| 1 | Design, manufacturing, testing at manufacturer\"s works packing, transportation, delivery, unloading, storage, erection, testing and commissioningof the 415 Volts Load Distribution Panel at site as per the drawing, detailed specification and as directed by Engineer-in-charge. Refer Drg No. GSO/ESG/ESD/ATS/SHREDDING MACHINE /LDP/SLD -01 |
| 2 | Load Distribution Panel consisting of following:a) 2 Sets of Incomer Feeders with 400 Amps, 4 Pole, MCCB with CBCT, Shunt Trip Coil, operating handle, interlocking facility and all control, measuring units and indication lamps etc., with Mechanical Castell Lock-Key interlockb) 6 Sets of Outgoing Feeders with 125 Amps, 4 Pole, MCCB with CBCT, Shunt Trip Coil, operating handle, interlocking facility and all control, measuring units and indication lamps etc.c) 8 Sets of Outgoing Feeders with 63 Amps,4 Pole, MCCB with Shunt Trip Coil, operating handle etc. |
| 3 | Supply, Loading, Transportation, Unloading at site, Laying, Testing and Commissioning of 1.1 KV grade of following size of the cable through direct in ground including excavation, sand cushioning, protective covering with chamber burnt/cement bricks on sides & top, refilling the trench and providing RCC route indicator etc., as required.(Refer Sec VI, Clause No.3) |
| 4 | 4C x16 sqmm 1.1kV grade Aluminium conductor XLPE / HRPVC insulation flat wire armour FRLSH PVC outersheath |
| 5 | 4C x 70 sqmm 1.1kV grade Aluminium conductor XLPE insulation flat wire armour FRLSH PVC outersheath |
| 6 | 3.5C x 400 sqmm 1.1kV grade Aluminium conductor XLPE insulation flat wire armour FRLSH PVC outersheath |
| 7 | Supply, Loading, Transportation, Unloading at site, Installation, Testing and Commissioning of 1100 Volts Grade following sizes of cables in built-in trenches, on walls, poles and through embedded pipes including supply of GI spacer, clamps etc and as per the detailed specification.(Refer Sec VI, Clause No.3) |
| 8 | 4C x16 sqmm 1.1kV grade Aluminium conductor XLPE / HRPVC insulation flat wire armour FRLSH PVC outersheath |
| 9 | 4C x 70 sqmm 1.1kV grade Aluminium conductor XLPE insulation flat wire armour FRLSH PVC outersheath |
| 10 | 3.5C x 400 sqmm 1.1kV grade Aluminium conductor XLPE insulation flat wire armour FRLSH PVC outersheath |
| 11 | End Termination of the following sizes of Aluminium Conductor PVC Insulated and sheathed armoured UG Cable using Single Compression, Heavy Duty, Gland connecting the cable to the equipment such as Switches/Panel Boards etc. using Comet or equivalent make Aluminium crimping lugs as directed by Engineer-in-Charge. The rate shall include the cost of supply of Cable Gland and Lugs. The Contractor shall arrange for making holes wherever necessary for fixing cable gland. (Refer Sec VI, Clause No.10.1). |
| 12 | 4 Core x 16 Sq.mm |
| 13 | 3.5/4 Core x 50/70 Sq.mm |
| 14 | 3.5 Core x 400 Sq.mm |
| 15 | Supply, installation, testing and commissioning of the following Raychem make Heat Shrinkable Cable Straight Through Jointing Kits (Crimping type) for 3.5 Core Aluminium Conductor, 1.1 kV (E), PVC/XLPE insulated cables of following sizes as specified. Excavation will be measured separately (Refer Sec VI, Clause No.10.6). |
| 16 | Straight Through Joint (Crimping type) for 3.5 Core x 400 Sq. mm |
| 17 | Supply, installation and testing of GI Pipe Earth Electrode as per IS: 3043 including RCC Chamber and RCC cover slab as per Drawing Nos. IGC/ESD/5060/1007/1 & IGC/ESD/5060/1008/1 are enclosed. (50 Kg. Each Bentonite & Charcoal shall be provided for each earth pit). (Refer Sec VI, Clause No.12.4). |
| 18 | Supply, fabrication and installation of the following size of Hot dip Galvanised GI Flats including excavation and refilling as per the detailed specification. No cutting or drilling permitted after galvanisation.Refer Sec VI, Clause No.12.9). |
| 19 | 25 x 6 mm GI flat |
| 20 | Supply, fabrication and installation of the following size of Hot dip Galvanised GI Flats in Built in trenches on walls, poles, RCC Concrete and through embedded pipes as per the detailed specification. No cutting or drilling permitted after galvanisation. (Refer Sec VI, Clause No.12.9). |
| 21 | 25 x 6 mm GI flat |
| 22 | Supply and Installation of 9 meter Single arm/Double arm GI pole. (Refer Sec VI, ClauseNo.13.1 & 13.2). |
| 23 | Supply & Installation of 9 meters high Hotdipped G.I street light pole including painting with PU paint, foundation EP, heavy duty GI cable entry pipe in 1:3:6 PCC foundation, excavation and refilling etc., as per the drawing no: IGC/ESD/4013/5005/1-R1 for single arm GI pole and drawing no: IGC/ESD/4013/5005/3-R1 for Double arm GI pole including supply of GFRP box as per the drawing no: IGC/ESD/2021/6001/3, 40 NB heavy duty GI pipe, 40 NB heavy duty long bend, Clamp for JB with 25 X 6 mm Alu. flat ,1mtr 16mm Dia SS rod with SS wire (2 runs) equivalent to 8SWG , 3C X1.5 sqmm copper flexible cable, fixing fasteners etc., as required. |
| 24 | Supply and Installation of 3.75mtr Area lighting poles With PU painting (Pedestal type). (Refer Sec VI, Clause No.13.3 & 13.4). |
| 25 | Post top Lantern pole including supply and embedment of Cast Aluminium Junction Box with FRP cover as per the drawing No: - IGC/ESD/2021/6001/1-R1. 3.75mtr 50NB GI pole with PU painting, cable entry pipe, cable termination arrangements etc. including providing of 1:4:8 mudmat and 1:3:6 foundation PCC conforming to the detailed specification 1mtr 16mmDia SS rod with SS wire (2 runs) equivalent to 8SWG and as per Drawing No. - IGC/ESD/2021/6001/P2-R1. |
| 26 | Supply, installation, testing and commissioning of following street light luminaries on RCC / Metallic poles of height from 7 M to 12 M as perthe detailed specification scope includes installation of external surge protection device wherever required. (Refer Sec VI, Clause No.16.1). |
| 27 | Adornis INT 100W 4000k CCT NON DIM GREY (PC) PRIME 50 POLE DIA LED, Item code STA0T10040NDGYP00050C13or equivalent |
| 28 | Supply, Installation, Testing and Commissioning of following Area lighting luminaries on Metallic poles of height from 2.5 M to 4 M as per per the detailed specification. (Refer Sec VI, Clause No.16.1). |
| 29 | 240V,LED Street Light Luminarie of Catalogue: LPTO-40-CDL or equivalent lumens LED Area Light Luminarie |
| 30 | Supply, Installation, Testing and Commissioning of 195 Watts LED flood light luminaries in Shredder Shed at the height of 7-12 M high as per the detailed specification.. (Refer Sec VI, Clause No.16.1 for installation). |
| 31 | 195 Watts, 24100 Lumen, TANGO Flood LED Luminaires with PDC aluminium housing and PC cover opticsof Phillips make or equivalent as per the detailed specification. |
| 32 | Supply, installation, testing and commissioning of the following SDFU with factory made enclosure with 3Nos Fuse links on MS frame work as per the scope of work. (MS item will be measured separately). (Refer Sec VI, Clause No.14.1). |
| 33 | SDFU TPN 125A, DIN FUSES with 3Nos 125A HRC fuse links, Open Execution FN Sheet steel enclosure FN Cat No:SK90486 |
| 34 | Supply and Installation of Cast aluminium Junction box with FRP cover. (Refer Sec VI, Clause No.13.6) |
| 35 | Supply and Installation of Cast aluminium Junction box for PTL as per the drawing no: IGC/ESD/2021/6001/1-R1, for street light pole as per the drawing no: IGC/ESD/2021/6001/3, and as per the detailed specification. |
| 36 | Supply and Embedment of following sizes of flush mounting POWDER COATED TPN/SPN DB Enclosures with Double Door consisting of Phase, Neutral and Earth Bus and interconnecting wires etc. at suitable depth in brick work as per the detailed specification and as directed by the Engineer-in-charge .(Refer Sec VI, Clause No.15.2) |
| 37 | SPN, 8 Way Distribution Board with all accessories, cat No:507611 |
| 38 | Supply and Embedment of following sizes Cable end termination box at suitable depth in brick work as per the detailed specification and as directed by the Engineer-in-charge.(Refer Sec VI, Clause No.15.2.2). |
| 39 | SPN, 8 way Cable end box, cat No:507913 or equivalent suitable for SPN, 8 way Distribution Board cat No:507611 |
| 40 | Supply, open installation testing and commissioning of the following DB with Double Door consisting of Phase, Neutral and Earth Bus and interconnecting wires. (MS item will be measured separately). (Refer Sec VI, Clause No.15.2) |
| 41 | DB SPN 8 Way (8) WITH METAL DOOR IP 43 - IK 09 cat No:507611 or equivalent |
| 42 | Supply, open installation testing and commissioning of the following sizes of cable end termination box on MS frame work (MS frame will be measured separately) as per the scope of work. (Refer Sec VI, Clause No.15.1.15). |
| 43 | Cable End Box for IP 43 SPN 8 Way DB cat No:507913 suitable for SPN 8 Way DB cat No:507611 |
| 44 | Supply fixing testing and commissioning of the following RCBOs on Distribution Boards as per the detailed specification. (Refer Sec VI, Clause No.14.2). |
| 45 | RCBO DP 32A sensitivity 30mA TYPE AC, 2Module |
| 46 | Supply Installation testing and commissioning of the following MCB on Distribution Boards as per the detailed specification. (Refer Sec VI, Clause No.14.2). |
| 47 | 6-32 Amps SP MCB (Type-C) |
| 48 | Supply and Installation of MS Brackets, Supports, Frame work, Clamps, Base Channels, etc. fabricated out of angle / Channel / Rods etc. The rate quoted shall include the cost of fabrication / welding, cleaning and painting/ galvanising as follows including supply of required, fasteners, nuts, washers, etc.(Refer Sec VI, Clause No.11). |
| 49 | MS fabrication 1 coat primer & 2 coats synthetic enamel paint |
| 50 | Clearing light jungle area, bulb weeds, grass including removal all unwanted plants, branches, twigs, wild growth etc.complete, and disposing the same 100 meters away manually or burning them without disturbing other areas etc., complete all as directed by the Engineer-in-Charge. Contractor must inform the Engineer-in-charge and prior permission shall be obtained from him for burning the wild growth. (Refer Sec VI (MNC), Clause No.7.3). |
| 51 | Excavation in hard soil including refilling with excavated earth and disposing surplus earth at places as directed with in a lead of 10 Mtrs. and initial lift upto 1.5 Mtrs. including neat banking as per detailed specification. (Refer Sec VI, Clause No.2) |
| 52 | Supply and installation of following sizes of Heavy Duty, PVC circular rigid Conduits for Electrical & Communication System with all the required accessories like round JBs, Solid Long Bends, Couplings, GI wire etc, on roof slab, column, beams etc as per the detailed specification.(Refer Sec VI, Clause No.27). |
| 53 | 25mm Dia, 2mm wall thick PVC heavy duty conduit with 63mm deep Junction box |