, for 2 breakers and 100-50/5A for 2 breakers Core1: Class 5P10, 10VA, Core2: Class 0.5, 10VA - Set of 03Nos.each/ breaker |
| 121 | (iii) Main Protection Relay shall be numerical IED Relay confirming to IEC60255, having 04CT Inputs with microprocessor based protection scheme for tripping the breaker on various faults like (a) over-current or earth-fault in any of the three phases, (b) circuit-breaker-failure alarm, (c) interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol. (d) Integrted arc flash protection with current and light sensing. |
| 122 | (e )Transformer protection (Marshalling Box and Buchhloz relay).The relay shall be communicable on IEC 61850 GOOSE platform over RJ-45/USB/FO port, and fully integrated with the feeder, internally capturing feeder statuses incl. various status, Line-Current, Breaker On/Off/Spring.Chrgd, Trip Circuit Failure (from TCS relay), Local-Remote etc. and display locally on a built-in back-lit LCD screen with mimic as a Single-Line-Diagram with current measurements and suitably labelled status LEDs.Relay setting should be possible through inbuilt software or through addtional software supplied with life time software support by the relay manufacturer. |
| 123 | (iv) Metering Equipment including:-(a) 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), (b) 01no. Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring current, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on ModBus via RS485 port. |
| 124 | (v) LED Indications - (a) Breaker ON/OFF/TRIP/Spring-Charged, (b) Trip Circuit Healthy |
| 125 | (vi) 08-Window Annunciator with Hooter to indicate following alarms :- (a) OC Trip, (b) EF Trip(c) Trip Circuit Failure, (d) Inter-Tripping Fault, The Annunciator will be complete with required Acknowledge/Test buttons as required |
| 126 | (vii) Control Equipment incl. (a) 01 x TNC Switch, (b) 01 x Emergency Trip Push Button, (c) 01 x Local/Remote Switch, (d) MCBs for AC/DC isolation(e) Heater Switch with Thermostat - 01no.(f) 3-pin socket with ON/OFF switch - 01no.(g) LEDLamp with ON/OFF switch - 01no. |
| 127 | (viii) Flush mounted Auxillary Protection Relays incl. (a) Trip Circuit Supervision Relay, (b) Master trip Relay, |
| 128 | (ix) Transformer protection each comprising of :-(a)Oil Temperature high.(b)Winding Temperature high.(c ) Tank oil level low. (d) OLTC oil level low.(e) Buchhloz relay trip or sudden gas and sudden oil pressure relay trip.(f)Pressure relief. |
| 129 | (C) 11 Nos including Battery Bank consisting of 55 Nos of batteries each of 2 volts, 120 Ah connected in series with single core Cu wire and terminals and battery Charger of size 110 Volt,20 Amp with following specification :-(a) Rated Input Volts - 415 V AC(b) Rated Output Volt - 120 V DC(c ) Charging current for Float charger 20 Amps and for boost charger 40 Amps(d) Float charger voltage control should be stepless (e) Temperature rise on float charger at rated current must be within range of 30-50 DEG C.(f) Details of transformer of float charger unit:- |
| 130 | (i) Capacity - 4 Kva(ii) Wire Size - 1.8 Sqmm/ 14.4 Sqmm (iii) No of turns of primary/ secondary - 192 T/ 24 T(iv) Flux density - 1.42 Tesla (v) Core Type - CRGO (f) Details of transformer of Boost charger unit:- (i) Capacity - 9 Kva(ii) Wire Size - 2.9 Sqmm/ 21.8 Sqmm(iii) No of turns of primary/ secondary - 231 T/ 30 T(iv) Flux density - 1.42 Tesla(v) Core Type - CRGO |
| 131 | Note:- Rate Quoted by the firm for this item should include the cost of the activities:-(i) PCC work / any civil work for foundation required for errection of VCB and other accessories all as per standard norns.(ii) Contractor shall submit type test certificate to the engineer - in - charge / GE for approval before placing the order.(iii) The contractor will be submitted the NABL accredited lab test reports in original and the same shall be produced well before claiming RAR payment .(iv) The drawings in respect of VCB shall be approved by accepting officer before placing order.(v) VCB shall be tested by representative of Accepting Officer at factory premises before dispatch. All arrangeementfor the same shall be arranged by the contractor. |
| 132 | Item No 104 : Material and labour for 11 kV bus coupler panel, designed for indoor installation in electrical distribution networks, operational flexibility by interconnecting two bus sections to allow power flow and load sharing, Metal-clad, totally enclosed, indoor type, 11 kV, 3-phase, 50 Hz, 630 Amps capacity, Air-insulated with adequate creepage distance complete all as specified and directed. |
| 133 | Earth Work |
| 134 | Item No 105 : Material and labour for river washed and screened ,dry sand for filling in trenches/sub stationsbelow and around underground cables for cushioning of cables etc complete all as specified. |
| 135 | Item No 106 : Supplying and laying unreinforced precast cement concrete cable covers, Class EHV, Type- 2, Flat, size 450 mm x 180 mm x 40 mm with peak as per relevant IS in trenches for cable protection, embossed with \"MES 33 KV HT ELECTRIC\" on the top surface complete all as specified and as directed. |
| 136 | Item No 107 : Supplying and laying unreinforced precast cement concrete cable covers, Class HV, Type- 1, Flat, size 300 mm x 180 mm x 40 mm in trenches for cable protection, embossed with \"MES 11 kV HT ELECTRIC\" on the top surface complete all as specified and as directed. |
| 137 | Item No 108 : S & F Cable route indicator / Marker made up of PCC Block in cement mortar 1:3:6 (20 mm graded aggregrate) of size 900 x 300x 100 mm thick with \"MES 33 KV CABLE /MES 33 KV HT JOINT\" embossing on cable route Indicator / Marker including painting as per approved colour and buried in ground 45 Cms including necessary earth work (as required/ ordered at site) complete all as specified and as directed. |
| 138 | Item No 109 : S & F Cable route indicator / Marker made up of PCC Block in cement mortar 1:3:6 (20 mm graded aggregrate) of size 900 x 300x 100 mm thick with \"MES 11 KV CABLE /MES 11 KV HT JOINT\" embossing on cable route Indicator / Marker including painting as per approved colour and buried in ground 45 Cms including necessary earth work (as required/ ordered at site) complete all as specified and as directed. |
| 139 | Item No 110 : M&L for trenchless boring of 175mm bore under road crossing/foot paths etc complete all as specified and directed at site. |
| 140 | Item No 111 : Supply and fixing GI Pipe light grade of size 150 mm dia with all fittings for passing of cables fixed to pole / wall / laid under floor or roads including all fixing accessories complete for protection of cable all as specified and directed. |
| 141 | Item No 112 : Supply and laying of GI pipe 100 mm bore,Light grade (for cable protection ) with all fittings for passing of cables fixed to pole / wall / laid under floor or roads including all fixing accessories complete for protection of cable all as specified and directed. |
| 142 | Item No 113 : M & L hardcore of gauge n-exc. 40mm, deposited, spread and levelled in layers n exc. 15cm thick, watered and rammed to a true surface. |
| 143 | Item No 114 : M & L Cement Concrete PCC 1:3:6 (20 mm graded aggregate) as in coping of poleetc including form work & finishing the surfaces even & smooth with out using extra cement complete all as specified |
| 144 | Item No 115 : M &L for GI Earthing complete with GI earth plate electrode 60cm x 60cm x6 mm buried directly in ground verticvally to size of depth not less than 0.90x 0.60 x 2.25 mtr below ground level with top edge of the plate at a depth not less than 1.5 mtr below ground level, earth plate connected to galvanised earth strip of size 32 X6 mm, 7.5 mtr long by means of brazing nuts, bolts, check nuts, & washers ,testing of completion (drawn in earth lead protection pipe light gade GI of size 32/40 mm dia) by means brazing at both edges with vertical plane of electrode all as shown in plate No 3 of SSR Part - I connected to earthing lead with Main switch/main control board,filling with charcoal dust 200 Kg, and common salt 100 KG , including necessary excavation and earth work in any type of soil ,perforated watering pipe,funnel with wire mesh,earth lead protection pipe light grade PCC chamber 1:3:6 type C1 (for even finish on both the faces) and RCC cover 1:2:4 Type B1,450 x450 x50 mm thick with 6 mm dia CTD bars 150 mm c/c with 2 Nos of handles of 10 mm dia steel rod all as specified and directed and testing on completion and connected to equipment with lugs and screw nuts etc all as specified and directed by EIC |
| 145 | Note : (i) 7.5 RM GI earth wire deemed to be included in quoted rates beyond 7.5 RM wire shall be measured and paid separately. (ii) Earth resistance of earth pit should be not more than permissible limit on testing after completion if the desired earth resistance is not obtained the earthing will be redone at no extra cost. (iii) Rate quoted by the tenderer is deemed to included salt & Charcoal upto & above 450 mm top of GI Plate. iv) Megger required for testing will be be provided at site by the contractor. v) Contractor shall submit earth resistance testing report before submission of RAR. |
| 146 | Item No 116 : Supply & fix Galvanised iron strip of size 32 mm x 6 mm for earth contunity conductorcomplete all as specified and directed. |
| 147 | Taking Down |
| 148 | Item No 117 : Taking down or up UG 11 kV HT Cable including cable cover laid in trenches/ cable duct or connection to HT panel /GOD and removing from site and transporting to store for safe custody for reuse or for issue under Sch of Credit all as specified and directed by EIC at site |
| 149 | Item No 118 : Relaying the HT 11kV UG cable obtain from taking down of 11 kV capacity complete all as specified and directed at site. |
| 150 | Item No 119 : Taking down or up 33 kV 300 sqmm UG HT Cable including cable cover laid in trenches/ cable duct or connection to HT panel /GOD and removing from site and transporting to store for safe custody for reuse or for issue under Sch of Credit all as specified and directed. |
| 151 | Item No 120 : Relaying the 33 kV HT cable obtain from taking down item any capacity any size complete all as specified and directed at site. |
| 152 | Item No 121 : Dismantling of ACSR conductor from Substation GI structures / HT OH lines any size all as directed at site. |
| 153 | Item No 122 : Dismantling of Copper hollow pipes/ copper strips from substation GI structure of any size all as directed at site. |
| 154 | Item No 123 : Dismantling cross-arms of MS,channel or angle sections & earth wire etc complete and setting aside for re-use with in 50 m distance. |
| 155 | Item No 124 : Dismantling/ Taking down existing 11 mtr long PCC pole of any description complete all as specified and as directed. |
| 156 | Item No 125 : Dismantling/ Taking down existing 12 mtr long tubular pole of any description complete all as specified and as directed. |
| 157 | Item No 126 : Taking down/dismantling pin/post 33/11 kV insulators of any size |
| 158 | Item No 127 : Taking down/dismantling 33/11 kV Lightning arrestors of any size |
| 159 | Item No 128 : Dismantling /taking down old unserviceable 33/11 KV Air break gang operated switches vertical/horigontal mounted including insulators and operating mechanism for insulators and operating mechanism for repair/replacement of broken/worn out components and insulators etc complete all as specified and directed at site. |
| 160 | Item No 129 : Dismantling /taking down old unserviceable 33/11 KV Horn Gap fuse including insulators complete all as specified and directed at site. |
| 161 | SCHEDULE \"A\"(Schedule of credit )Schedule of Credit Rs 354486.00 (Minus) inserted by the MES. (Note : Credit amount shall be deducted manually to arrive net amount) |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2025 · All Rights Reserved. Terms of Usage | Privacy Policy