| 1 | Dismantling old unserviceable LT panel including disconnecting connected cables complete all as specified and as directed., |
| 2 | Material and labour for dismantling old unserviceable LT panel along with disconnecting connected cables, supplying, installing, testing and commissioning of 415 Volts 3 Phase 4 Wire, 3.15 mm thick factory fabricated and tested all as per existing IEC 60439 Part 1, floor mounted, IP 55 grade, sheet Outdoor double door Partially Type Tested Assembly Type (PTTA) LT cubical panel made out ofCRCA MS sheet duly powder coated with Seimens grey shade RAL 7032, dust and veremin proof with TPN PVC sleeved aluminium bus bar of size 250 Amps incld. angle iron base frame of suitable size. Including Panel mounted/grouted on 150 mm thick PCC (1:4:8) type D2 1 Mtr above ground level and with 500 mm offsets on all 04 sides of the panel complete and including spiral HDPE pipes for all cables under the PCC of panel inclusive of following accessories :- A. INCOMING - (I) MCCB 100 Amps ,415 V 3 pole 36 KA 50 Hz with Ics =100% Icu & thermal magnetic adjustable , Microprocessor release type including spreader terminals - set of 04 and direct rotary handle -01No as per OEM specifications- 01NosB. OUTGOING - (i) MCCB 63 Amps ,415 V 3 pole 25 KA 50 Hz with Ics =100% Icu & thermal magnetic adjustable type including spreader terminals - set of 04 and direct rotary handle -01No as per OEM specifications- 01 Nos(ii) MCB TPN 63 Amp - 01 No. (iii) MCB TPN 32 Amp - 03 No. (iv) Spare cubicles for expansion as per MCCB 4P Amps - 02 Nos.(v) LED indicators - R/Y/B 240 V AC - 03 Sets of 03 Nos. per incoming & outgoing(vi) Multifunction meter with accuracy Class 1.0, Flush mounting 96 x 96 mm, CT/PT site programmable for measurement of V, A, PF, kW, kVA, Load hours all as and including suitable size CTs (set of 3) - 01 No. (for Incoming feeder)(vii) MCB SP \"C\" series 10kA 60-32 Amps as protection for LED lamps (01 No. each for set of 03 Nos. LED lamps, multifunction and single function meters) and multifunction meter - 2 Nos. (viii) Control wiring with suitable size PVC insulated single core copper conductor cable for LED lamps, MFMs, etc. |
| 3 | Material and labour for dismantling old unserviceable LT panel along with disconnecting connected cables, supplying, installing, testing and commissioning of 415 Volts 3 Phase 4 Wire, 3.15 mm thick factory fabricated and tested all as per existing IEC 60439 Part 1, floor mounted, IP 55 grade, sheet Outdoor double door Partially Type Tested Assembly Type (PTTA) LT cubical panel made out ofCRCA MS sheet duly powder coated with Seimens grey shade RAL 7032, dust and veremin proof with TPN PVC sleeved aluminium bus bar of size 250 Amps incld. angle iron base frame of suitable size. Including Panel mounted/grouted on 150 mm thick PCC (1:4:8) type D2 1 Mtr above ground level and with 500 mm offsets on all 04 sides of the panel complete and including spiral HDPE pipes for all cables under the PCC of panel should be inclusive of following fitted in accessories :- A. INCOMING - (I) MCCB 63 Amps ,415 V 3 pole 36 KA 50 Hz with Ics =100% Icu & thermal magnetic adjustable , Microprocessor release type including spreader terminals - set of 04 and direct rotary handle -01No as per OEM specifications- 01NosD. OUTGOING - (i) MCB TPN 32 Amp - 04 No. (ii) Spare cubicles for expansion as per MCCB 4P Amps - 02 Nos.(iii) LED indicators - R/Y/B 240 V AC - 03 Sets of 03 Nos. per incoming & outgoing(iv) Multifunction meter with accuracy Class 1.0, Flush mounting 96 x 96 mm, CT/PT site programmable for measurement of V, A, PF, kW, kVA, Load hours all as and including suitable size CTs (set of 3) - 01 No. (for Incoming feeder) (v) MCB SP \"C\" series 10kA 60-32 Amps as protection for LED lamps (01 No. each for set of 03 Nos. LED lamps, multifunction and single function meters) and multifunction meter - 2 Nos. (vi) Control wiring with suitable size PVC insulated single core copper conductor cable for LED lamps, MFMs, etc. |
| 4 | Material and labour for trenchless boring in any strata of soil across road, pavement,hardstanding etc upto depth as directed but not n,less than 0.60 mtrs below GL/road, pavement,hardstanding etc for laying of LT cable under road, pavement,hadrstanding without damaging existing under ground material complete all as specified and as directed. Note:- GI pipe shall be measured and paid separately under respective items of this schedule. |
| 5 | Material and labour for 50 mm bore galvanized steel tubing light garde (ISI marked) forprotection of cable fixed to pole/walls or laid in floors, road and duct crossingwith all necessary fittings and fittings and fixed with clamps, bolts, nuts and washers etc complete all as specified and as directed |
| 6 | Dismantling concrete poles/ struts, any size complete all as specified and as directed |
| 7 | Dismantling ofcross arms of MS channel or angle etc complete setting aside for reuse within 50 m or remove from site complete all as specified and as directed. |
| 8 | Dismantling insulators any type any size complete all as specified and as directed. |
| 9 | Dismantling stay assembly complete including demolition of concrete and excavationetc complete all as specified and as directed |
| 10 | Dismantling earth wire or copper conductor, service fedder or distribution span complete all as specified and as directed. |
| 11 | Dismantling of ACSR or AAC conductor any size and any type complete all as specified and as directed . |
| 12 | Taking down old unserviceable cables/ service cableof any size complete all as specified and as directed. |
| 13 | Dismantling GI pipe of any size complete all as specified and as directed |
| 14 | Supply,laying/fixing, jointing,testing and commissioning XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 16 sqmm 4 core laid in trenches/ducts/pipes/fixed on wall/pole etc complete all as specified and as directed. |
| 15 | Supply,laying/fixing, jointing,testing and commissioning XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 25 sqmm 4 core laid in trenches/ducts/pipes/fixed on wall/pole etc complete all as specified and as directed. |
| 16 | Supply,laying/fixing, jointing,testing and commissioning XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 70 sqmm 3.5 core laid in trenches/ducts/pipes/fixed on wall/pole etc complete all as specified and as directed. |
| 17 | Excavation in trenches in soft/loose soil n exc 1.5m wide and not Exc1.5m deep and getting out including forming bottom surfaces to required level or slope for taking out old cables,brick/PCC tiles coverscomplete allspecified and all as directed . |
| 18 | Material and labour filling, spreading dry sand in trenches in layers for cushioningto under ground cable for protection of cable, 8cm deep before layingand 15 cm after laying the cable and punned to provide required cover complete all as specified and as directed.Note :- For payment Punned depth shall only be measured. |
| 19 | Material and labour for laying in thenches unreinforced cement concrete cable cover ISI Marked IS-5820( Latest Edition) , class LV, type 1, flat size 250mm x 150mm x 40mm for protection of cable complete all as specified and as directed. |
| 20 | Removal of surplus excavated soil to a distance exc 50 m but not exc in 100 m and deposited where directed at a level n\"exc 50 m above the starting point complete all as specified and as directed. |
| 21 | Returning filling in soil in trenches including spreading, leveling watering and well ramming in 25mm thick layers complete all as specified and as directed. |
| 22 | Material and labour for cement concrete 1:4:8 type D- 2 using 40mm graded crushed stone aggregate in foundation, filling & mass concrete for poles/struts/stays assembly etc complete all as specified and as directed. |
| 23 | Material and labour for cement concrete 1:2:4 type B - 1 using 20mm graded crushed stone aggregate in coping, pedestal to poles including necessary frame work finishing the expossed surface even and smooth complete all as specified and as directed. |
| 24 | Demolition of cement concrete of poles / struts/stay / panel foundation complete as directed by Engineer-in-charge. |
| 25 | Material and labour for complete removal of oldpaint from external surface of 9 mtr longsteel tubular/rail polesand applying of two coats of aluminium /Metal Black paintexternallyincluding numbering of poles in black base of 200 mmdia with white paint letters of size 50 mmandpainting five no.of strips 30 cm wide each upto depth of 1.50 m from baseof pole with black and red colour paint alternately complete all as specified and directed. |
| 26 | Supplyand fixing LED LUMINARIE, pressure die cast aluminum housing, 45 watts capacity, 240V, IP 65 class, with suitable in-built electronic driver complete including taking down of old unsvconventional existing security lights complete all as specified and as directed. Note: - Cost of all minor spares and jobs required for fixing of light fixture on wall and for electrical connections are deemed to be included in the quoted rate. |
| 27 | Supply and erection of intenally and externally hot dipped galvanised made of 3mm thick steel sheet (grade S355JO) 7mtr long \"smart poles\" of octogonal cross section with intergral camouflaged junction box for incorporating controlgears with flust door with necessary locking arrangements, having base plate 220x220x12mm includinggrouted on suitable size shallow foundation with M-15 concrete with 700 mm long 04 Nos 20mm dia, bolts and 3mm anchor plate, mounted with pole top mounting spigot type hot galvanised single arm street light mounting bracket single arm bracket 1000mm in length in all as per instructions and technical specification of manufacturer complete all as specified and as directed |
| 28 | Supply and fixing weather proof Copper conductor 1.5 sqmm 3 core, round cable for connection from looping box to street light fitting in side the existing pole complete all as specified and as directed by Engineer-in-Charge. |
| 29 | Supply and fixing in replacement of old unvs box street light control junction box 280x170x130mm from cable looping box to the connector of the luminarie made out of FRP sheetand arrangement3 phase 4 wire system with R.Y.B.& N studs and control for incoming & outgoing cables with MCB SP 10 Amps 230 volts with neutral link including flat iron “D” clamps (2 Nos) suitable for mounting of box to pole /Angle of requiredsize & shapeincluding bolts nuts & washers.complete all as specified and as directed by Engineer-in-Charge Note: - The quoted rate is deemed to be inclusive of cost of suitable size incoming & outgoing cable glands & lugs. |
| 30 | Supply and fixing for three-Phase load 5 KW for automatic Street Light control Switch using Infrared Sensor based NATURAL SWITCH for automatic switching of Street Lights. Nature Switch operation should be based on Natural Light Lux* level, required illuminance Level for Switching ON is ≤ 30 Lux and for Switching OFF ≥ 10 Lux. The Sensor should have part night operation facility of minimum 4 hrs. to max. 12 hrs. The Sensor along with 3 Nos suitable Contactor each 20 to 25 Amp current rating incoming MCBs & Outgoing MCBs of 20-25 Amps (03 Nos) and circuit should also have provision for manual operation (i.e. Sensor Bye-pass option). circuit should be multistrand FRLSH min size ofminmum 10 sq.mm copper cable. Selection operation should be enclosed in a pole/wall mounted enclosure made of rust proof, electric shock proof termite proof and FR grade special mounting compound (sintex made SMC junction box) confirming to IP 54 including taking down old unserviceable timer any type complete all as specified and as directed by Engineer-in-Charge |
| 31 | Material and labour for earthing complete with galvanized steel earth plate electrode 600mm x 600mm x 6mm thick buried directly in ground (earth pit not less than 2.25 meters deep below normal ground level) with top edge of plate not less than 1.5 meter deep below normal ground level connected to galvanized earth strip of size 32x 6 mm, 7.5m long means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical plate No 3 of SSR part I connecting to earthing test point and testing on completion with and including PCC pit in mix 1:3:6 type c1 with RCC 1:2:4 type B-1, 40 mm thick cover reinforced with 6mm dia MS bars 3 Nos both ways with lifting book made out of 6mm dia bar, watering arrangement with funnel and wire mesh and 20mm bore light grade GI watering pipe, common salt and charcoal filling, necessary excavation and earth work complete including removing the old unserviceable earthing all as specified and as directed by Engineer-in-Charge |
| 32 | Material and labour for LT cable route indicator/made of RCC M-20 grade with 4 x 6mm round bar with 3 rings of size 450x300x100 mmthick duly embossed of letter likt HT/LT cable including painting with tint as directed with proper finishing and smoothing the surface and embedding of cable rote indicators in foundation concrete PCC 1:2:4 type B-1 complete all as specified and as directed by Engneer-in-charge. |