| 1 | Taking down and Servicing offollowingceiling fans /exhaust fan /air circulator fan at siteand removing of old grease from bearing of ceiling fan and re-filling new grease including replacement of worn out nut, bolts, washers, gaskets grease, cotton waste etc and T&P such as chain pulley block ladders nut bolt/ washer and reassembling the fan complete and hanging on its original/ new position complete all as specified and as directed.NOTE :- Item NO 2 to 21 will be fixed under item No 1 and it will be paid and measured seperately. |
| 2 | (a) Ceiling Fan 1200/1400 mm sweep |
| 3 | (b) Exhaust fan heavy duty, metal body 380/400/450/600 mm sweep.(Installed at height upto 11 meter) |
| 4 | (c ) Air circulator fan, metal body 600 mm sweepNOTES for item No 1.01, 1.02 & 1.03 a)Quoted rates are deemed to be inclusive of the cost of all materials and labour required for dismantling and assembling of equipment in whole as a part there of and cost of minor spares and material required such as grease, nut bolts, washers, clamp, cable gland, supporting clamp, insulation tapes etcb)Major defects such asmotor rewinding, replacment of faulty bearings, capacitor does not includes in this cost. c) The rate quoted by the contractor is deemed to be inclusive ofthe cost of dismantling/taking down and reassembling/refixing of the item on its original location.d)The quoted rate include the cleaning of ceiling / exahust /air circulator fan of any capacity.e) Quoted rate is deemed to be inclusive all the safety equipment and other T andP required for carrying out the repairs / maintence. The contractor has to liase with the department in case of taking of electric shutdown of each machinery and the contractor shall provide the required arrangement mechineryto work at height because maximumfans/air circulators are at the height of more than 10 mtr.f)Maximum fans are installed at the height upto 12 mtr. Contractor are advised to see the site before quoting the rates.No extra payments will be done in this regard. |
| 5 | Material and labour for opening the body cover of fan any type and make and cutting the existingworn out winding with out damaging the stator, removing the coil insulation and putting new insulation of polyster paper, winding with super enameled copper wire of suitable gauge with correct number of turns of auxillary and main winding and varnishing and backing complete including thesoldering new lead of copper wire testing complete including transportation to work shop and back complete all as specified and as directed.NOTE :- a) Contractor have to make the arrangement for testing of Rewinded fan upto 24hrs at Complaint cell of AGE E/M-II (C) Kirkee b) Fan should be return to MES yard after rewinding within 10 days from the date of issue |
| 6 | (a)Ceiling Fan 1200 mm sweep |
| 7 | (b)Ceiling fan 1400 mm sweep |
| 8 | (C)Exhaust fansingle phase 250/280/300 mm Sweep |
| 9 | (d) Exhaust fan single phase380/ 450 mm Sweep |
| 10 | (e) Exhaust fan single phase 600 mm Sweep |
| 11 | (f) Air circulator fansingle phase 450 mm sweep |
| 12 | (g)Air circulator fansingle phase 600 mm sweep |
| 13 | Supply only dimmer controller 240 volts 50 Hz 400 Wattssuitable for air circulators complete all as specified and as directed. |
| 14 | Supply only following components / parts of ceiling / exhaust fans / Air Circulatorscomplete all as specified and as directed. |
| 15 | (a)SKF bearings 6201 2Z /6202 2Z/6203 2Z/ 6204 2Z |
| 16 | (b)SKF bearings 6301 2Z / 6301 2Z /6302 2Z |
| 17 | Supply only condenser / capacitor suitable for 440 volts single phaseof capacity 2.5 MFD to 10 MFD, complete all as specified and as directed. |
| 18 | Supply only (Brass) gun metal bush suitable for 1200 mm / 1400 mm sweep ceiling fan complete all as specified and as directed. |
| 19 | Supply only fan regulator electronic step type for 1200 mm /1400 mm sweep ceiling fan including necessary connection complete all as specified and as directed. |
| 20 | Supply only fan blade suitable for any make of following sweep all as directed at site by Engr -in-charge. |
| 21 | (a)Ceiling Fan 1200 mm sweep |
| 22 | (b)Ceiling Fan 1400 mm sweep |
| 23 | (c)Single Phase Exhaust Fan 250/280/300 mm Sweep |
| 24 | (d)Single Phase Exhaust Fan 380/450 mm Sweep |
| 25 | (e)Single Phase Exhaust Fan 600 mm Sweep |
| 26 | (f)Single Phase Air Circulator Fan 450 mm Sweep |
| 27 | (g)Single Phase Air Circulator Fan 600 mm Sweep |
| 28 | Supply only ceiling fan down rod of 15 mm dia GI pipe medium grade with holesfor nutbolt , connectors, clamps etc for fixing ceiling fan duly screwed for 0.6 to 1.8 mtrlength . |
| 29 | Supply onlyprotection gaurd round shape made out with M S wires Suitable clamps bolts and nut etc complete suitable for old air circulatorsof Usha/AUE/Almonard make for following sweep complete all as specified and as directed. |
| 30 | (a)Single Phase Air Circulator Fan 450 mm Sweep |
| 31 | (b)Single Phase Air Circulator Fan 600 mm Sweep |
| 32 | Supply onlyfan motor suitable for 250/300 mm exhaust fan of any make and model or as per site requirement complete all as specified and as directed. |
| 33 | Supply onlyfan motor suitable for 450 mm exhaust fan of any make and model or as per site requirement complete all as specified and as directed. |
| 34 | Supply onlyfan motor suitable for 600 mm exhaust fan of any make and model or as per site requirement complete all as specified and as directed. |
| 35 | Supply only fan motor suitable for capacity Single phase 240 volt 1400 RPMsuitable for 600 mm sweep wall Air circulator. makeanymodel or as per site requirement complete all as specified and as directed. |
| 36 | Supply only fan motor suitable for capacity Single phase 240 volt 1400 RPMsuitable for 1200/1400 mm sweep ceiling fanMakeanymodel or as per site requirement complete all as specified and as directed.Note for item No 11 to 15 :- (a) The trial motor should beprovided first and tested for fitting / performance/quality on the existing fan / air circulator . (b) Necessary addn/alteration for theproper installation to be carried out by the contractor at no extra cost . |
| 37 | Supply only mounting bracket of size 12\"/300 mm including necessary clamps bolts and nut etc complete suitable forexhaustfan motor as per existing shape all as specified and as directed. |
| 38 | Supply only mounting bracket of size 18\"/450 mm including necessary clamps bolts and nut etc complete suitable forexhaustfan motor as per existing shape all as specified and as directed. |
| 39 | Supply only mounting bracket of size 24\"/600 mm including necessary clamps bolts and nut etc complete suitable forexhaustfan motor as per existing shape all as specified and as directed. |
| 40 | Material and labour forpoint wiring in casing & caping of suitable size but not less than 20mm including all fittings such as elbow, bends, junction boxes, saddles, etc. on surface with and including ISI marked two runs of PVC insulated unsheathed multistranded copper conductor cable (FRLSH) 1.5 sqmm nominal cross sectional area, 1100 volts grade and including one run of 1.5 sqmm (green colour) ISI marked PVC insulated unsheathed multistranded (FRLSH) copper conductor cable as earth wire to be terminated in and incl PVC rectangular block of suitable size for mounting, switches, sockets, fan regulator etc. with 3 mm thick plastic laminated sheet cover for one light point or one fan point controlled by one switch including making good the disturbed wall and painting the same with matching to existing wallall as specified and as directed. |
| 41 | Description all as per srl item No 19 above but point wiring for light/fan/exhaust fan point controlled by one switch. |
| 42 | Description all as per srl item No 19 above but point wiring for 5 pin switch socket outlet 5 Amps on independent board controlled by one switch. |
| 43 | Description all as per srl item No 19 above but point wiring for 5 pin switch socket outlet 5 Amps on same board controlled by one switch. |
| 44 | Description all as per Srl item No 19 above butfor 2.5 sqmm point wiring for 5 pin switch socket outlet 15 Amps onindependentboard controlled by one switch. |
| 45 | Material and labour forpoint wiring inPVC conduit of suitable size but not less than 20mm including all fittings such as elbow, bends, junction boxes, saddles, etc. on surface with and including ISI marked two runs of PVC insulated unsheathed multistranded copper conductor cable (FRLSH) 1.5 sqmm nominal cross sectional area, 1100 volts grade and including one run of 1.5 sqmm (green colour) ISI marked PVC insulated unsheathed multistranded (FRLSH) copper conductor cable as earth wire to be terminated in and incl PVC rectangular block of suitable size for mounting, switches, sockets, fan regulator etc. with 3 mm thick plastic laminated sheet cover for one light point or one fan point controlled by one switch including making good the disturbed wall and painting the same with matching to existing wallall as specified and as directed by Engineer in charge. |
| 46 | Description all as per Srl item No 24 above but light/fan/exhaust fan point controlled by one switch. |
| 47 | Description all as per Srl item No 24 above but 5 pin switch socket outlet 5 Amps on independent board controlled by one switch. |
| 48 | Description allas per Srl item No 24 above but 5 pin switch socket outlet 5 Amps on same board controlled by one switch. |
| 49 | Description all as per Srl item No 24 above but for 2.5 sqmm 5 pin switch socket outlet 15 Amps on independent board controlled by one switch. |
| 50 | Material and labour for point wiring completeas specified with 1100 V grade4 Sqmm single core PVC insulated unsheathed multistranded copper conductor cable FR grade, conforming to relevant IS drawn through and including PVC casing and caping with all accessories fixed on surfaces of wall, ceiling, incl PVC rectangular block of suitable size for mounting, switches, sockets, fan regulator etc. with 3 mm thick plastic laminated sheet cover including 4 Sqmm single core PVC insulated and unsheathed copper conductor cable FR grade as earth continuity wire connected to common earthand earth dolly including testing complete all as specifiedand directed.for one 6 pin switch socket outlet 15 Amps/AC Point on independent board controlled by one switch. |
| 51 | Description all as per srl item No 29 above but for for one 6 pin switch socket outlet 15 Amps/AC Point on independent board controlled by one switch in PVC conduit. |
| 52 | Supplying and fixing ceiling rose PVC/polycarbonate, isolated body, three terminals, complete all as specified & directed . |
| 53 | Supply and fix switch socket combination 2 in 1, 5 pin, 5 Amp flush type universal. |
| 54 | Supply and fix switch piano flush type single pole, one way 5 Amp. |
| 55 | Supply and fix switch flush type,15 Amps, single pole , one way , 230 volts AC circuit complete all as specifiedand diected |
| 56 | Supply and fixsocket flush type ,15 Amps , single pole, one way, 230 volts AC circuit complete all as specifiedand diected |
| 57 | Dismantling and taking out old unserviceable aluminum/copper sub main wiring/unarmoured cable (used as Sub main wiring) from any height of any Size and core with all connecting accessories incld. conduit or casing caping and incld. making good to the disturbed wall and painting the same with matching paint as of existing wall including material all as specified and directed. |
| 58 | Material and labour for sub main wiring at any height with 2 single core PVC insulated, multi stranded copper conductor cable (FRLSH), unsheathed, 1.5 sqmm, 1100 volt grade conforming to IS drawn through and including New 20 mm PVC conduit and including one single core PVC insulated multi stranded unsheathed copper conductor cable, 1.5 sqmm,, FRLSH green in colour as continuous earth wire including all accessories and fixing arrengements, supporting clamps, bends, sockets and connecting items etc. all as specified and as directed. |
| 59 | Description all as per Srl item No 37 above but for casing & capping |
| 60 | Material & labour for sub main wiring at any height with 2 single core PVC insulated, multi stranded copper conductor cable (FRLSH), unsheathed, 2.5 sqmm, 1100 volt grade conforming to IS drawn through and including New 20 mm PVC conduit and including one single core PVC insulated multi stranded unsheathed copper conductor cable, 2.5 sqmm,, FRLSH green in colour as continuous earth wire including all accessories and fixing arrengements, supporting clamps, bends, sockets and connecting items etc. all as specified and directed. |
| 61 | Description all as per Srl item No 39 above but for casing & capping |
| 62 | Material and labour for sub main wiring at any height and surface with and including two single core PVC insulated multi stranded copper conductor cable, conforming to IS, FRLSH type, 4.0 Sqmm, 1100 volts grade, drawn through and including New PVCconduit 20 mm dia including connected accessories and one single core PVC insulated multi stranded unsheathed copper conductor cable,FRLSH type, 4.0 sqmm, 1100 Volts grade,,green in colour as earth contuinity wire all as specified and as directed. |
| 63 | Description as per Srl item No 41 above but for casing & capping |
| 64 | Material and labour for sub main wiring at any height and surface with and including two single core PVC insulated multi stranded copper conductor cable, conforming to IS, FRLSH type, 6.0 Sqmm, 1100 volts grade, drawn through and includingincluding New PVCconduit 20 mm dia connected accessories and one single core PVC insulated multi stranded unsheathed copper conductor cable,FRLSH type, 6.0 sqmm, 1100 Volts grade,,green in colour as earth contuinity wire all as specified and as directed. |
| 65 | Description as per Srl item No 43 above but for casing & capping |
| 66 | Dismantling and taking down unserviceable any light fitting from any location/height after disconnecting of electrical connection complete including all connected accessories all as directed by Engr-in-Charge. |
| 67 | Supply and fixing InvertorLED batten polycarbonatebody tube light fitting suitable for and including 1x20 W 4 feet long tube with polycarbonate diffuser complete including connecting up to ceiling rose with twin core twisted flexible copper conductor cable with suitable size & all accessories for fixing on steel trusses / false / normal ceiling all as specified & directed.MAKE :- cromptonor equivalent in Bajaj/havells |
| 68 | Supply and fixing LED type luminiare suitable for and including 2x20 W 4 feet long complete including tube rod & connecting up to ceiling rose with twin core twisted flexible copper conductor cable with suitable size & all accessories for fixing on steel trusses / false / normal ceiling all as specified & directed. MAKE :- Bajajor equivalent in Havells/Crompton |
| 69 | Supply and fix MCCB thermal magnetic releasefour pole 25 KA 63 Ampswith one way metal inclosureand making conections of cables with suitable size nutbolt etc including making good the disturbed suface of wall including material complete all as specified and as directed. |
| 70 | Supply and fix MCCB thermal magnetic release four pole 25 KA 100 Ampswith one way metal inclosure and making conections of cables with suitable size nutbolt etc including making good the disturbed suface of wall including material complete all as specified and as directed. |
| 71 | Supply and fix MCCB thermal magnetic release four pole 25 KA 160 Ampswith one way metal inclosureLegrand/ Siemens/ABBand making conections of cables with suitable size nuts, bolt etc including making good the disturbed suface of wall complete all as specified and as directed. |
| 72 | Supply and fix one way metal ednclosure all as perLegrand/ Siemens/ABB and MCB \"C\" curve TPN 10 KA 32Amps Legrand/ Siemens/ABBand making conections of cables with suitable size nuts, bolt etc. including making good the disturbed suface of wall complete all as specified and as directed. |
| 73 | Supply, fixing, connecting and testing in replacement of industrial earth plug & socket with sheet metal enclosure of IP 44 protection rating,electric driven, single phase including MCB \"C\" series SP 20 Amps and supplied with neutral link complete all as specified and as directed. |
| 74 | Supply, fixing, connecting and testing in replacement industrial earth Plug & socket with sheet metal enclosure of IP 44 protection rating, electric driven three phase including MCB \"C\" series TP 20 Amps and supplied with neutral link complete all as specified and as directed. |
| 75 | Disconnecting and taking down olddistribution box with MCB/fuse grip TPN/SPN DB 2 Way to 12 Way old type DB including taking out all cable connections of any description and in any position and making good the disturbed surface of walls, to match with the existing surfaces complete all as specified and as directed. |
| 76 | Supply and fix, connecting & testing of VTPN DB of 12 way suitable for MCCBup to 160A as a incomer & SP / TP MCB as a outgoings with IP 43 -IK09 as conforming to IEC 61439-3 & made of high quality CRCA sheet shall have integrated door earthing system, shall have reversible door facility, ergonomic design with rounded corners to protect against damage like bending, peeling of paint hence preventing rusting. DB shall be with Insulated Busbar with withstand capacity of 36kA, shrouded neutral bar, door earthing, corner Safe. wiresets, shrouded neutral bar, earth bar & wire ties, complete all as specified and as directed.NOTE :- MCCB , MCBwill be measured and paid separately under relevant item of this schedule. |
| 77 | Supply and fix, connecting & testing of VTPN DB of 8 way suitable for MCCBup to 160A as a incomer & SP / TP MCB as a outgoings with IP 43 -IK09 as conforming to IEC 61439-3 & made of high quality CRCA sheet shall have integrated door earthing system, shall have reversible door facility, ergonomic design with rounded corners to protect against damages like bending, peeling of paint hence preventing rusting. DB shall be with Insulated Busbar with withstand capacity of 36kA, shrouded neutral bar, door earthing, corner Safe. wiresets, shrouded Neutral bar, earth bar & wire ties, all as specified and as directed.NOTE :- MCCB , MCBwill be measured and paid separately under relevant item of this schedule. |
| 78 | Supply and fix, connecting & testing of VTPN DB of 4 way suitable for MCCBup to 160A as a incomer & SP / TP MCB as a outgoings with IP 43 -IK09 as conforming to IEC 61439-3 & made of high quality CRCA sheet shall have integrated door earthing system, shall have reversible door facility, ergonomic design with rounded corners to protect against damages like bending, peeling of paint hence preventing rusting. DB shall be with Insulated Busbar with withstand capacity of 36kA, shrouded neutral bar, Door earthing, corner Safe. wiresets, shrouded Neutral bar, earth bar & wire ties, a complete all as specified and as directed. NOTE :- MCCB , MCBwill be measured and paid separately under relevant item of this schedule. |
| 79 | Supply and fix, connecting & testing SPN DBs of 8 way for using MCBs / MCB isolators suitable for single pole and neutral, with IP 43 -IK09 as conforming to IEC 61439-3 & made of high quality CRCA sheet shall have integrated door earthing system, shall have reversible door facility, ergonomic design with rounded corners to protect against damages like bending, peeling of paint hence preventing rusting. DB shall be with Insulated Busbar with withstand capacity of 10kA, shrouded neutral bar, door earthing, corner Safe. wiresets, shrouded neutral bar, earth bar & wire ties, complete all as specified and as directed. |
| 80 | Supply and fix, connecting & testing SPN DBs of 12 way for using MCBs / MCB isolators suitable for single pole and neutral, with IP 43 -IK09 as conforming to IEC 61439-3 & made of high quality CRCA sheet shall have integrated door earthing system, shall have reversible door facility, ergonomic design with rounded corners to protect against damages like bending, peeling of paint hence preventing rusting. DB shall be with Insulated Busbar with withstand capacity of 10kA, shrouded neutral bar, door earthing, corner Safe. wire sets, shrouded neutral bar, earth bar & wire ties, all as specified and as directed. |
| 81 | Supply and fix ceiling fan of 1200 mm sweep 5 star ratingincluding provision of cable from ceiling rose or connector to fan,anchor bolt for fixing of ceiling fan,ceiling fan rod at any height complete all as specified and as directed. |
| 82 | Supply and fix exhaust fan (Metal body)AC single phase 230/240 V of size 300 mm sweep with louvres and provn of flexible copper cord from ceiling rose to fan including making hole in wall without making disturbed the good surface complete all as specified and as directed. |
| 83 | Supply and fix exhaust fan (Metal body)AC single phase 230/240 V of size 450 mm sweep with louvres and provn of flexible copper cord from ceiling rose to fan including making hole in wall without making disturbed the good surface complete all as specified and as directed. |
| 84 | Supply and fix exhaust fan (Metal body)AC single phase 230/240 V of size 600 mm sweep with louvres and provn of flexible copper cord from ceiling rose to fan including making hole in wall without making disturbed the good surface complete all as specified and as directed. |
| 85 | Supply and fix Wall mounted fan 400mm sweep 230V, AC, SP oscilating swing type with all acceessories and fixing arrengement complete all as specified and as directed. |
| 86 | Supply and fix exhaust fan (PVCbody white ) AC single phase 230/240 V of size 250 mm sweep with louvres and provn of flexible copper cord from ceiling rose to fan including making hole in wall without making disturbed the good surface complete all as specified and as directed. |
| 87 | Supply and fix air circulator fan 600mm sweep 230V, AC, SP oscilating swing type with all acceessories and fixing arrengement complete all as specified and as directed. |
| 88 | Supply only MCCB FP, 16kA, 63 AMPS with thermal magnetic release, Ics = 100% Icu, adjustable over load setting: 0.8 -1.0 x In, adjustable short circuit for each phase from 5 - 10 x Ir including supply only of spreader terminals, disconnecting and dismantling old unserviceable MCCB to the complete satisfaction of Engr-in-Charge . |
| 89 | Supply only MCCB FP, 25kA, 100 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, Adjustable short circuit for each phase from 5 - 10 x Ir including supply only of spreader Terminals, disconnecting and dismantling old unserviceable MCCB to the complete satisfaction of Engr-in-Charge. |
| 90 | Supply only MCCB FP, 25kA, 160 AMPS with thermal magnetic release, Ics = 100% Icu, adjustable Over Load setting: 0.8 -1.0 x In, adjustable short circuit for each phase from 5 - 10 x Ir including supply only of spreader terminals, disconnecting and dismantling old unserviceable MCCB to the complete satisfaction of Engr-in-Charge. MAKE :- Legrandor equivalent to ABB/L&T/Seimens |
| 91 | Supplying & fixing MCB 6 to 32 Amps, single pole and neutral, \"C\" curve10 kA breaking capacity with integrated label holder,sliding bottom clamp, color coded on/off indication on dolly complete all as specified and as directed. |
| 92 | Supplying & fixingMCB 6 to 32 Amps, single pole, 10 kA breaking capacity with integrated label holder, sliding bottom clamp, color coded on/off indication on dolly,complete all as specified and as directed. |