| 1 | Drain out the Sewage sumps of capacity 6000/8000 glns and cleaning of sludges up to bottom level at sewage pump houses and takingoutand depositing the sludge not more than 50 m ,including excavated earth and covered with earth and spreading bleaching powder allaround as directed. |
| 2 | Dismantling and taking down unservicibleelectric motor installed at Sewage pump house 3 phase 415 Volts, 15 HP capacity, disconnection of incoming electric connection from panel, stripping out burnt wiring, cleaning slots and rewinding the motor with super enameled copper wire as per existing size and gaugeincluding insulating materials and varnishing, replacing worn out bearing as per existing size, reassembling the motor after rewinding and mounting on its original position including replacing the old unserviceable nuts, bolts and tested completed all as directed . |
| 3 | All as per Item No.2 above but of capacity 7.5 HP |
| 4 | All as per Item No.2 above but of capacity5 HP |
| 5 | Dismantling and taking down the electric motor of sewage pump set 15 HP capacity and transporting to work Shop and carrying out servicing/ maintenance of motor unit as per the following maintenance work:-(a) Opening of electric motor and cleaning/ removing dust from Armature andfield coil(b) Cleaning of used/ old lubricated substance(c) Cleaning of starter and rotor unit(d) Checking and tightening of coupling, nuts, bolts and replacement of rubber insert.(e) Carrying out heat varnishing with varnish solution of best quality for field and armature coil.(f) Replacement of oil worn out bearings.(g)Reassembling the complete motor and carrying out testing at work Shop and transporting back to installation and coupling with pumping set including necessary alignment, cable connection all as directed |
| 6 | All as per Item No.5 above but of capacity 7.5 HP |
| 7 | All as per Item No.5 above but of capacity5 HP |
| 8 | Disconnecting the suction and delivery pipe line and electric connections of centrifugal non clogging pump set coupled with electric motor 15 HP, 3 Phase and removing it from its position carefully and transportingto the work shop and refixing the same in its original position after servicing including replacement of bushes , machining the pump shaft to suit in new bushes all as specified and as directed.Note: (i) Consumable stores like cotton waste/cleaning materials lubricants , gland packing metal filling , machining and transportationfrom site to work shop are deemed to be included inrate quoted. |
| 9 | All as per item No 8 but for centrifugal non clogging pump set coupled with electric motor 7.5 HP complete. |
| 10 | All as per item No 8 but for centrifugal non clogging pump set coupled with electric motor 5 HP complete. |
| 11 | M&L for cleaning & Scraping of old painted surface of the pumps and motors of any capacity (05 hp to 15 hp) ,and painted with two coats of synthetic super enamelled paint of desiered colour including marking the flow of waste water pipe lines completespecified and directed. |
| 12 | Supply and fix in repair 80 mm dia pipe foot valve as perIS-4038 of cast iron with brass diaphragm heavy dutyscrewing type complete of the following sizes .Make-Kirloskar/Kartar/Leader/Upadhaya |
| 13 | Supply and fix in repair 100 mm dia pipe foot valve as perIS-4038 of cast iron with brass diaphragm heavy dutyscrewing type complete of the following sizes .Make-Kirloskar/Kartar/Leader/Upadhaya |
| 14 | S&FFully Automatic star delta starter Submersible pump controller(IP54) 15 HP capacity, 11 KW,415coil voltage withrelay range 13-21 Amps including combined V/A meter,voltmeter selector switch, star delta timer and SPPsuitable for 15 HP submersible/ Centrifugal pumping set including taking down old star delta starter all as specified and directed. |
| 15 | S&FFully Automatic star delta starter Submersible pump controller(IP54) 7.5 HP capacity, 5.5 KW,415coil voltage withrelay range 6-10 Amps including combined V/A meter,voltmeter selector switch, star delta timer and SPPsuitable for 7.5 HP submersible/ Centrifugal pumping set including taking down old star delta starter all as specified and directed. |
| 16 | S&FFully Automatic DOL starter Submersible pump controller(IP54) 7.5 HP capacity, 5.5 KW,415coil voltage withrelay range13-22 Amps including combined V/A meter,voltmeter selector switch,SPPsuitable for 7.5 HP submersible/ Centrifugal pumping set including taking down old star delta starter all as specified and directed. |
| 17 | Material and labour for providing two coats of synthetic enamel paint to any metel surface after removing of old paint by rubbing embroyed paper/wire brushed andPriming with aluminium red oxide on complete surfaces all as specified anddirected. |
| 18 | M & L Framed work such as grills, gratings, etc.. with ends of bars shouldered and/or riveted, or forged into spikes; framed guard bars; barred iron doors; ladders; framed balusters; walk ways; railings; framework of water tanks and similar work conforming to Fe.290.Gde-E-165 including taking out oldall as specified and directed. |
| 19 | Supply and fixing in repairs PVC insulated and sheathedCopper Flexible Cable cable, 3 core, multistranded copper conductor of 1100 volts grade conforming to IS-694,ofsize 10 sqmm in PVC conduit from starter to sewage pump Make-Havells/Finolex/Polycab. |
| 20 | Supply and fix in repair CI sluicevalve80 mm dia bore pipe flangedof class PN 1.6 conforming to IS - 14846 complete with iron wheel head , SS spindle and check nut , includingjointing material such as rubber insertionnuts, bolts andwashers etc complete ,of following size: Make - Kirloskar/upadhaya/Leader/Zoloto or eqvlnt. |
| 21 | All as per item No 20 above but for 100 mm dia bore pipe |
| 22 | Supply and fix in repair 80 mm dia bore CINon - Return Valves without by pass arrangement , ISI marked , heavy duty , flangedtype including rubber sheet & nut bolts etc completeall as specified by the Engr-in-charge of following size . Make - Kirloskar/Upadhaya/Leader/Zoloto or equivalent |
| 23 | All as per item No 22 above but for 100 mm dia bore pipe |
| 24 | M&L for Earthing complete with GI earth plate electrode of size 600x600x6 mm thick buried directly in ground with earth pit not less than 2.25 meter deep below ground level with top edge of plate not less than 1.5 meter below normal ground level connected to 32x6 mm GI iron strip earth lead by means of nuts, bolts, check nuts, washers of galvanised iron as steel,protected by galvanized iron pipe 40mm bore (Medium grade) allas directed including cement concrete (1:3:6) type C-1 earth pit with Cast iron cover slab of size 42cm x 42 cm and 10mm thick , funnel,wire mesh, 20 mm bore galvanized iron pipe (medium grade) for watering, earth testing point, charcoal or coke and salt in alternate layers with necessary earth work in soft/loose soil complete all as shown in electrical plate No 3 of SSR Part I including testing on completion all complete as specified and directed after taking down old earthing.(note :- 7.5 mtr GI strip with GI pipe is included in above item) |
| 25 | M&L for earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc for size 32x6 mm galvanised iron strip complete all as specified and directed. |
| 26 | Taking down the existing LT Panel board andSupply , install , test and commissioning of factory made CPRI ApprovedLT Panel board, outdoor type of make as pecified in list of Makes withsize not less than1.2m x 1.2m x 0.5 m, made out of CRCA sheet of 3.15 mm of outer cover and 2mm thick sheet of inner compartment with 50x50x6 mm of angle iron frame duly painted with powder coating over a coat of red oxide primer all over with canopy totally enclosed weather, dust and vermin proof with front and rear openable doors with locking arrangement suitable for 3 phase 4 wire LT AC, 50 Hz, 415 Voltswith suitable copper bus barwith lifting PCC foundation/platform as per manufacturer guide lines for installing the panel board complete for accommodating the following accessories. Incoming:-(a) MCCB 100 amps, four pole ,25 KA 01 No (b) On load change over switch 100 Amps , 4 pole - 01 No (c) LED Multi function meter - 01 No (d)CT 100/5 - 03 Nos M(e) LED type Indicating lamp R, Y, B (set of 3 ) -01set (f) Copper bus bar-04 nos of current rating capacity not less than 150 Amps.(g) Necessary wiring including wiring material and copper strip.Outgoing:- (a) MCCB 32 amps, four pole ,25 KA- 02No (b) MCB SPN 40A, C curve ,10KA -01 Nos (c) S&FFully Automatic star delta starter Submersible pump controller(IP54) 15 HP capacity, 11 KW,415coil voltage withrelay range 13-21 Amps including combined V/A meter,voltmeter selector switch, star delta timer and SPPsuitable for 15 HP submersible/ Centrifugal pumping - 02 Nos.Model -MU G20 FASD of Make - L&T or equivalent of modelin Havells/Crompton Greaves/BCH /C&S |
| 27 | M&L for Brickwork with subclass ‘B’ old size bricks with cement mortar (1:4) straight or curved on plain exc 6 m mean radius complete all as specified ad directed. |
| 28 | M & L for cement concrete in copping type B1 1:2:4 using 20 mm graded stone aggregate complete all as specified ad directed. |
| 29 | M&L for Rendering / plastering 15 mm thick with cement mortar (1:4) on fare faces of brick work or concrete surfaces complete all as specified ad directed. |
| 30 | Excavation in trenches not exc 1.5 wide and not exc 1.5 mtr deep and getting out in soft/loose soil for laying pipes complete all as specified . |
| 31 | Returning and filling in soils , includingspreading ,levelling ,wateringand well ramming in layersnot exc25 cm thick completeall as specified . |
| 32 | Removal of excavated material to a distance not exc 50 m away from starting pointand depositing where directed at a level notexc 1.5 mtr above the starting pointcomplete all as specifiedand directed |
| 33 | Supply,laying and testing ofcable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size of size 35 sqmm 3.5 core complete as directed. |
| 34 | M & L for Sand covering /cushioning for under ground cable protection complete all as specified and as directed |
| 35 | Supply and laying burntbricks sub class\"B\" laid perpendicularover & cushioning for cable protectioncomplete all as specified & directed at site by the Engr- in Charge. |
| 36 | M & L for taking out old corroded unserviceable MS sheet cover, frame etc from top of the roof of the under ground sewage sumpwith MS channel base square / circular type , of any size and shapeincluding providing of newcover made out of 3.15 mm MS sheet coverwith 50 cm X 50 cm X 6 mm angle iron base frame including painting with two coatsblack bituminous paint over a coat of red oxide primer complete with locking arrangementsall as specified and directed.Note-MS sheet and angle iron only be measured for payment . |
| 37 | Supply only Strong bleaching powder stable type suitable for disinfectant of pump house sweage chember etc complete all as specified and directed.Note- Contractor shall submit original copy of purchase vouchar alongwith manufacturers test certificate before claiming any payment. |
| 38 | S&FMS ERW pipe of 80 mm dia pipe with provision of necessary MS bend, MS flange etc, by cutting and welding and painting with two coats of synthetic enamel paint over a coat of primer and testing including taking down old MS pipe. |
| 39 | S&FMS ERW pipe of 100 mm diapipewith provision of necessary MS bend, MS flange etc, by cutting and welding and painting with two coats of synthetic enamel paint over a coat of primer and testing including taking down old MS pipe. |
| 40 | M&L MCCB 4 Pole, current rating 100 Amp, breaking capacity 18kA at 415V,50Hz including connection and testing complete all as directed. |
| 41 | S&Fon load change over switch 100 Amps 4 pole for open mount including taking downold change over switch all as directed. |
| 42 | M & L forGalvanized Iron water tubing \" Medium Grade\"80 mm dia bore pipe with all fittings and fixture to walls and ceilings or laid in floors Complete all as specified and directed. |
| 43 | M & L forGalvanized Iron water tubing \" Medium Grade\"100 mm dia bore pipe with all fittings and fixture to walls and ceilings or laid in floors Complete all as specified and directed. |
| 44 | Complete removal of existing treatment by manually/ mechanically on walls /ceiling & cornices etc.by brooming down or steel wire brushing, scrapping down smoke soot, moulds, moss & efflorescent salts and trading oil & greasy spots incl washing, rubbing down and stopping of painted surfaces at any height of the bldg complete all as specified and directed.(Note : (1) Rate quoted shall be inclusive of all scaffolding, props and other T&P) |
| 45 | M&L for applying 1mm thick wall care putty of approved make to prepare the surface even and smooth at any height of the bldg complete all as specified & directed. |
| 46 | M&L for applying two coats of acrylic emulsion distemperwith one coat of alkali resistant priming paint of shades as approved by GE at any height of the bldg complete all as specified and directed. |
| 47 | M&L forapplying two coats of 100% acrylic emulsion exterior paint over a coat of primer of shades as approved by GE at any height of the bldg complete all as specified and directed. |
| 48 | M&L for preparation of old decorated surfaces of walls, cornices etc by brooming down or steel wire brushing, scrapping down smoke soot, moulds, moss & efflorescent salts and trading oil & greasy spots and applying one coat of 100% acrylic emulsion exterior paint of shades as approved by GE at any height of the bldg complete all as specified and directed. |
| 49 | M&L for preparation of old decorated surfaces of walls, cornices etc by brooming down or steel wire brushing, scrapping down smoke soot, moulds, moss & efflorescent salts and trading oil & greasy spots and applying one coat of acrylic emulsion distemper of shades as approved by GE at any height of the bldg complete all as specified and directed. |
| 50 | All as per item no. 49 here-in-before but on ceiling. |
| 51 | M&L for preparation of old decorated surfaces of walls, cornices etc by brooming down or steel wire brushing, scrapping down smoke soot, moulds, moss & efflorescent salts and trading oil & greasy spots and applying one coat of cement based paint of shades as approved by GE at any height of the bldg complete all as specified and directed. |
| 52 | M&L for preparation of old decorated surfaces of walls, cornices etc by brooming down or steel wire brushing, scrapping down smoke soot, moulds, moss & efflorescent salts and trading oil & greasy spots incl washing, rubbing down and stopping of distempered/painted surfaces and applying two coats of cement based paint of shades as approved by GE at any height of the bldg complete all as specified and directed. |
| 53 | M&L for preparation of old painted surface of wood and wood based surfaces by knotting, stopping etc of any description exc 10 cm width or girth and applying one coat of synthetic enamel paint at any height complete all as specified and directed. |
| 54 | M&L for preparation of old painted steel and iron surfaces of any description exc 10 cm width or girth and applying one coat of synthetic enamel paint at any height of bldg/sign board complete all as specified and directed. |
| 55 | Taking down cement plaster on brick or stone walls etc at any height including raking out joints, hacking for key, scrubbing down with water etc complete all as specified and directed. |
| 56 | M&L for 10mm thick rendering in CM 1:6 on brick work or concrete surfaces finished even and smooth without using extra cement at any height including wire mesh nettting where ever required complete all as specified and directed.(Note : Wire mesh netting shall be measured separately) |
| 57 | M&L for 15mm thick rendering in CM 1:4 on brick work or concrete surfaces finished even and smooth without using extra cement with water proofing compound mixed as per manufacturers instruction at any height including wiremesh nettting where ever required complete all as specified and directed.(Note : Wire mesh netting shall be measure separately) |
| 58 | M&L for rendering 5 mm thick in CM 1:3on ceiling surfaces finished even and smooth without using extra cement at any height including wire mesh nettting where ever required complete all as specified and directed.(Note : Wire mesh netting shall be measure separately) |
| 59 | S&F GI wire netting 0.90mm dia and 12mm mesh lathing to plastered/concrete surfaces, wood or metal studding, joists, etc. in walls, ceilings, stanchions, beams, etc. including all laps, cutting and waste complete all as specified and directed. |
| 60 | M&L for preparation of newly plastered or unplastered surfaces of walls, cornices etc by brooming down or steel wire brushing, scrapping down smoke soot, moulds, moss & efflorescent salts and trading oil & greasy spots incl washing, rubbing down and stopping of distempered/painted surfaces and applying two coats of acrylic emulsion distemper of shades as approved by GE over a coat of cement primer complete all as specified and directed. |
| 61 | All as per item no. 60 here-in-before but on ceiling. |
| 62 | M&L for preparation of newly plastered or unplastered surfaces of walls, cornices etc by brooming down or steel wire brushing, scrapping down smoke soot, moulds, moss & efflorescent salts and trading oil & greasy spots incl washing, rubbing down and stopping of painted surfaces and applying two coats of cement based paint of shades as approved by GE over a coat of alkali resistant priming paint complete all as specified and directed. |
| 63 | M&L for preparation of newly plastered or unplastered surfaces of walls, cornices etc by brooming down or steel wire brushing, scrapping down smoke soot, moulds, moss & efflorescent salts and trading oil & greasy spots incl washing, rubbing down and stopping of painted surfaces and applying two coats of 100% acrylic emulsion exterior paint of shades as approved by GE over a coat of alkali resistant priming paint complete all as specified and directed. |
| 64 | M&L for writing letters/figures (Block, Roman, Italic or Indian (HINDI) ) with thick synthetic enamel paint not exc 30 cm high at any height of bldg/sign boardcomplete all as specified and directed. |