| 1 | Supply, laying, jointing & testing in replacement XLPE insulated, PVC bedded galvanised steel strip or wire armoured electric power cable heavy duty with stranded aluminium conductor 1100 volts grade cross sectional area 10 Sqmm 4 core laind in trenches or passing through pipe or fixed on poles complete all as specified and directed by Engr-in-Charge. |
| 2 | Description all as per serial item No 1.00 here-in-before but of size 16 Sqmm 4 core. |
| 3 | Description all as per serial item No 1.00 here-in-before but of size 25 Sqmm 4 core. |
| 4 | Description all as per serial item No 1.00 here-in-before but of size 35 Sqmm 3.5 core. |
| 5 | Description all as per serial item No 1.00 here-in-before but of size 50 Sqmm 3.5 core. |
| 6 | Description all as per serial item No 1.00 here-in-before but of size 70 Sqmm 3.5 core. |
| 7 | Taking down the unserviceable LT cable of any size from tranches/ walls /floor etc complete all as specified and as directed by engineer in charge. |
| 8 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m deep for laying of cables, pipes foundations of poles/stays/pipes etc .not exc 10 Sqm area on plan and getting out in soft/loose soil complete all as specified and directed by Engr-in-charge |
| 9 | Returning, filling in excavated soil in trenches including spreading, leveling, watering and well rammingin layers n. exc. 25 cm thick complete all as specified and directed by Engr-in-charge. |
| 10 | Removing of excavated soil to a distance n. exc. 50 mtr and deposited where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed by Engr-in-charge. |
| 11 | S&F double walled corrugated (DWC) pipe of size90 mm including snap fit coupler conforming to IS14930 (Pt-II)/IS16205 Pt-II for protection of HT cable in under ground complete all as spd and directed. |
| 12 | S&F double walled corrugated (DWC) pipe of size 77 mm including snap fit coupler conforming to IS14930 (Pt-II)/IS16205 Pt-II for protection of HT cable in under ground complete all as spd and directed. |
| 13 | M&L for cement concreate 1:2:4 type B-2 (using 40 mm graded stone aggregate) as in coping etc including necessary form work and finishing the surface with cement mortar 1:4, 5mm thick finished to the portion of PCC muffs above ground level complete all as specified and directed by Engr-in-Charge. |
| 14 | M&L for PCC 1:4:8 type D-2 (using 40 mm grade stone aggregrate in foundation, mass concrate) as in foundation of poles & stay etc complete all as specified and directed by Engr-in-Charge. |
| 15 | Supply and Laying in replacement Galvanised iron steel tubes, ISI marked light grade of size 40 mm bore for cable protection along the poles under road under drains,laid in trenches/fixed on walls/poles with suitable clamps bolts nuts etcincluding taking down of old unserviceble pipe complete all as specified and directed by Engineer-in-Charge. |
| 16 | S&F in replacement of automatic street light control switch of 8 KW three phase using Infrared sensor based Nature Switch for automatic switching of street light. Nature switch operation should be based on Natural Light Lux*level. Reqd illuminance level also have part night operation facility for min 4 hrs to max 12 hrs. The sensor along with suitabe rating power contractor (s), one Incoming and three Outgoing MCBs rating of 20-32 Amps & main load circuit wiring (copper) of min 10 sqmm should be enclosed in a pole/wall mountable rust proof, electric shock proof, termite proof and FR grade thermoplastic polycarbonate enclosure conforming to IP66 protection class-2 (Hansel make). The circuit should be also have provision for manual operation (i.e. sensor by pass option) complete all as specified and directed. Model No SWADEEP 66- 8 KW3P or L&T or Havells |
| 17 | Taking down carefully Unserviceable Security light 60/90/120/150 watt /Flood Light/ High Mast light fitting from pole/Structure complete all as specified and directedby Engr-in-charge |
| 18 | Refixing the U/S light aftervisual inspection at complaint cell/power house and fixing the unservicable parts and connecting accesories suchcables conductors 2.5 sqmm/4sqmm,drivers, service brackets along with nut bolts etc without any extracost to the contractor by the department all as specefied and as directed by Engr-in-charge. |
| 19 | Supply only Driver for LED energy saving & enviornment area light fitting > 75 watts security light with active power factor correction (APFC) electronic driver.LED driver 75 Watt with operating voltage between 100-270 V of existing specifications & make complete all as specefied and as directed by Engr-in-charge. |
| 20 | Supply only Driver for LED energy saving & enviornment area light fitting > 45 watts security light with active power factor correction (APFC) electronic driver.LED driver 45 Watt with operating voltage between 100-270 V of existing specifications & make complete all as specefied and as directed by Engr-in-charge. |
| 21 | Supply only Surge protection 5 KV devices compatible with industrial & outdoor LED fixtures upto rated power of 45 W & up to 150 W with operating voltage between 100-270 V of existing specifications & make complete all as specefied and as directed by Engr-in-charge. |
| 22 | S&F in replacement 120 Watt LED street light with pressure die cast aluminium housing & toughened glass with IP-66 degree protection, individual LED\"s must have peanut lenses for better throw across & along the road with luminarie efficacy of greater than 100 lumen/Watt (Minimum lumen output of luminarie should be 9000 Lumens) color rendering (CRI) of > 75 and co-related color temperature (CCT) of 5700K (+ 500K), The luminarie should have 5 KV surge protection,PF > 0.95, and total harmonic distortion of THD < 10%, voltage range of 140-280V should be provided.Luminarie should have top maintainable driver compartment for easy access to driver during maintenance.The driver used must be a constant current driver with efficiency of > 85%.The manufactures LOGO must be embossed/Engraved in the housing of the luminarie.Manufactures to provide LM80 from source manufacturer and should have adequate testing facilities approved by ministry of science (Govt of India) to provide LM 79 report complete all as specefied and directed by Engr-in-charge.Make : Wipro-(LRO2-132-XXX-57-G3)/Bajaj/Philips. |
| 23 | S&F in replacement 90 Watt LED street light with pressure die cast aluminium housing & toughened glass with IP-66 degree protection, individual LED\"s must have peanut lenses for better throw across & along the road with luminarie efficacy of greater than 100 lumen/Watt (Minimum lumen output of luminarie should be 9000 Lumens) color rendering (CRI) of > 75 and co-related color temperature (CCT) of 5700K (+ 500K), The luminarie should have 5 KV surge protection,PF > 0.95, and total harmonic distortion of THD < 10%, voltage range of 140-280V should be provided.Luminarie should have top maintainable driver compartment for easy access to driver during maintenance.The driver used must be a constant current driver with efficiency of > 85%.The manufactures LOGO must be embossed/Engraved in the housing of the luminarie.Manufactures to provide LM80 from source manufacturer and should have adequate testing facilities approved by ministry of science (Govt of India) to provide LM 79 report complete all as specefied and directed by Engr-in-charge.Make : Wipro-(LR02-102-XXX-57-G2)/Bajaj/Philips. |
| 24 | S&F in replacement 60 Watt LED street light with pressure die cast aluminium housing & toughened glass with IP-66 degree protection, individual LED\"s must have peanut lenses for better throw across & along the road with luminarie efficacy of greater than 100 lumen/Watt (Minimum lumen output of luminarie should be 6000 Lumens) color rendering (CRI) of > 75 and co-related color temperature (CCT) of 5700K (+ 500K), The luminarie should have 5 KV surge protection,PF > 0.95, and total harmonic distortion of THD < 10%, voltage range of 140-280V should be provided.Luminarie should have top maintainable driver compartment for easy access to driver during maintenance.The driver used must be a constant current driver with efficiency of > 85%.The manufactures LOGO must be embossed/Engraved in the housing of the luminarie.Manufactures to provide LM80 from source manufacturer and should have adequate testing facilities approved by ministry of science (Govt of India) to provide LM 79 report complete all as specefied and directed by Engr-in-charge.Make :Wipro-(LRO2-671-XXX-57-G3)/Bajaj/Philips. |
| 25 | Supply, Laying, jointing in replacement & testing 1100 Volts grade heavy duty cablewith copper conductor cable, PVC sheathed2.5Sqmmnominal cross section laid in trenches/fixed to poles/walls or passing under the roads in existing pipes etc including takind down old UNSV cable complete all as specefied and directed by Engr-in-charge. |
| 26 | Supply, Laying, jointing in replacement & testing 1100 Volts grade heavy duty cablewith copper conductor cable, PVC sheathed4 Sqmmnominal cross section laid in trenches/fixed to poles/walls or passing under the roads in existing pipes etc including takind down old UNSV cable complete all as specefied and directed by Engr-in-charge. |
| 27 | S&F in replacement modular boxof size 333 x 233 x 120 mm made of FRP inpact resistance plastic & heat resistant materials including MCB SP 6 A, Connector terminal block 4 pole 16 A capacity and fixing to the street light or post top light pole with suitable sizes of clamps, nuts and bolts complete all as specefied and directed by Engr-in-charge. |
| 28 | Supply, Laying, jointing in replacement & testing 1100 Volts grade heavy duty cable PVC tape PVC sheathed 4 Sqmm aluminium solid conductor 2 core nominal cross section laid in trenches/fixed to walls/ passing under the roads in existing pipes etc including takind down old UNSV cable complete all as specefied and directed by Engr-in-charge. |
| 29 | Supply, Laying, jointing in replacement & testing 1100 Volts grade heavy duty cable PVC tape PVC sheathed 6 Sqmm aluminium solid conductor 2 core nominal cross section laid in trenches/fixed to walls/ passing under the roads in existing pipes etc including takind down old UNSV cable complete all as specefied and directed by Engr-in-charge. |
| 30 | Supply, Laying, jointing in replacement & testing 1100 Volts grade heavy duty cable PVC tape PVC sheathed 10Sqmm aluminium solid conductor 2 core nominal cross section laid in trenches/fixed to walls/ passing under the roads in existing pipes etc including takind down old UNSV cable complete all as specefied and directed by Engr-in-charge. |
| 31 | Cleaning the existing exposed surfaces of steel tubular pole of9.0 mtr long including cross arms, brackets, clamps etc and painting with two coats of synthetic enamel paint (Aluminium shade) marking five black & white bands at lower portion of pole, each 300 mm wide alternately and marking pole No. with yellow paint on black base at suitable height complete all as specified and directed by Engr-in-Charge. |
| 32 | Supply, installation, testing and commissioning in repair of outdoor type,weather proof, LT Panel made out of 3.15 mm thick CRCA steel sheet mounted on 60 cm long legs made out of 50 x 50 x 6 mm equal angle,embedded in PCC 1:2:4 type B-1 bocks of size 15x15x20 cm , front and back openable,double door openable up to minimum 150 deg. & removable type having magnetic catche system, lockable / openable by keys from both sides having chromium plated locks, louvers and air vent gaskets for natural air flowsuitable for 3 phase 4 wire 415 volts 50 Hz ,factory febricatedwith suitable foamed-in PU gasket to make it dust/vermin proof , IP 54 protection, Powder coated andprewired as per standard engineering practice, the panel manufacturer should have got any one of the panel tested at CPRI earliest for short circuit current of 50 KA for one second and similar design and technology shall be adopted for fabrication of panel copy of CPRI test report shall be produce to GE along with a certificate from manufacturer of the panel that the similar design and standard have followed in these panels.complete ,suitable cable glands for cable entry. The panel shall be suitable to accomodate the following equiptments :- |
| 33 | (a)Aluminium bus bar of capacity duly covered with colour coded shrinkable sleeves not less than 800 amps for Phases neutral - 01 set (b)Phase indicating lamp neon/LED type (Red ,Yellow &Blue) with lamp holders - 03 Nos(c)Panel instrumental wiring with FRLS suitable size but not less than 2.5 sqmm copper wire single core - 01 Job(d)Digital multifunction meter of size 96x96 mm to measure current, voltage, frequency and power factor with built in selector switch and programable CT of appropriate ratio. Incoming :-(a) MCCB 4 pole , Ics=100%Icu- 50 KA, 415 Volts, 400 Amps ,with thermal adjustable and adjustable magnetic setting with extended terminals -01 No (I/C)(b) MCCB 4 pole , Ics=100%Icu- 25/26 KA, 415 Volts, 200 Amps , with thermal adjustable and adjustable magnetic setting with extended terminals -1 No.(c) MCCB 4 pole , Ics=100%Icu- 25/26 KA, 415 Volts, 125 Amps , with thermal adjustable and adjustable magnetic setting with extended terminals -1 No. (d) MCCB 4 pole , Ics=100%Icu- 25/26 KA, 415 Volts, 100 Amps , with thermal adjustable and adjustable magnetic setting with extended terminals -1 No. (e) Additional/Spare compartment with the same bus for accomudating 4 pole MCCB of any size -01 Nos complete all as specified and directed by Engr-in-charge( f)PCC 1:3:6 type C-2 for grouting 4 legs of LT Panelcomplete all as specified. |
| 34 | Labour only for re-stretching properly sagged/loose ACSR conductor of any size fixed on LT poles by means of machine method to the permissible limit at different location including tightening of cross arms or D clamps and binding with new binding wire, tightening of jumpers complete all as specified and directed by Engr-in-Charge.Note: - (i) Each line of conductor shall be measured.(ii) Rate including unwinding of old winding wire and rewind with new binding wire after restretching) |
| 35 | S&F in replacement Shackle type porcelain vitreous white, brown or green insulator of size 75 mm height & 90 mm dia including galvanized mild steel straps of size 31 x 3 mm and bolt of size 12 mm dia, washers and nuts of 75 mm height & 90 mm dia for working pressure 1100 volts grade complete all as specefied and directed by Engr-in-charge. |
| 36 | S&F in replacement Pin type, porcelain, vitreous, white, brown or green insulator 1100 V grade including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 100mm height, 65mm diacomplete all as specified and directed by Engineer-in-Charge. |
| 37 | M&L for defect rectification of LT 1.1 KV cable laid in trenches by locating fault with help of electronic fault locating machine comprising of surge generator pules, ECHO fault locator with high frequency distance calculator for cable of any size XLPE 11 KV / 1.1 KV complete all as specified and directed |
| 38 | S&F in replacement Stay assembly complete with acessories as shown in electrical plate no 1 (loop type insulator, stay clamps, stay wire, excavation and concrete measured separately) with 16 mm dia stay rod complete all as specefied and directed by Engr-in-charge including taking down old U/S same items. |
| 39 | S&F in replacementGalvanized steel wire 4 mm dia for continious earth wire on poles and cradles at road crossing with fixing arrangement complete all as specefied and directed by Engr-in-charge. |
| 40 | S&F in replacement on LT overhead line separator 3 way complete all as specefied and directed by Engr-in-charge. |
| 41 | S&F in replacement on LT overhead line separator 4 way complete all as specefied and directed by Engr-in-charge. |
| 42 | M&L danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with MS clamps, bolts and nuts of approved size for LT 20x15cm size complete all as specified and directed by Engr-in-Charge. |
| 43 | M&L for repairing the existing LT panel/ Feeder Pilller Box/ APFC Panel any type or sizeby taking proper shutdown from power house and disconnecting and re-connecting cables connection both in coming and outgoing using appropriate size of thimbles, making proper welding, drilling for smooth functioning of panel / feeder door, replacement of unserviceable aluminium bus barof suitable capacity/size as per existing includingbakelite insulators, terminals, base plate, necessary nuts, bolts & washers, locking arrangement complete all as specified and directed by Engr-in-Charge. Note: - Necessary accessories like MCCB/MCB, CT coil, ammeter, voltmeter, indication lamp, selector switch, Proper Loacking Arrangement, Base Frame etc shall be measured and paid separately as supply & fixing under respective item. |
| 44 | S&F in replacementMCCB four pole 63 Amps,50 Hzwith breaking capacity 16KA, Ics = 100% Icu , 415 Volts, Adjustable thermal & Fixed magnetic setting including making all incoming/ outgoing connections complete all as specified and directed by Engineer in Charge. |
| 45 | Description all as per serial item No 43.00 here-in-before but 100 Amps, 4P, with breaking capacity 25 KA. |
| 46 | Description all as per serial item No 43.00 here-in-before but 125 Amps with breaking capacity 25 KA. |
| 47 | Description all as per serial item No 43.00 here-in-before but 160 Amps with breaking capacity 25 KA. |
| 48 | S&F in replacementMCCB four pole 200 Amps,50 Hzwith breaking capacity 36 KA, Ics = 100% Icu , 415 Volts, Adjustable thermal & Adjustable magnetic setting including making all incoming/ outgoing connections complete all as specified and directed by Engineer in Charge. |
| 49 | Description all as per serial item No 47.00 here-in-before but 250 Amps with breaking capacity 36 KA. |
| 50 | Description all as per serial item No 47.00 here-in-before but 315 Ampswith breaking capacity 36 KA. |
| 51 | Description all as per serial item No 47.00 here-in-before but 400 Ampswith breaking capacity 36 KA. |
| 52 | Description all as per serial item No 47.00 here-in-before but 630 Ampswith breaking capacity 36 KA. |
| 53 | S&F Onload change over switch FP 200 Amps, 415 Volt, 4 pole complete all as specefied and directed by Engr-in-charge. |
| 54 | S&F Onload change over switch FP 125 Amps, 415 Volt, 4 pole complete all as specefied and directed by Engr-in-charge. |
| 55 | S&F Onload change over switch FP 63 Amps, 415 Volt, 4 pole complete all as specefied and directed by Engr-in-charge. |
| 56 | M&L for earthing complete with galvanized steel earth plate electrode 600 mm x 600mm x 6.0mm thick buried directly in ground ( earth pit not less than 2.25 mtr below normal ground level ) with top edge plate not less than 1.5 metre below normal ground level connected to galvanized earth strip of size 32 x 6mmas earthing lead by means of bolts, nuts, chuck nuts and washers of galvanized iron earth lead with 15 cm thick alternate layers of charcoal dust & common slat including PCC pit in PCC 1:2:4 type B-1, RCC covermade out of cement concrete 1:2:4 type B-1 (using 20 mm graded crushed stone aggregate) reinforced with TMT steel bars 8 mm dia @150 mm c/c both ways with suitable handle andangle iron 40 x 40 x 5 mm frame, GI medium grade watering pipe 20 mm bore and funnel with wire mesh light grade protection pipe 40mm bore up to main board complete as shown on electrical plate No 3 of MES Sch 2009 (Part-I) and testing on completion complete all as specified and directed by the Engineer-in-Charge. Note: - On testing after completion of earthing, if desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk & cost to the entire satisfaction of Engineer-in-charge. |
| 57 | M&L for earthing complete with galvanized steel earth plate electrode 600 mm x 600 mm x 6.0 mm thick buried directly in ground (earth pit not less than 2.25 mtr below normal ground level) with top edge plate not less than 1.5 metre below normal ground level connected to galvanized earth strip of size 25 x 4 mmas earthing lead by means of bolts, nuts, chuck nuts and washers of galvanized iron earth lead with 15 cm thick alternate layers of charcoal dust & common salt including PCC pit in PCC 1:2:4 type B-1, RCC covermade out of cement concrete 1:2:4 type B-1 (using 20 mm graded crushed stone aggregate) reinforced with TMT steel bars 8 mm dia @150 mm c/c both ways with suitable handle andangle iron 40x40x5mm frame, GI medium grade watering pipe 20 mm bore and funnel with wire mesh light grade protection pipe 20 mm bore up to main board complete as shown on electrical plate No 3 of MES Sch 2009 (Part-I) and testing on completion complete all as specified and directed by Engr-in-Charge. Note: - On testing after completion of earthing, if desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk & cost to the entire satisfaction of Engineer-in-charge. |
| 58 | M&L for switchyard gravelling of 15.0 cm (loose thickness) by broken stone of 40 mm size in and around two pole/ four pole structure/ substation complete all as specified and directed by Engr-in-Charge. |
| 59 | Taking out/dismantling any type of LT Panel by disconnecting the electric connection carefully after taking proper shutdown and removing from the site and stacking complete all as specefied and directed by Engr-in-charge. |
| 60 | Taking down/Dismantling of old unserviceable/corroded ACSR Conductor of any size from existing over head lines completed and supply, lay and fix aerial bunched cable 1100V grade stranded and compact aluminium phase conductor of size 3x95 sqmm + 1x70 sqmm (bare messenger) with Aluminium alloy and Junction box The phase conductor shall be insulated with XLPE (Sioplas) compound Aluminium as per IS-14225-1995including all fittings such as anchor clamp, suspension clamp, line connector, service clamp, Including End joints insulator piercing connectors, for taps from bare line etc. complete all as specified and as directed by Engr-in-Charge. |
| 61 | Taking down/Dismantling of old unserviceable/corroded ACSR Conductor of any size from existing over head lines completed and supply, lay and fix aerial bunched cable 1100V grade stranded and compact aluminium phase conductor of size 3x 150sqmm + 1x150 sqmm (bare messenger) with Aluminium alloy and Junction box The phase conductor shall be insulated with XLPE (Sioplas) compound Aluminium as per IS-14225-1995including all fittings such as anchor clamp, suspension clamp, line connector, service clamp, Including End joints insulator piercing connectors, for taps from bare line etc. complete all as specified and as directed by Engr-in-Charge. |
| 62 | M&L for Boring for laying of cable/pipe and making good the disturbed/excavated surface as per existing road including refilling the excavated material, compacting, WBM and black top carpeting with bitumen & aggregate following the stone/sand on top complete all as specifiedand directed by Engr-in-Charge. |
| 63 | Lopping/prooning of tree branches upto the extend to obtain clearance all around the HT/LT over headlines conductor upto 3 mtr from farthest conductor on pole including removing of cut branches & cleaning of site compleall as specified and directed by Engr in charge.(Note:- (a) The trees branches etc will be left as it is & will not be carried away by the contractor/DEL as the wood belongs to CEO/DEO & they will be responsible to lift the wood. (b) Pruning of all tree branches in one tree shall be measured as one Job. (c ) Contractor will employ sufficient labour to complete the Job with in time as directed. (d) Contractor will be responsible for any type mis-happening/accident while pruning the trees. (e) Contractor supervisor will take proper shut down from MES installation before starting the work & clear it before resuming power supply. However, full assistance will be provided by MES staff. (f) The contractor will provide proper tools & safety to his staff for purning of trees. |
| 64 | Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified) LT feeder pillar box (KIOSK) out door type, floor mounted,compertmantalised suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, IP-65 dust and vermin proof, made of 2 mm CRCA MS sheet with digital Volt meter, Ammeter, with CTs ,Led lamps RYB for all incomers & outgoings base frame of 40x40x6mm angle iron , powder coated, having front and rear openeable hinged double door shutters with aprons for cable entryand locking arrangement complete with following :- |
| 65 | Incoming:-(a)MCCB 100amps, 4 pole, 25 KAwith adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 1 Nos.Make: L&T , Legrand, Scheineider, ABB, Havells, C&S.Outgoing:-Bus bar electrolytic grade copper and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 160 Amp, 4 pole, not less than 45 cm long mounted on insulators for incomming supply 01 No.15/16 Amp Switch Socket combine- 06 NosNote- (i) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work.(ii) Panels shall be placed above 0.6 mtr from ground level(iii) Outgoing MCCBs shall be fed with solid busbar connectors and (iv) Cables shall be terminated using gun metal /SS glands.(v) cable glands for incomingand out going suitable cables is including rate quated by vendover(vi) includingsuitable thimbles/lugs, nut bolts ,washersfitted the cables |