| 1 | Dismantling and taking down old existing ACSR or AAC conuctorof any size/type complete all as specified and as directed. |
| 2 | Dismantling insulator any size/type complete all as specified and as directed. |
| 3 | Dismantling of cross arms of MS channel or angle section etc any size/type complete all as specified and as directed. |
| 4 | Supply, laying and testing in repair/replcement of XLPE insulated cable, screened, PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 1100V grade with multistrandedaluminium conductor of size 240Sqmm 3.5 core as per IS 7092 Pt -I including suitable size aluminium thimble/lugs for connection of LT cable with panelcomplete all as specified and directed. |
| 5 | Supply, laying and testing in repair/replcement of XLPE insulated cable, screened, PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 1100V grade with multistrandedaluminium conductor of size 120Sqmm 3.5 core as per IS 7092 Pt -I including suitable size aluminium thimble/lugs for connection of LT cable with panel complete all as specified and directed. |
| 6 | Supply, laying and testing in repair/replcement of XLPE insulated cable, screened, PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 1100V grade with multistrandedaluminium conductor of size 70Sqmm 3.5 core as per IS 7092 Pt -I including suitable size aluminium thimble/lugs for connection of LT cable with panel complete all as specified and directed. |
| 7 | Supply, laying and testing in repair/replcement of XLPE insulated cable, screened, PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 1100V grade with multistrandedaluminium conductor of size 35 Sqmm 3.5 core as per IS 7092 Pt -I including suitable size aluminium thimble/lugs for connection of LT cable with panel complete all as specified and directed. |
| 8 | Supply, laying and testing in repair/replcement of XLPE insulated cable, screened, PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 1100V grade with multistrandedaluminium conductor of size 25 Sqmm 4 core as per IS 7092 Pt -I including suitable size aluminium thimble/lugs for connection of LT cable with panel complete all as specified and directed. |
| 9 | Supply, laying and testing in repair/replcement of XLPE insulated cable, screened, PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 1100V grade with multistrandedaluminium conductor of size 16 Sqmm 4 core as per IS 7092 Pt -I including suitable size aluminium thimble/lugs for connection of LT cable with panel complete all as specified and directed. |
| 10 | Excavation in trenches n. exc 1.5 mtr wide and n. exc 1.5 mtr depth for pole / cable / foundation etc including getting out in hard/dense soil complete all as specified and directed. |
| 11 | Excavation in trenchesexc 1.5 mtr wide and n. exc 3.0 mtr depth for pole / cable / foundation etc including getting out in hard/dense soil complete all as specified and directed. |
| 12 | Returning, filling in, approved earth including spreading, levelling, watering and well ramming in layers n.exc 25 Cm thick after cable are laid and tested complete all as specified and directed. |
| 13 | Removing excavated material / surplus soil to a distance not exc. 50 mtrs & deposited where directedat a level not exc. 1.5 mtr above the ground level complete all as specified & directed. |
| 14 | M&L for PCC 1:4:8 type D2 (using 40 mm graded stoneaggregates) forfoundation filling and bed concrete all as specified. |
| 15 | M&L for PCC 1:3:6 type C-1 (using 20mm graded stone aggregate) as in mass concrete of pole including necessary form work, weathering slightly rounded or chamfered angles and throating etc complete all as specified. |
| 16 | M&L for PCC 1:2:4 type B-2(using 20mm graded stone aggregates) as in coping etc including form work for polesincluding taking down of u/s existing HDPE pipes all as specified and directed by Engr-in-Charge. |
| 17 | Material and labour for Double wall corrugated HDPE pipe,PN-10 ISI marked of outer dia 63mm, inner dia 50 mm with smooth internal and profiled external surface, non-pressure type, laid in trenches/floors/duct or fixed on walls /pole including all connections, accessories like socket, couplers, bends, etcfor protection of LT cable XLPE grade 1100 volts including taking down of u/s existing HDPE pipes complete all as specified and directed by Engineer-in-Charge. |
| 18 | Material and labour for Double wall corrugated HDPE pipe,PN-10 ISI marked of outer dia 90 mm, inner dia75 mm with smooth internal and profiled external surface, non-pressure type, laid in trenches/floors/duct or fixed on walls /pole including all connections, accessories like socket, couplers, bends, etcfor protection of LT cable XLPE grade 1100 volts including taking down of u/s existing HDPE pipes complete all as specified and directed by Engineer-in-Charge. |
| 19 | M&L for GI tubing (light grade) with all necessary fittings laid in trenches under road crossing fixed on poles, wall under floor etc. of 80 mm dia bore complete all as specified and directed. |
| 20 | M&L for GI tubing (light grade) with all necessary fittings laid in trenches under road crossing fixed on poles, wall under floor etc. of 40 mm dia bore complete all as specified and directed. |
| 21 | Supply and fixing of three phase automatic street light timer switch of capacity 12 KW using integrated sensor based NATURE SWITCH for automatic switching of street light based on LUX level of natural light required illuminance for switching on is less than 30 Lux and for switching off greater than 10 Lux level. The sensor (nature switch) along with suitable power contactors input (supply) MCB and output (load MCB (s), support terminals should be enclosed in pole/wall mountable enclosure made of rust proof, electric shock proof, termite proof and FR graded SMC junction box conforming to IP 66 degree of ingress three phase 12 KW lighting load capacity including mounting bracket, cable glands, openable doors with locking arrangement complete all as specified and as directed. The contactor MCB and circuit wiring should enough to take load of 12 KW equally distributed over single phase and street light timer should be comprising of following:-(a) Input MCB rating 40 Amps 230 volst-03 Nos(b) Contactor rating 40 Amps 230 volts- 03 Nos(c) Out put MCB rating 40 Amps 230 vots-03 Nos(d) three phase circuit wiring minimum 10 Sqmm x 4 core multistranded copper wire.Make: Cat Part No SWADEEP-02EC 8 KW1P, Note :- 01 Year Guarantees+01 year warranty on remaining other item from date of purchase. |
| 22 | Supply , fixin repairs ,commissioningandtestingfactory madeLTfeeder pillar, outdoortypefloor mounted ,suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber duly insulated . The panel shall be dust and vermin proof, IP 65 class protection and made of3.15mm CRCA MS sheet and 50x50x5mm thick angle iron base frame work,powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside,both side openingtype, with aprons for cable entry,with double door shutter and locking arrangement. LTPanel board should be as per IS/IEC 61439-I: 2011 &IS/IEC 61439-2 : 2011, Type Test certificates for Short Circuit Test, Temperature Rise Test, Di-ElectricProperty Test and Degree of Protection IP-65 at minimum 4000 Amps with Breaking capacity not less than 65KA.The panel shall be powder coated finish with RAL 7032 SIEMENS GRAY STRUCTURE after seven tank phosphating treatment, front & back opening type, andfixing 2 Nos.danger notice plate with letter, figures and conventional skull bones in signal red colour and fixed front & back door to LT panel with voltage and danger indicated in Hindi and English, airvent gasket for natural flow of air, Neoprene adhesive type gasket shall be used to make panel vermin proof and comprising of following :-Make:- M/s Mclayers Bhopal/M/s shalabh(india) Ltd/ M/suniversal switchgear Ltd |
| 23 | Item No 22 Contd..)(a)Aluminumbus barfour strips800 Amps ,415 volts, fixed horizontally, duly insulated with heat shrinkable sleeves in colour code - 01 Set.(b)Incoming MCCB,04 Pole, 630 Amps with ultimate breaking capacity Icu-50 KA at 415 volts, fixed type withthermal and magnetic settings conforming to IEC 60947 Part-I/IS-13947 Part-I- 01 No (Ics=Icu=100%)(c)Outgoing MCCB,04 Pole, 250 Amps with ultimate breaking capacity 25 KA at 415 volts with fixed thermal settings conforming to IEC 60947 Part-I/IS-13947 Part-I- 02 No (Ics=Icu=100%)(d) Outgoing MCCB,04 Pole, 160 Amps with ultimate breaking capacity 25 KA at 415 volts with fixed thermal settings conforming to IEC 60947 Part-I/IS-13947 Part-I - 02 Nos (Ics=Icu=100%)(e )Spare way for 125 Amp, MCCB 4 way-01Nos(f)Digitalvoltmeter0-500 Volt with selector switch with MCBs -1 Set(g) Digital Ammeter0-400 Amps with selector switch with MCBs -1 Set(h) Indication lamps R,Y,B LED type with 3 Nos of 2A MCBs -1 set: |
| 24 | Item No 22 Contd..)(j)Internal wiring with suitable size of PVC insulated stranded copper conductor cable duly crimped with copper lugs & ferruled and aluminumstrips for MCCB\"s. Note:-(i) Panel drawing and make of MCCB and connected accessories will be submitted by the contractor for approval of Accepting officer before ordering the panel. (ii) The holes / aprons of cable exit and incoming should be close with suitable size of gland.( iii) The contractor should submit all Certificates before executing the job.(iv) CA No.,Contractor name, item of CA No. to be mentioned on the panel.(v)Suitable Cable glands for incoming cables and outgoing cable to be provided in the panel by the contractors. Cost of provisioning of cable glands deemed to be included in qouted rate. |
| 25 | Supply , fixin repairs ,commissioningandtestingfactory madeLTfeeder pillar, outdoortypefloor mounted ,suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber duly insulated . The panel shall be dust and vermin proof, IP 65 class protection and made of3.15mm CRCA MS sheet and 50x50x5mm thick angle iron base frame work,powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside,both side openingtype, with aprons for cable entry,with double door shutter and locking arrangement. LTPanel board should be as per IS/IEC 61439-I: 2011 &IS/IEC 61439-2 : 2011, Type Test certificates for Short Circuit Test, Temperature Rise Test, Di-ElectricProperty Test and Degree of Protection IP-65 at minimum 4000 Amps with Breaking capacity not less than 65KA. |
| 26 | The panel shall be powder coated finish with RAL 7032 SIEMENS GRAY STRUCTURE after seven tank phosphating treatment, front & back opening type, andfixing 2 Nos.danger notice plate with letter, figures and conventional skull bones in signal red colour and fixed front & back door to LT panel with voltage and danger indicated in Hindi and English, airvent gasket for natural flow of air, Neoprene adhesive type gasket shall be used to make panel vermin proof and comprising of following:-Make:- M/s Mclayers Bhopal/M/s shalabh(india) Ltd/ M/suniversal switchgear Ltd(a)Aluminumbus barfour strips600 Amps ,415 volts, fixed horizontally, duly insulated with heat shrinkable sleeves in colour code - 01 Set.(b) IncomingMCCB,04 Pole, 400 Amps with ultimate breaking capacity Icu-35 KA at 415 volts, fixed type withthermal and magnetic settings conforming to IEC 60947 Part-I/IS-13947 Part-I- 01 No (Ics=Icu=100%)(c) Outgoing MCCB,04 Pole, 200 Amps with ultimate breaking capacity 25 KA at 415 volts with fixed thermal settings conforming to IEC 60947 Part-I/IS-13947 Part-I- 02 No (Ics=Icu=100%) |
| 27 | (d)Outgoing MCCB,04 Pole, 160 Amps with ultimate breaking capacity 25 KA at 415 volts with fixed thermal settings conforming to IEC 60947 Part-I/IS-13947 Part-I - 01 Nos (Ics=Icu=100%)(e)OutgoingMCCB,04 Pole, 125 Amps with ultimate breaking capacity 25 KA at 415 volts with fixed thermal settings conforming to IEC 60947 Part-I/IS-13947 Part-I - 01 Nos (Ics=Icu=100%) (d )Spare way for 200 Amp, MCCB 4 way-01Nos(f)Digitalvoltmeter0-500 Volt-1 Set(f)Digital Ammeter0-400 Amps-1 Set(g) Indication lamps R,Y,B LED type-1 set:h)Internal wiring with suitable size of PVC insulated stranded copper conductor cable duly crimped with copper lugs & ferruled and aluminumstrips for MCCB\"s. Note:-(i) Panel drawing and make of MCCB and connected accessories will be submitted by the contractor for approval of Accepting officer before ordering the panel. (ii) The holes / aprons of cable exit and incoming should be close with suitable size of gland.( iii) The contractor should submit all Certificates before executing the job.(iv) CA No.,Contractor name, item of CA No. to be mentioned on the panel.(v)Suitable Cable glands for incoming cables and outgoing cable to be provided in the panel by the contractors. Cost of provisioning of cable glands deemed to be included in qouted rate. |
| 28 | M & L for earthingcomplete with galvanized steel earth plate electrode600 x 600 x 6 mm thick burried directly in ground (earth pit not less than 2.25m deep below normal ground level)with top edge of the plate not less than 1.5 mtr below normal GL and connected to earth plate . Earth plate surrounded by 15 cm thick packed layers of charcoal dust and common saltupto 1.5 meter depth all around the earth plate and connected to galvanised earth lead32X6mm by means of bolts, nuts, check nuts and washers of galvd iron or steel surronded by charcoal of coke and saltand protected by galvanized iron or steel pipe light grade 40 mm bore and water pipe 20mm bore GI medium grade with funnel and wire mesh, including all necessary excavation and earth work PCC chamber in cement concrete 1:3:6 type C-2 and RCC cover and all as shown in electrical plate No 5 of MES schedule Pt I of2009 and also including making test point for testing of earthingmade out ofgun metal or phosphorous bronge size 75x75x25 mm complete . Note : 1. RCC pit cover shall be pre-cast of RCC (1:2:4) type B-I , 80mm thick reinforced with XPM weighting not less than 4 KG/sqmmin lieu of CI cover.2. Charcoal dust and commonsaltupto 1.5 meter depth shall be filled in layers of 15 centimeters all around the earth plate inside earth pit .On testing after completion of earthing if desired earth resistance is not achieved , the earthing will be redone at no extra cost to obtain the desired earth values less than 2 ohms.3. The cost of GI earth lead and GI pipe of 7.50m lenth for protection of GI wire and excavationwork fpr pit shall deemed to be included in this item. |
| 29 | S&F in replacement kiosk box for luminaires ,weather proof made out of HDPE/FRP housing fire retardant, non fusing, shock & rust proof, single piece moulded andcover with hinged door, pole mounting type comprising of four pole copper connectors of 16 Amps capacity with 6 Amp MCB single pole , of minimum size 300x200x125mm,fixed on pole with MS, clamps 30 x 5mm with necessary nuts, washer and incl applying two coats of synthetic enamel paint over ared oxide primer on steel surface/clamps and embossing/painting of Danger sign of size not less than 10cms x 7.5cms with letter and conventional skull and bones in single red color on front face of kiosk box complete all as directed. The quoted rate also includes cost for material & repalcement of 4 sqmm multistranded twincore aluminium cable ISI marked from overhead conductor to junction box and replacement of 3 core copper cable of 1.5 Sqmm ISI marked from junction box to security light length as per required at site. Make-Syntex/Supreme/Hensal |
| 30 | S & F in replacement of GI brackets for fixing LED street light fitting fabricated out of GI tubing 40 mm dia, medium grade,1.2 mtr long , bend to 120 degree shape by cutting, welding and well finishing including MS clamp of flat iron of size 32 x 4 mm -02 Nos complete for steel poles / PCC pole as per site requirement with nut, bolt & washers for fixing of GI bracket complete all as specified and directed. |
| 31 | S&F in replacement of new generation energy saving and environmental friendly long life LED security/ street light fittings made up of innovative die cast aluminium housing high power LED as lighting source with IP - 65 power consumption 70/72 watt with toughened glass, colour white complete input voltage of 150-240 Volt (nominal rated voltage 240 Volt) complete including replacement of twisted 3 core copper cable of size 1.5 Sqmm dia for connecting phase, neutral and earth from junction box to light through connectors complete as specifiedand as directed. |
| 32 | S&F in replacement of new generation energy saving and environmental friendly long lifeLED security/ street light fittings made up of innovative die cast aluminium housing high power LED as lighting source with IP - 65 power consumption 90 watt with toughened glass, colour white complete input voltage of 150-240 Volt (nominal rated voltage 240 Volt) complete including replacement of twisted 3 core copper cable of size 1.5 Sqmm dia for connecting phase, neutral and earth from junction box to light through connectors complete as specifiedand as directed. |
| 33 | S&F in replacement of new generation energy saving and environmental friendly long lifeLED security/ street light fittings made up of innovative die cast aluminium housing high power LED as lighting source with IP - 65 power consumption 120 watt with toughened glass, colour white complete input voltage of 150-240 Volt (nominal rated voltage 240 Volt) complete including replacement of twisted 3 core copper cable of size 1.5 Sqmm dia for connecting phase, neutral and earth from junction box to light through connectors complete as specifiedand as directed. |
| 34 | S&F in replacement of new generation energy saving and environmental friendly long lifeLED flood light made up of innovative die cast aluminium housing high power LED as lighting source with IP - 66 power consumption 100 watt with toughened glass, colour white complete input voltage of 150-240 Volt (nominal rated voltage 240 Volt) complete including replacement of twisted 3 core copper cable of size 1.5 Sqmm dia for connecting phase, neutral and earth from junction box to light through connectors complete as specifiedand as directed. |
| 35 | S&F for replacement & testing commissioning of outdoor type bus bar panel weather proofMS cubical panelboard made of3.15 mm CRCA MS sheet outdoor type of size 110 cm x 80 cm x 40 cm, 4 Nos of aluminium bus bar of 400 Amp capacity with MCCB 4 pole of Capacity 250 Amp 25 KA (Ics =Icu=100%) including one coat of redoxide and two coat of enamel paint powder coated, mounted onangular frame work of 50x50x5mm thick angle iron base frame, minimum 60 cm hightand fixed with PCC 1:4:8 type D-2 (using 40mm graded crushed stone aggregate) in foundation for fixing panels,aluminium busbar chanel insulated with colour coated heat shrinkable sleaves and mounted on DMC/Epoxy insulator all as specified & directed. Make:- M/s Mclayers Bhopal/M/s shalabh(india) Ltd/ M/suniversal switchgear Ltd.Note:-(i) Panel drawing and make of MCCB and connected accessories will be submitted by the contractor for approval of Accepting officer before ordering the panel. (ii) The holes / aprons of cable exit and incoming should be close with suitable size of gland.( iii) The contractor should submit all Certificates before executing the job.(iv) CA No.,Contractor name, item of CA No. to be mentioned on the panel.(v)Suitable Cable glands for incoming cables and outgoing cable to be provided in the panel by the contractors. Cost of provisioning of cable glands deemed to be included in qouted rate. |
| 36 | S&F for replacement & testing commissioning of outdoor type bus bar panel weather proofMS cubical panelboard made of3.15 mm CRCA MS sheet outdoor type of size 110 cm x 80 cm x 40 cm, 4 Nos of aluminium bus bar of 300 Amp capacity with MCCB 4 pole of Capacity 200 Amp 25 KA (Ics =Icu=100%) including one coat of redoxide and two coat of enamel paint powder coated, mounted onangular frame work of 50x50x5mm thick angle iron base frame, minimum 60 cm hightand fixed with PCC 1:4:8 type D-2 (using 40mm graded crushed stone aggregate) in foundation for fixing panels,aluminium busbar chanel insulated with colour coated heat shrinkable sleaves and mounted on DMC/Epoxy insulator all as specified & directed. Make:- M/s Mclayers Bhopal/M/s shalabh(india) Ltd/ M/suniversal switchgear Ltd.Note:-(i) Panel drawing and make of MCCB and connected accessories will be submitted by the contractor for approval of Accepting officer before ordering the panel. (ii) The holes / aprons of cable exit and incoming should be close with suitable size of gland.( iii) The contractor should submit all Certificates before executing the job.(iv) CA No.,Contractor name, item of CA No. to be mentioned on the panel.(v)Suitable Cable glands for incoming cables and outgoing cable to be provided in the panel by the contractors. Cost of provisioning of cable glands deemed to be included in qouted rate. |
| 37 | S&F for replacement & testing commissioning of outdoor type bus bar panel weather proofMS cubical panelboard made of3.15 mm CRCA MS sheet outdoor type of size 110 cm x 80 cm x 40 cm, 4 Nos of aluminium bus bar of 250 Amp capacity with MCCB 4 pole of Capacity 160 Amp 25 KA (Ics =Icu=100%) including one coat of red oxide and two coat of enamel paint powder coated, mounted onangular frame work of 50x50x5mm thick angle iron base frame, minimum 60 cm hightand fixed with PCC 1:3:6 type C-2 (using 40mm graded crushed stone aggregate) in foundation for fixing panels,aluminium busbar chanel insulated with colour coated heat shrinkable sleaves and mounted on DMC/Epoxy insulator all as specified & directed. Make:- M/s Mclayers Bhopal/M/s shalabh(india) Ltd/ M/suniversal switchgear Ltd.Note:-(i) Panel drawing and make of MCCB and connected accessories will be submitted by the contractor for approval of Accepting officer before ordering the panel. (ii) The holes / aprons of cable exit and incoming should be close with suitable size of gland.( iii) The contractor should submit all Certificates before executing the job.(iv) CA No.,Contractor name, item of CA No. to be mentioned on the panel.(v)Suitable Cable glands for incoming cables and outgoing cable to be provided in the panel by the contractors. Cost of provisioning of cable glands deemed to be included in qouted rate. |
| 38 | M & L for earthing in repairscomplete with galvanized steel earth plate electrode600 x 600 x 6 mm thick burried directly in ground (earth pit not less than 2.25m deep below normal ground level)with top edge of the plate not less than 1.5 mtr below normal GL and connected to earth plate . Earth plate surrounded by 15 cm thick packed layers of charcoal dust and common saltupto 1.5 meter depth all around the earth plate and connected to earth leadof GI wire 4 mm diaby means of bolts, nuts, check nuts and washers of galvd iron or steel surronded by charcoal of coke and saltand protected by galvanized iron or steel pipe light grade 40 mm bore and water pipe 20mm bore GI medium grade with funnel and wire mesh, including all necessary excavation and earth work PCC chamber in cement concrete 1:3:6 type C-2 and RCC cover and all as shown in electrical plate No 3 of MES schedule Pt I of2009 and also including making test point for testing of earthingmade out ofgun metal or phosphorous bronge size 75x75x25 mm complete . Note : 1. RCC pit cover shall be pre-cast of RCC (1:2:4) type B-I , 80mm thick reinforced with XPM weighting not less than 4 KG/sqmmin lieu of CI cover.2. Charcoal dust and commonsaltupto 1.5 meter depth shall be filled in layers of 15 centimeters all around the earth plate inside earth pit .On testing after completion of earthing if desired earth resistance is not achieved , the earthing will be redone at no extra cost to obtain the desired earth values less than 2 ohms.3. The cost of GI earth lead and GI pipe of 7.50m lenth for protection of GI wire and excavationwork fpr pit shall deemed to be included in this item. |
| 39 | M & L for decorative LED post top gate light of capacity 20 W with IP 65 pretection resistant to impact and corrosion,glare free and better uniformityand complete fitting arrangement on gates/pillars complete all as specified and as directed. |
| 40 | Supply, erecting and fixing in true vertical position, steel tubular swaged pole (410 SP-31) 9 mtr long, complete with cast iron base plate, pole cap / finial taper plug, bolts, nuts and washers, welded reduced section and longitudinal weld throughout entire length of pole including 2 coats of black bituminous paint externally upto planting depth and remaining exterior portion of pole shall be provided withtwo coats of aluminium paint overone coat of red oxide primer and incl taking down existing old unserviceable poles complete all as specified and directed. (Numbering of the poles shall be done with synthetic enameled painted letter of shape & size as directed.) Note :- Excavation incl earth work and PCC foundation will be measured and paid separately. |
| 41 | Supply & fixing GI tube 50 mm bore light grade with all fittings for laid in trenches/fixed along with poles/walls & floor of buildings etc under crossing of road for protection of cables including demolition and taking down of the old existing pipe including repair of the floor/wall and matching with the existing surface if required complete as directed by Engineer-in-Charge. |
| 42 | M&L for painting of steel tubuler 11/9 mtr poles any type complete incl flat iron clamps,D clamps, Stay clamps, earth wire clamps, bracing, cross arm with two coat aluminium paint including prepration old painted surface initally & applying one coat of red oxide, applying two coat of aluminum paint over the red oxide, marking with alternate white and red strips 30 cm height 5 Nos strips with two coat of synthetic enamel paint (Ist quality of manufacturer )and also including numbering of poles with white paint are located on different locationscomplete all as specified and directed . |
| 43 | M & L for cutting of road up to 0.75m deep suitable for laying underground cable/MS tubes of any size/dia including GI pipe of 50mm dia and making good the disturbed area to match with the existing level with cement concrete including removing the surplus soil to a distance upto 50mtrscomplete all as specified and directed. |
| 44 | S&F in replacement Factory made sheet metal enclosure of CRCA sheet 2 mm thickness suitable for fixingofMCCB 4 pole with fixing arrangement including provision of MCCB04 pole125 Amp, 16 KA,( Ics=Icu=100%) cable connection with copper glands packing etc complete all as specified and direcetd. Make- ABB/Havells/L&T/Indo asian/Seimens |