| Sl. No. | Item Description |
| 1 | Supplying and laying or fixing in replacement, jointing and testing LT under ground electric power cablecrossed linked polyethylene ( XLPE)insulated, galvanised steel strip or wire armoured,ISI marked, with aluminium conductor multi stranded , heavy duty 1100 Volts grade of size 10 sqmm cross sectional area, 2 core, complete laid in trenches / laid under floor or fixed naked with walls / on poles/ in ducts /in GI pipes etc. with and including MS Clamps, nuts, bolts, washers complete. Note :-Excavation, earth work, sand cushioning, protection bricks/ tiles/ block andpipe shall be measured and paid separately under appropriate items. |
| 2 | All as per item No 02 above but LT UG Cable of size 10 Sqmm 4 core |
| 3 | All as per item No 02 above but LT UG Cable of size 16 Sqmm 4 core |
| 4 | All as per item No 02 above but LT UG Cable of size 25 Sqmm 3.5 core |
| 5 | All as per item No 02 above but LT UG Cable of size 50 Sqmm 3.5 core |
| 6 | All as per item No 02 above but LT UG Cable of size 95 Sqmm 3.5 core |
| 7 | All as per item No 02 above but LT UG Cable of size 185 Sqmm 3.5 core |
| 8 | All as per item No 02 above but LT UG Cable of size 240 Sqmm 3.5 core |
| 9 | Excavation in trenches, not exceeding 1.5 m wide and not exceeding 1.5 m in depth for laying of cables, pipes etc. and getting outincluding trimming the sides and forming bottom surfaces to required levels in soft / loose soilcomplete. |
| 10 | Returning filling in,. Including spreading, levelling,. Watering and well ramming in layers not exceeding 25 cm thick, using excavated soil all as specified and directed. |
| 11 | Removing excavated soil from site to a distance n. exc 50 meters away and depositing where directed at a level n. exc. 1.5 mtr above the starting point all as specified and directed by Engineer-in-Charge. |
| 12 | Supply and laying in trenches/Floor/road crossing or fixed to Pole/Wall GI pipe light grade ISI marked with fitting of size 80 mm bore for protection of cable including taking down existing pipe complete all as specified and directed by the Engineer-in-Charge. |
| 13 | Supply and laying in trenches/Floor/road crossing or fixed to Pole/Wall GI pipe light grade ISI marked with fitting of size 50 mm bore for protection of cable including taking down existing pipe complete all as specified and directed by the Engineer-in-Charge. |
| 14 | Supply and laying in trenches/Floor/road crossing or fixed to Pole/Wall GI pipe light grade ISI marked with fitting of size 40 mm bore for protection of cable including taking down existing pipe complete all as specified and directed by the Engineer-in-Charge. |
| 15 | Material and labour for PCC 1:2:4 type B-2 using 40 mm graded stone aggregates for filling of cutting of roads / path / hardstanding etc complete all as specified and as directed by Engineer-in-Charge. |
| 16 | Supply, fix, connecting andtesting in repairMCCB 160 Amp 4 pole 16 KA 415 volts 50 Hz adjustablethermal & adjustable magnetic release with spreader,MCCB shall have double make, double break with Arc Chute per pole fixed in existing panel including all connection complete all as directed. |
| 17 | Supply, fix, connecting andtesting in repairMCCB 200 Amp 4 pole 36 KA 415 volts 50 Hz adjustablethermal & adjustable magnetic release with spreader,MCCB shall have double make, double break with Arc Chute per pole fixed in existing panel including all connection complete all as directed. |
| 18 | Supply, fix, connecting andtesting in repairMCCB 250 Amp 4 pole 36 KA 415 volts 50 Hz adjustablethermal & adjustable magnetic release with spreader,MCCB shall have double make, double break with Arc Chute per pole fixed in existing panel including all connection complete all as directed. |
| 19 | Supply, fix, connecting andtesting in repairMCCB 400 Amp 4 pole 36 KA 415 volts 50 Hz adjustablethermal & adjustable magnetic release with spreader,MCCB shall have double make, double break with Arc Chute per pole fixed in existing panel including all connection complete all as directed. |
| 20 | Supply, fix, connecting andtesting in repairMCCB 630 Amp 4 pole 36 KA 415 volts 50 Hz adjustablethermal & adjustable magnetic release with spreader,MCCB shall have double make, double break with Arc Chute per pole fixed in existing panel including all connection complete all as directed. |
| 21 | Supply, fix, connecting andtesting in repairMCCB 100 Amp 3 pole 16 KA 415 volts 50 Hz adjustablethermal & adjustable magnetic release with spreader,MCCB shall have double make, double break with Arc Chute per pole fixed in existing panel including all connection complete all as directed. |
| 22 | Supply, fix, connecting andtesting in repairMCCB 125 Amp 3 pole 16 KA 415 volts 50 Hz adjustablethermal & adjustable magnetic release with spreader,MCCB shall have double make, double break with Arc Chute per pole fixed in existing panel including all connection complete all as directed. |
| 23 | Supply, fix, connecting andtesting in repairMCCB 160 Amp 3 pole 16 KA 415 volts 50 Hz adjustablethermal & adjustable magnetic release with spreader,MCCB shall have double make, double break with Arc Chute per pole fixed in existing panel including all connection complete all as directed. |
| 24 | Supply, fix, connecting andtesting in repairMCCB 200 Amp 3 pole 36 KA 415 volts 50 Hz adjustablethermal & adjustable magnetic release with spreader,MCCB shall have double make, double break with Arc Chute per pole fixed in existing panel including all connection complete all as directed. |
| 25 | Supply, fix, connecting andtesting in repairMCCB 250 Amp 3 pole 36 KA 415 volts 50 Hz adjustablethermal & adjustable magnetic release with spreader,MCCB shall have double make, double break with Arc Chute per pole fixed in existing panel including all connection complete all as directed. |
| 26 | Supply, fix, connecting andtesting in repairMCCB 400 Amp 3 pole 36 KA 415 volts 50 Hz adjustablethermal & adjustable magnetic release with spreader,MCCB shall have double make, double break with Arc Chute per pole fixed in existing panel including all connection complete all as directed. |
| 27 | Supply and install steel tubular swaged pole type 410 SP-31 (9 metre long) complete with MS base plate of size 300 x 300 x 6mm thick at bottom, welded at the centre with through hole of 14 mm dia at a height of 300 mm above the coping finial cap, painted with two coats of aluminium paint over a coat of red oxide primer with writing pole number including excavation up to required depth and PCC type C-2 1:3:6 (using 40mm graded) at bottom and PCC type B-1 1:2:4 (20mm graded) for mass filling and pole coping (60 x 60 x 30 cm) and rendering of coping with 05 mm thick in 1:4 cement mortar, including painting up to 1.5 metre above PCC coping in black and white strips 05 Nos each 30 cm high starting from bottom of pole & Marking number on pole with black paint, including taking down old pole complete all as specified and directed. |
| 28 | M&L Earthing complete with galvanised mild steel earth plate electrode 600x600x6.0mm thick, buried directly in ground to a depth not less than 2.25 metres deep below ground level with top edge of earth plate not less than 1.5 metre below normal ground level surrounded with adequate quantity of charcoal dust mixed with salt to a packed thickness of 15 cm all around the plate, using GI strip 32 x 6 mm as earth strip electrode bolted or rivetted to earth plate at one end and connected to equipment\"s at another end, GI earth strip encased inand including 40 mm dia GI \"lightgrade\" pipe from upper end of earth plate up to equipments,20 dia bore GI pipe \"light grade\" as water pipe from earth chamber to upper edge of earth plate, Test point , GI funnel with wire mesh fixed on water pipe andPCC 1:2:4 type B-1 (using 20mm graded stone aggregate) as in pit chamber and RCC pit cover 50mm thick precast RCC 1:2:4 type B-1, duly reinforced with MS TMT bars 8mm dia @ 100 c/c both ways with 10mm dia MS round bar as in lifting handles, excavation, earth work including laying the GI pipe concealed in floor/wall all as describedin electric plate of SSR Part I complete. |
| 29 | Note :- Ifthe desired earth resistance is not found, earthing shall be redone by the contractor at no extra cost to the department. |
| 30 | Supply and laying or fixing HDPE Double wall corrugated pipe 40 mm outer dia & 32 mm inner dia along with all accessories like socket, couplers etc, ISI marked as per IS-16205 (Part-24), including cutting / jointing and laid in trenches, fixed to walls, floor etc. for cable protection complete all as specified & directed. |
| 31 | Supply and laying or fixing HDPE Double wall corrugated pipe 50 mm outer dia & 38 mm inner dia along with all accessories like socket, couplers etc, ISI marked as per IS-16205 (Part-24), including cutting / jointing and laid in trenches, fixed to walls, floor etc. for cable protection complete all as specified & directed. |
| 32 | Supply and laying or fixing HDPE Double wall corrugated pipe 77 mm outer dia & 63 mm inner dia along with all accessories like socket, couplers etc, ISI marked as per IS-16205 (Part-24), including cutting / jointing and laid in trenches, fixed to walls, floor etc. for cable protection complete all as specified & directed. |
| 33 | Supply and laying or fixing HDPE Double wall corrugated pipe 110 mm outer dia & 95 mm inner dia along with all accessories like socket, couplers etc, ISI marked as per IS-16205 (Part-24), including cutting / jointing and laid in trenches, fixed to walls, floor etc. for cable protection complete all as specified & directed. |
| 34 | Supply and laying or fixing HDPE Double wall corrugated pipe 120 mm outer dia & 103 mm inner dia along with all accessories like socket, couplers etc, ISI marked as per IS-16205 (Part-24), including cutting / jointing and laid in trenches, fixed to walls, floor etc. for cable protection complete all as specified & directed. |
| 35 | M& L for fabrication and fixing canopy headed junction box of size 30 x 25 x 15 cm with cover, suitable for fixing on LT Pole, made out 3.00 mm MS sheet, including 04 Nos aluminium bus bar of size 25 x 3 mm for phase and neutral, 01 Nos 06 Amps MCB SP with mounting channel, for control street light, cable gland, aluminium lug, MS Fixing clamp -02 Nos with nut bolt washer, painting with two coat of synthetic enamel paint over a coat of red oxide primer on external and internal surface complete |
| 36 | Supplying and fixing in replacement10 Watt LED cool white / warm white bollard light fitting of 1 meter heightnew generation , energy saving , environmental friendly , long life aesthetically designed aluminium landscape IP 65 luminaire for diffused lighting with high power LED as light source housing made up of aluminium pipe UV protected pure polyester powder coated black after phosphocreatine treatmentit consists of aluminium heat sink for effective thermal management , sturdiness & excellent corrosion resistantmounting flange of MS sand casting is used at bottomPC diffuser in opal finish is used for glare free uniform light distribution powered by built in , isolated , potted electronic LED driver in ABS housing with APFC (SMPS based constant current supply) with lower THD , output short/open circuit protection , over voltage protection , Surge voltage protectionLumen efficiency not less than 80 lumen per wattsystem efficiency ,power factor >0.95, THD<10% at Full load CRI> 70% |
| 37 | Supply and fix in replacement 15 WattLEDPost Toplanterns housing made of Die-cast aluminium spigot for mounting LED driver and spun aluminium canopy , epoxy powder coated matt black finish after phosphocreatine treatment , high quality polycarbonate cover is used over LED module to enhance the lumen output & clear acrylic diffuser is used to provide overall glare free light white/warm white, Powered by electronic integral , isolated potted electronic LED driver in ABS housing with APFC (SMPS based constant current supply) with lower THD , output short/open circuit protection , Surge Voltage protection & other safety test as per IS 15885 Part-2/Sec-13 , IP 65 ,Lumen efficiency not less than 98 lumen per wattsystem efficiency ,power factor >0.95, THD<10% at Full load CRI> 70% |
| 38 | Supply, installation, testing and commissioning outdoor cubical type MV Panel board design verified with switchgear and control gear assemblies as per IS / IEC-61439 (Part - 1 & 2) of 2020 suitable for 415 V, 3 phase, 4 wire 50 Hz supply system fabricated from 3 mm thick CRCA sheet, overall powder coated (RAL 7032 shade), dust, weather & vermin proof, degree of ingress protection IP-54 having TPN busbar supported on SMC insulators with short circuit withstand capacity 35 MVA for 1 second, bottom base channel of MS section not less than 100 mm x 50 mm x 5 mm thick, entire panel shall have a common copper earth bar of size 25 mm x 3 mm at the rear with 2 Nos earth stud, solid connections from main bus bar to switch gears with required size of bus bars and control wiring with min 1.5 sqmm PVC insulated copper conductor cable, cable alleys, cable gland plates in two half, phase indication lamps mounted on suitable PCC foundation with following controls:- |
| 39 | (a) Incomer (a)MCCB 4 pole, 320 Amp, 36 KA (Icu=Ics) thermally adjustable between 70% to 100%.- 02 Nos(b)On load Change Over of capacity 320 Amps - 01 No(c) Voltmeter with selector switch of range 0-500V - 01 No (d) Ammeter with selector switch of range 0-500 Amps - 01 No(e) Indicators lamps - 01 Set of three(f) CT/PTs of suitable range - 01 No(g) TPN Aluminium bus bar with colour code insulated of capacity 400 Amps |
| 40 | (b) Out going(a) MCCB FP 250 Amps, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 01 No(b) MCCB FP 160 Amp, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 01 No(c) MCCBFP 100 Amp, 25 KA (Icu=Ics) thermally adjustable between 70% to 100% - 02 NosNote for MCCB : All incoming & outgoing MCCB shall have double make, double break with Arc Chute per pole. |
| 41 | (c) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class \"B\", old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel.The hight of platform shall be 45 cm above the nearest road level. |
| 42 | Note - (i) Following type test certificate for panel with switchgear as per IEC 61439 Part I & II shall be obtained from panel manufacturer by the contractor and shall be submitted along with panel Drawing for the approval the GE before supply of panel at site.A - Construction Requirement:(a) Strength of material and parts(b) Degree of protection of enclosures(c) Clearances(d) Creepage distances(e) Protection against electric shock and integrity of protective circuits(f)Incorporation of switching devices and components(g) Internal electrical circuits and connections(h) Terminals for external conductorsB - Performance Requirement:(a) Di-electric properties(b) Verification of temperature rise(c) Short circuit withstand strength(d) Electromagnetic compatibility(e) Mechanical operations |
| 43 | Note (ii) All out going feeder shall be connected by cable through suitable size gland plate / glands. (iii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iv) All MCCBwithadjustable protection for over load and short circuit and conforming to IEC60947-II/IS 13947-II (Latest Version). The MCCB should have Ics=100%Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacturer (v) The enclosures shall be designed to take care of normal stress as well as abnormal electromechanical stress due to short circuit conditions. All covers and doors provided shall offer adequate safety to operating persons and provide ingress protection up to IP 54 unless otherwise stated. Ventilating openings and vent outlets, shall be arranged such that same ingress protection of IP 54 is retained. Suitable pressure relief devices shall be provided to minimize danger to operator during internal fault conditions.(vi) MCCBs up to 160A should have operating voltage 415Vac , insulation voltage 1000V ac , positive isolation , class II insulation , Line Load Reversibility , ICS=100%ICU , ROHS Compliant. |
| 44 | Supply, installation, testing and commissioning outdoor cubical type MV Panel board design verified with switchgear and control gear assemblies as per IS / IEC-61439 (Part - 1 & 2) of 2020 suitable for 415 V, 3 phase, 4 wire 50 Hz supply system fabricated from 3 mm thick CRCA sheet, overall powder coated (RAL 7032 shade), dust, weather & vermin proof, degree of ingress protection IP-54 having TPN busbar supported on SMC insulators with short circuit withstand capacity 35 MVA for 1 second, bottom base channel of MS section not less than 100 mm x 50 mm x 5 mm thick, entire panel shall have a common copper earth bar of size 25 mm x 3 mm at the rear with 2 Nos earth stud, solid connections from main bus bar to switch gears with required size of bus bars and control wiring with min 1.5 sqmm PVC insulated copper conductor cable, cable alleys, cable gland plates in two half, phase indication lamps mounted on suitable PCC foundation with following controls:- |
| 45 | (a) Incomer (a) MCCB 4 pole, 400 Amp, 36 KA (Icu=Ics) thermally adjustable between 70% to 100%.- 02 Nos(b) On load Change Over of capacity 400 Amps - 01 No(c) Voltmeter with selector switch of range 0-500V - 01 No(d) Ammeter with selector switch of range 0-500 Amps - 01 No(e) Indicators lamps - 01 Set of three(f) CT/PTs of suitable range - 01 No(g) TPN Aluminium bus bar with colour code insulated of capacity 400 Amps |
| 46 | (b) Out going(a) MCCB FP 250 Amps, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 03 Nos(b) MCCB FP 160 Amp, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 01 No(c) MCCBFP 100 Amp, 25 KA (Icu=Ics) thermally adjustable between 70% to 100% - 01 NoNote for MCCB : All incoming & outgoing MCCB shall have double make, double break with Arc Chute per pole. |
| 47 | (c) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class \"B\", old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel.The hight of platform shall be 45 cm above the nearest road level. |
| 48 | Note - (i) Following type test certificate for panel with switchgear as per IEC 61439 Part I & II shall be obtained from panel manufacturer by the contractor and shall be submitted along with panel Drawing for the approval the GE before supply of panel at site.A - Construction Requirement:(a) Strength of material and parts(b) Degree of protection of enclosures(c) Clearances(d) Creepage distances(e) Protection against electric shock and integrity of protective circuits(f)Incorporation of switching devices and components(g) Internal electrical circuits and connections(h) Terminals for external conductorsB - Performance Requirement:(a) Di-electric properties(b) Verification of temperature rise(c) Short circuit withstand strength(d) Electromagnetic compatibility(e) Mechanical operations |
| 49 | Note (ii) All out going feeder shall be connected by cable through suitable size gland plate / glands. (iii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iv) All MCCBwithadjustable protection for over load and short circuit and conforming to IEC60947-II/IS 13947-II (Latest Version). The MCCB should have Ics=100%Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacturer (v) The enclosures shall be designed to take care of normal stress as well as abnormal electromechanical stress due to short circuit conditions. All covers and doors provided shall offer adequate safety to operating persons and provide ingress protection up to IP 54 unless otherwise stated. Ventilating openings and vent outlets, shall be arranged such that same ingress protection of IP 54 is retained. Suitable pressure relief devices shall be provided to minimize danger to operator during internal fault conditions.(vi) MCCBs up to 160A should have operating voltage 415Vac , insulation voltage 1000V ac , positive isolation , class II insulation , Line Load Reversibility , ICS=100%ICU , ROHS Compliant. |
| 50 | Supply, installation, testing and commissioning outdoor cubical type MV Panel board design verified with switchgear and control gear assemblies as per IS / IEC-61439 (Part - 1 & 2) of 2020 suitable for 415 V, 3 phase, 4 wire 50 Hz supply system fabricated from 3 mm thick CRCA sheet, overall powder coated (RAL 7032 shade), dust, weather & vermin proof, degree of ingress protection IP-54 having TPN busbar supported on SMC insulators with short circuit withstand capacity 35 MVA for 1 second, bottom base channel of MS section not less than 100 mm x 50 mm x 5 mm thick, entire panel shall have a common copper earth bar of size 25 mm x 3 mm at the rear with 2 Nos earth stud, solid connections from main bus bar to switch gears with required size of bus bars and control wiring with min 1.5 sqmm PVC insulated copper conductor cable, cable alleys, cable gland plates in two half, phase indication lamps mounted on suitable PCC foundation with following controls:- |
| 51 | (a) Incomer (a) On load Change Over of capacity 400 Amps - 02 Nos(b) Voltmeter with selector switch of range 0-500V - 01 No(c) Ammeter with selector switch of range 0-500Amps - 01 No(d) Indicators lamps - 01 Set of three(e) CT/PTs of suitable range - 01 No(f) TPN Aluminium bus bar with colour code insulated of capacity 500 Amps |
| 52 | (b) Out going(a) MCCB FP 400 Amps, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 01 Nos (b) MCCB FP 160 Amp, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 02 NoNote for MCCB : All incoming & outgoing MCCB shall have double make, double break with Arc Chute per pole. |
| 53 | (c) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class \"B\", old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel.The hight of platform shall be 45 cm above the nearest road level. |
| 54 | Note - (i) Following type test certificate for panel with switchgear as per IEC 61439 Part I & II shall be obtained from panel manufacturer by the contractor and shall be submitted along with panel Drawing for the approval the GE before supply of panel at site.A - Construction Requirement:(a) Strength of material and parts(b) Degree of protection of enclosures(c) Clearances(d) Creepage distances(e) Protection against electric shock and integrity of protective circuits(f)Incorporation of switching devices and components(g) Internal electrical circuits and connections(h) Terminals for external conductorsB - Performance Requirement:(a) Di-electric properties(b) Verification of temperature rise(c) Short circuit withstand strength(d) Electromagnetic compatibility(e) Mechanical operations |
| 55 | Note (ii) All out going feeder shall be connected by cable through suitable size gland plate / glands. (iii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iv) All MCCBwithadjustable protection for over load and short circuit and conforming to IEC60947-II/IS 13947-II (Latest Version). The MCCB should have Ics=100%Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacturer (v) The enclosures shall be designed to take care of normal stress as well as abnormal electromechanical stress due to short circuit conditions. All covers and doors provided shall offer adequate safety to operating persons and provide ingress protection up to IP 54 unless otherwise stated. Ventilating openings and vent outlets, shall be arranged such that same ingress protection of IP 54 is retained. Suitable pressure relief devices shall be provided to minimize danger to operator during internal fault conditions.(vi) MCCBs up to 160A should have operating voltage 415Vac , insulation voltage 1000V ac , positive isolation , class II insulation , Line Load Reversibility , ICS=100%ICU , ROHS Compliant. |
| 56 | Supply, installation, testing and commissioning outdoor cubical type MV Panel board design verified with switchgear and control gear assemblies as per IS / IEC-61439 (Part - 1 & 2) of 2020 suitable for 415 V, 3 phase, 4 wire 50 Hz supply system fabricated from 3 mm thick CRCA sheet, overall powder coated (RAL 7032 shade), dust, weather & vermin proof, degree of ingress protection IP-54 having TPN busbar supported on SMC insulators with short circuit withstand capacity 35 MVA for 1 second, bottom base channel of MS section not less than 100 mm x 50 mm x 5 mm thick, entire panel shall have a common copper earth bar of size 25 mm x 3 mm at the rear with 2 Nos earth stud, solid connections from main bus bar to switch gears with required size of bus bars and control wiring with min 1.5 sqmm PVC insulated copper conductor cable, cable alleys, cable gland plates in two half, phase indication lamps mounted on suitable PCC foundation with following controls:- |
| 57 | (a) Incomer (a)MCCB 4 pole, 200 Amp, 36 KA (Icu=Ics) thermally adjustable between 70% to 100%.- 02 Nos(b)On load Change Over of capacity 200 Amps - 01 No(c) Voltmeter with selector switch of range 0-500V - 01 No(d) Ammeter with selector switch of range 0-500 Amps - 01 No(e) Indicators lamps - 01 Set of three(f) CT/PTs of suitable range - 01 No(g) TPN Aluminium bus bar with colour code insulated of capacity 400 Amps |
| 58 | (b) Out going(a) MCCB FP 160 Amps, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 02 Nos(b) MCCB FP 100 Amp, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 01 NoNote for MCCB : All incoming & outgoing MCCB shall have double make, double break with Arc Chute per pole. |
| 59 | (c) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class \"B\", old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel.The hight of platform shall be 45 cm above the nearest road level. |
| 60 | Note - (i) Following type test certificate for panel with switchgear as per IEC 61439 Part I & II shall be obtained from panel manufacturer by the contractor and shall be submitted along with panel Drawing for the approval the GE before supply of panel at site.A - Construction Requirement:(a) Strength of material and parts(b) Degree of protection of enclosures(c) Clearances(d) Creepage distances(e) Protection against electric shock and integrity of protective circuits(f)Incorporation of switching devices and components(g) Internal electrical circuits and connections(h) Terminals for external conductorsB - Performance Requirement:(a) Di-electric properties(b) Verification of temperature rise(c) Short circuit withstand strength(d) Electromagnetic compatibility(e) Mechanical operations |
| 61 | Note (ii) All out going feeder shall be connected by cable through suitable size gland plate / glands. (iii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iv) All MCCBwithadjustable protection for over load and short circuit and conforming to IEC60947-II/IS 13947-II (Latest Version). The MCCB should have Ics=100%Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacturer (v) The enclosures shall be designed to take care of normal stress as well as abnormal electromechanical stress due to short circuit conditions. All covers and doors provided shall offer adequate safety to operating persons and provide ingress protection up to IP 54 unless otherwise stated. Ventilating openings and vent outlets, shall be arranged such that same ingress protection of IP 54 is retained. Suitable pressure relief devices shall be provided to minimize danger to operator during internal fault conditions.(vi) MCCBs up to 160A should have operating voltage 415Vac , insulation voltage 1000V ac , positive isolation , class II insulation , Line Load Reversibility , ICS=100%ICU , ROHS Compliant. |
| 62 | Supply, installation, testing and commissioning outdoor cubical type MV Panel board design verified with switchgear and control gear assemblies as per IS / IEC-61439 (Part - 1 & 2) of 2020 suitable for 415 V, 3 phase, 4 wire 50 Hz supply system fabricated from 3 mm thick CRCA sheet, overall powder coated (RAL 7032 shade), dust, weather & vermin proof, degree of ingress protection IP-54 having TPN busbar supported on SMC insulators with short circuit withstand capacity 35 MVA for 1 second, bottom base channel of MS section not less than 100 mm x 50 mm x 5 mm thick, entire panel shall have a common copper earth bar of size 25 mm x 3 mm at the rear with 2 Nos earth stud, solid connections from main bus bar to switch gears with required size of bus bars and control wiring with min 1.5 sqmm PVC insulated copper conductor cable, cable alleys, cable gland plates in two half, phase indication lamps mounted on suitable PCC foundation with following controls:- |
| 63 | (a) Incomer (a)MCCB 4 pole, 250 Amp, 36 KA (Icu=Ics) thermally adjustable between 70% to 100%.- 02 Nos (b)On load Change Over of capacity 200 Amps - 01 No(c) Voltmeter with selector switch of range 0-500V - 01 No(d) Ammeter with selector switch of range 0-500Amps - 01 No(e) Indicators lamps - 01 Set of three(f) CT/PTs of suitable range - 01 No (g) TPN Aluminium bus bar with colour code insulated of capacity 400 Amps |
| 64 | (b) Out going(a) MCCB FP 160 Amps, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 02 Nos (b) MCCB FP 100 Amp, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 02 NosNote for MCCB : All incoming & outgoing MCCB shall have double make, double break with Arc Chute per pole. |
| 65 | (c) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class \"B\", old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel.The hight of platform shall be 45 cm above the nearest road level. |
| 66 | Note - (i) Following type test certificate for panel with switchgear as per IEC 61439 Part I & II shall be obtained from panel manufacturer by the contractor and shall be submitted along with panel Drawing for the approval the GE before supply of panel at site.A - Construction Requirement:(a) Strength of material and parts(b) Degree of protection of enclosures(c) Clearances(d) Creepage distances(e) Protection against electric shock and integrity of protective circuits(f)Incorporation of switching devices and components(g) Internal electrical circuits and connections(h) Terminals for external conductorsB - Performance Requirement:(a) Di-electric properties(b) Verification of temperature rise(c) Short circuit withstand strength(d) Electromagnetic compatibility(e) Mechanical operations |
| 67 | Note (ii) All out going feeder shall be connected by cable through suitable size gland plate / glands. (iii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iv) All MCCBwithadjustable protection for over load and short circuit and conforming to IEC60947-II/IS 13947-II (Latest Version). The MCCB should have Ics=100%Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacturer (v) The enclosures shall be designed to take care of normal stress as well as abnormal electromechanical stress due to short circuit conditions. All covers and doors provided shall offer adequate safety to operating persons and provide ingress protection up to IP 54 unless otherwise stated. Ventilating openings and vent outlets, shall be arranged such that same ingress protection of IP 54 is retained. Suitable pressure relief devices shall be provided to minimize danger to operator during internal fault conditions.(vi) MCCBs up to 160A should have operating voltage 415Vac , insulation voltage 1000V ac , positive isolation , class II insulation , Line Load Reversibility , ICS=100%ICU , ROHS Compliant. |
| 68 | Supply, installation, testing and commissioning outdoor cubical type MV Panel board design verified with switchgear and control gear assemblies as per IS / IEC-61439 (Part - 1 & 2) of 2020 suitable for 415 V, 3 phase, 4 wire 50 Hz supply system fabricated from 3 mm thick CRCA sheet, overall powder coated (RAL 7032 shade), dust, weather & vermin proof, degree of ingress protection IP-54 having TPN busbar supported on SMC insulators with short circuit withstand capacity 35 MVA for 1 second, bottom base channel of MS section not less than 100 mm x 50 mm x 5 mm thick, entire panel shall have a common copper earth bar of size 25 mm x 3 mm at the rear with 2 Nos earth stud, solid connections from main bus bar to switch gears with required size of bus bars and control wiring with min 1.5 sqmm PVC insulated copper conductor cable, cable alleys, cable gland plates in two half, phase indication lamps mounted on suitable PCC foundation with following controls:- |
| 69 | (a) Incomer (a)MCCB 4 pole, 400 Amp, 36 KA (Icu=Ics) thermally adjustable between 70% to 100%.- 02 Nos(b)On load Change Over of capacity 400 Amps - 01 No(c) Voltmeter with selector switch of range 0-500V - 01 No(d) Ammeter with selector switch of range 0-500 Amps - 01 No(e) Indicators lamps - 01 Set of three(f) CT/PTs of suitable range - 01 No(g) TPN Aluminium bus bar with colour code insulated of capacity 400 Amps |
| 70 | (b) Out going(a) MCCB FP 250 Amps, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 01 Nos(b) MCCB FP 160 Amp, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 02 Nos(c) MCCB FP 100 Amp, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 01 NosNote for MCCB : All incoming & outgoing MCCB shall have double make, double break with Arc Chute per pole. |
| 71 | (c) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class \"B\", old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel.The hight of platform shall be 45 cm above the nearest road level. |
| 72 | Note - (i) Following type test certificate for panel with switchgear as per IEC 61439 Part I & II shall be obtained from panel manufacturer by the contractor and shall be submitted along with panel Drawing for the approval the GE before supply of panel at site.A - Construction Requirement:(a) Strength of material and parts(b) Degree of protection of enclosures(c) Clearances(d) Creepage distances(e) Protection against electric shock and integrity of protective circuits(f)Incorporation of switching devices and components(g) Internal electrical circuits and connections(h) Terminals for external conductorsB - Performance Requirement:(a) Di-electric properties(b) Verification of temperature rise(c) Short circuit withstand strength(d) Electromagnetic compatibility(e) Mechanical operations |
| 73 | Note (ii) All out going feeder shall be connected by cable through suitable size gland plate / glands. (iii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iv) All MCCBwithadjustable protection for over load and short circuit and conforming to IEC60947-II/IS 13947-II (Latest Version). The MCCB should have Ics=100%Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacturer (v) The enclosures shall be designed to take care of normal stress as well as abnormal electromechanical stress due to short circuit conditions. All covers and doors provided shall offer adequate safety to operating persons and provide ingress protection up to IP 54 unless otherwise stated. Ventilating openings and vent outlets, shall be arranged such that same ingress protection of IP 54 is retained. Suitable pressure relief devices shall be provided to minimize danger to operator during internal fault conditions.(vi) MCCBs up to 160A should have operating voltage 415Vac , insulation voltage 1000V ac , positive isolation , class II insulation , Line Load Reversibility , ICS=100%ICU , ROHS Compliant. |
| 74 | Supply, installation, testing and commissioning outdoor cubical type MV Panel board design verified with switchgear and control gear assemblies as per IS / IEC-61439 (Part - 1 & 2) of 2020 suitable for 415 V, 3 phase, 4 wire 50 Hz supply system fabricated from 3 mm thick CRCA sheet, overall powder coated (RAL 7032 shade), dust, weather & vermin proof, degree of ingress protection IP-54 having TPN busbar supported on SMC insulators with short circuit withstand capacity 35 MVA for 1 second, bottom base channel of MS section not less than 100 mm x 50 mm x 5 mm thick, entire panel shall have a common copper earth bar of size 25 mm x 3 mm at the rear with 2 Nos earth stud, solid connections from main bus bar to switch gears with required size of bus bars and control wiring with min 1.5 sqmm PVC insulated copper conductor cable, cable alleys, cable gland plates in two half, phase indication lamps mounted on suitable PCC foundation with following controls:- |
| 75 | (a) Incomer (a)MCCB 4 pole, 320 Amp, 36 KA (Icu=Ics) thermally adjustable between 70% to 100%.- 01 Nos(b)Voltmeter with selector switch of range 0-500V - 01 No(c)Ammeter with selector switch of range 0-500 Amps - 01 No(d)Indicators lamps - 01 Set of three(e)CT/PTs of suitable range - 01 No(f)TPN Aluminium bus bar with colour code insulated of capacity 400 Amps |
| 76 | (b) Out going(a) MCCB FP 200 Amps, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 01 Nos(b) MCCB FP 160 Amp, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 01 Nos(c) MCCB FP 100 Amp, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 03 NosNote for MCCB : All incoming & outgoing MCCB shall have double make, double break with Arc Chute per pole. |
| 77 | (c) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class \"B\", old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel.The hight of platform shall be 45 cm above the nearest road level. |
| 78 | Note - (i) Following type test certificate for panel with switchgear as per IEC 61439 Part I & II shall be obtained from panel manufacturer by the contractor and shall be submitted along with panel Drawing for the approval the GE before supply of panel at site.A - Construction Requirement:(a) Strength of material and parts(b) Degree of protection of enclosures(c) Clearances(d) Creepage distances(e) Protection against electric shock and integrity of protective circuits(f)Incorporation of switching devices and components(g) Internal electrical circuits and connections(h) Terminals for external conductorsB - Performance Requirement:(a) Di-electric properties(b) Verification of temperature rise(c) Short circuit withstand strength(d) Electromagnetic compatibility(e) Mechanical operations |
| 79 | Note (ii) All out going feeder shall be connected by cable through suitable size gland plate / glands. (iii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iv) All MCCBwithadjustable protection for over load and short circuit and conforming to IEC60947-II/IS 13947-II (Latest Version). The MCCB should have Ics=100%Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacturer (v) The enclosures shall be designed to take care of normal stress as well as abnormal electromechanical stress due to short circuit conditions. All covers and doors provided shall offer adequate safety to operating persons and provide ingress protection up to IP 54 unless otherwise stated. Ventilating openings and vent outlets, shall be arranged such that same ingress protection of IP 54 is retained. Suitable pressure relief devices shall be provided to minimize danger to operator during internal fault conditions.(vi) MCCBs up to 160A should have operating voltage 415Vac , insulation voltage 1000V ac , positive isolation , class II insulation , Line Load Reversibility , ICS=100%ICU , ROHS Compliant. |
| 80 | Supply, installation, testing and commissioning outdoor cubical type MV Panel board design verified with switchgear and control gear assemblies as per IS / IEC-61439 (Part - 1 & 2) of 2020 suitable for 415 V, 3 phase, 4 wire 50 Hz supply system fabricated from 3 mm thick CRCA sheet, overall powder coated (RAL 7032 shade), dust, weather & vermin proof, degree of ingress protection IP-54 having TPN busbar supported on SMC insulators with short circuit withstand capacity 35 MVA for 1 second, bottom base channel of MS section not less than 100 mm x 50 mm x 5 mm thick, entire panel shall have a common copper earth bar of size 25 mm x 3 mm at the rear with 2 Nos earth stud, solid connections from main bus bar to switch gears with required size of bus bars and control wiring with min 1.5 sqmm PVC insulated copper conductor cable, cable alleys, cable gland plates in two half, phase indication lamps mounted on suitable PCC foundation with following controls:- |
| 81 | (a) Incomer (a)MCCB 4 pole, 250 Amp, 36 KA (Icu=Ics) thermally adjustable between 70% to 100%.- 01 Nos(b)Voltmeter with selector switch of range 0-500V - 01 No(c)Ammeter with selector switch of range 0-500Amps - 01 No(d)Indicators lamps - 01 Set of three(e)CT/PTs of suitable range - 01 No(f)TPN Aluminium bus bar with colour code insulated of capacity 400 Amps |
| 82 | (b) Out going(a) MCCB FP 200 Amps, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 01 Nos (b) MCCB FP 160 Amp, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 02 Nos(c) MCCB FP 100 Amp, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 02 Nos(d) MCCB FP 63 Amp, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 01 NosNote for MCCB : All incoming & outgoing MCCB shall have double make, double break with Arc Chute per pole. |
| 83 | (c) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class \"B\", old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel.The hight of platform shall be 45 cm above the nearest road level. |
| 84 | Note - (i) Following type test certificate for panel with switchgear as per IEC 61439 Part I & II shall be obtained from panel manufacturer by the contractor and shall be submitted along with panel Drawing for the approval the GE before supply of panel at site.A - Construction Requirement:(a) Strength of material and parts(b) Degree of protection of enclosures(c) Clearances(d) Creepage distances(e) Protection against electric shock and integrity of protective circuits(f)Incorporation of switching devices and components(g) Internal electrical circuits and connections(h) Terminals for external conductorsB - Performance Requirement:(a) Di-electric properties(b) Verification of temperature rise(c) Short circuit withstand strength(d) Electromagnetic compatibility(e) Mechanical operations |
| 85 | Note (ii) All out going feeder shall be connected by cable through suitable size gland plate / glands. (iii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iv) All MCCBwithadjustable protection for over load and short circuit and conforming to IEC60947-II/IS 13947-II (Latest Version). The MCCB should have Ics=100%Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacturer (v) The enclosures shall be designed to take care of normal stress as well as abnormal electromechanical stress due to short circuit conditions. All covers and doors provided shall offer adequate safety to operating persons and provide ingress protection up to IP 54 unless otherwise stated. Ventilating openings and vent outlets, shall be arranged such that same ingress protection of IP 54 is retained. Suitable pressure relief devices shall be provided to minimize danger to operator during internal fault conditions.(vi) MCCBs up to 160A should have operating voltage 415Vac , insulation voltage 1000V ac , positive isolation , class II insulation , Line Load Reversibility , ICS=100%ICU , ROHS Compliant. |
| 86 | Supply, installation, testing and commissioning outdoor cubical type MV Panel board design verified with switchgear and control gear assemblies as per IS / IEC-61439 (Part - 1 & 2) of 2020 suitable for 415 V, 3 phase, 4 wire 50 Hz supply system fabricated from 3 mm thick CRCA sheet, overall powder coated (RAL 7032 shade), dust, weather & vermin proof, degree of ingress protection IP-54 having TPN busbar supported on SMC insulators with short circuit withstand capacity 35 MVA for 1 second, bottom base channel of MS section not less than 100 mm x 50 mm x 5 mm thick, entire panel shall have a common copper earth bar of size 25 mm x 3 mm at the rear with 2 Nos earth stud, solid connections from main bus bar to switch gears with required size of bus bars and control wiring with min 1.5 sqmm PVC insulated copper conductor cable, cable alleys, cable gland plates in two half, phase indication lamps mounted on suitable PCC foundation with following controls:- |
| 87 | (a) Incomer (a)MCCB 4 Pole 200 Amp, 36 KA (Icu=Ics) thermally adjustable between 70% to 100%.- 02 Nos(b)On load Change Over of capacity 160 Amps - 02 Nos(c) Voltmeter with selector switch of range 0-500V - 01 No(d) Ammeter with selector switch of range 0-500Amps - 01 No(e) Indicators lamps - 01 Set of three(f) CT/PTs of suitable range - 01 No(g) TPN Aluminium bus bar with colour code insulated of capacity 250 Amps |
| 88 | (b) Out going (a) MCCB FP 160 Amps, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 02 Nos (b) MCCB FP 125 Amp, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 02 Nos(c) MCCB FP 63 Amp, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 02 NosNote for MCCB : All incoming & outgoing MCCB shall have double make, double break with Arc Chute per pole. |
| 89 | (c) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class \"B\", old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel.The hight of platform shall be 45 cm above the nearest road level. |
| 90 | Note - (i) Following type test certificate for panel with switchgear as per IEC 61439 Part I & II shall be obtained from panel manufacturer by the contractor and shall be submitted along with panel Drawing for the approval the GE before supply of panel at site.A - Construction Requirement:(a) Strength of material and parts(b) Degree of protection of enclosures(c) Clearances(d) Creepage distances(e) Protection against electric shock and integrity of protective circuits(f)Incorporation of switching devices and components(g) Internal electrical circuits and connections(h) Terminals for external conductorsB - Performance Requirement:(a) Di-electric properties(b) Verification of temperature rise(c) Short circuit withstand strength(d) Electromagnetic compatibility(e) Mechanical operations |
| 91 | Note (ii) All out going feeder shall be connected by cable through suitable size gland plate / glands. (iii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iv) All MCCBwithadjustable protection for over load and short circuit and conforming to IEC60947-II/IS 13947-II (Latest Version). The MCCB should have Ics=100%Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacturer (v) The enclosures shall be designed to take care of normal stress as well as abnormal electromechanical stress due to short circuit conditions. All covers and doors provided shall offer adequate safety to operating persons and provide ingress protection up to IP 54 unless otherwise stated. Ventilating openings and vent outlets, shall be arranged such that same ingress protection of IP 54 is retained. Suitable pressure relief devices shall be provided to minimize danger to operator during internal fault conditions.(vi) MCCBs up to 160A should have operating voltage 415Vac , insulation voltage 1000V ac , positive isolation , class II insulation , Line Load Reversibility , ICS=100%ICU , ROHS Compliant. |
| 92 | M&L for Preparation of old painted surfaces of LT steel tubular pole 9 mitres long and applying one coat aluminium paint from bottom to top and painting up to 1.5 metre height from top of PCC coping with synthetic enamel paint one coat in black and Yellow / white alternate strip including re writing pole numbering in 8 cm height with stencil with one coat synthetic enamel paint complete all as specified & directed byEngineer –in-Charge. |
| 93 | Material and labour for rewriting of Pole Nos on existing pole with stencil out with white colour in BLACK background of 80 mm height around the radius of pole complete. |
| 94 | M&L for Preparation of old painted surfaces of LT panel by scrapping, making good disturbed surfaces by applying putties on uneven surface to make it even and spray painting to LT panel of any size with two coat of synthetic enamel paint with desired colour complete all as specified and directed. |
| 95 | Supply, fix, connecting andtesting in repairMCCB 100 Amp 4 pole 16 KA 415 volts 50 Hz adjustablethermal & adjustable magnetic release with spreader,MCCB shall have double make, double break with Arc Chute per pole fixed in existing panel including all connection complete all as directed. |
| 96 | Supply, fix, connecting andtesting in repairMCCB 125 Amp 4 pole 16 KA 415 volts 50 Hz adjustablethermal & adjustable magnetic release with spreader,MCCB shall have double make, double break with Arc Chute per pole fixed in existing panel including all connection complete all as directed. |
| 97 | S&F Offload change over switch, 200 Amps, 415 volts, 4 pole in sheet metal enclosure conforming to IS:13947 (Part-3); IEC:60947-3 with locking facility including all connecting / jointing materials and dismantling of existing change over switch, complete. |
| 98 | S&F off load change over switch, 63 Amps, 415 volts, 4 pole side handle typein sheet metal enclosure conforming to IS:13947 (Part-3); IEC:60947-3 with locking facility including all connecting / jointing materials and dismantling of existing change over switch, complete |
| 99 | S&F Off load change over switch (side operated handle) 400 Amps, 415 volts 4 pole in sheet metal enclosure with interlock door and pad lock facility including dismantling of existing change over switch, complete |
| 100 | Supply & fixing in replacementautomatic street light timer panel 6 KW TP switch using Infrared Sensor basedfor automatic switching of street lights based on LUX level of natural light. Required illuminance for switching ON is < 30 Lux and for switching OFF > 10 Lux level. The sensor (nature switch) along with suitable power contactors, Input (supply) MCB and output (load) MCB(s), support terminals should be enclosed in pole/ wall mountable enclosure made of rust proof, electric shock proof, termite proof and FR graded SMC junction box conforming to IP-54 degree of ingress three phase 6 KW lightening load capacity including mounting bracket, cable glands, openable doors with lock complete all as specified & directed by Engr-in-Charge. |
| 101 | Deployment of manpower / tools / machinery etc for restringing of existingloose over head line having 4 run ACSR conductor and 01 Nos GI wire any size / type etc of existing LT pole including repair of aluminium binding wire or suitable size carefully without damaging of insulator etc. complete all as specified and as directed by Engineer-in-Charge.Note :- (i) 4 Run of ACSR conductor with 01 Run of GI wire shall be measured as 01 RM for payment, Linear length centre to centre of the poles shall only be measured(ii) Cleaning / pruning of tree branches falling around the conductor shall also deemed to be included in the quoted rates |
| 102 | Supplying and fixing in repair flat twin core ,1.5sqmm nominal cross sectional areamultistrandedaluminium conductor cable, over all PVC sheathed, 1100 Volts grade heavy dutycable PVC insulatedand PVC sheathed complete |
| 103 | Supplying and fixing in repair flat twin core ,2.5 sqmm nominal cross sectional areamultistrandedaluminium conductor cable, over all PVC sheathed, 1100 Volts grade heavy dutycable PVC insulatedand PVC sheathed complete |
| 104 | Supplying and fixing in repair flat twin core ,6 sqmm nominal cross sectional areamultistrandedaluminium conductor FRLS cable, PVC insulated and sheathed 1100 Volts grade complete |
| 105 | S&F Cable jointing kit for straight through joint, heat shrink type joint for 1100 V grade cable complete with jointing material and accessories suitable for 3.5 / 4 core, 25 to 50 Sqmm XLPE armoured aluminium conductor cable.Note:- Excavation and earth work, extra cable if required will be measured & paid separately under respective items of this BOQ. |
| 106 | S&F Cable jointing kit for straight through joint, heat shrink type joint for 1100 V grade cable complete with jointing material and accessories suitable for 3.5 / 4 core, 70 to 150 Sqmm XLPE armoured aluminium conductor cable.Note:- Excavation and earth work, extra cable if required will be measured & paid separately under respective items of this BOQ. |
| 107 | S&F Cable jointing kit for straight through joint, heat shrink type joint for 1100 V grade cable complete with jointing material and accessories suitable for 3.5 / 4 core, 185 to 300 Sqmm XLPE armoured aluminium conductor cable.Note:- Excavation and earth work, extra cable if required will be measured & paid separately under respective items of this BOQ. |
| 108 | Deployment of manpower / tools / machinery for testing of LT under ground cable of any size / description in any location with high voltage DC testing machine after disconnecting form the supply and locating the fault in the cables by fault locating machine to pin point exact position of fault, including Reconnections and testing of cables after removal of fault complete all as specified and directed.Note :(a)Removal / rectification of fault, 1.1 KV LT cable & joints will be measured and paid separately under respective items of BOQ. (b) Contractor or his rep shall come to the site of breakdown within one hour of notification of breakdownalong with fault locating machine and manpower.In case the rep or contractor not come to the site of breakdown and not start attending breakdown within 1.00 hour a penalty of Rs 500 per fault per hour will be imposed over contractor and will be deduct from his dues. |
| 109 | S&F in repair Danger notice plate made of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S clamps, bolts and nuts of approved size, for HT, 25 mm X 20 mm X 1.6 mm size incl taking down old one complete. |
| 110 | M&L for Preparation of old painted surface of 4 pole / two pole structure of HT steel tubular pole 11 mtr long including cross arm & bracing complete, from bottom to top and painting with one coat aluminium paint, and painting to bottom up to 1.5 mtr height from top of PCC coping with synthetic enamel paint one coats in Red / yellow / blue alternate strip incl numbering in 8 cm heightof number with black paint dully approved.Note:- Each 4 / 2 pole structure shall be measured as 1 unit for payment. |
| 111 | Deployment of manpower / tools / machinery for Periodical servicing of air circuit breaker and disconnecting the electrical connection from unserviceable parts and taking out the unserviceable part from the ACB and supply and fix the new part as per existing make / model / capacity incl cleaning and greasing fixed and movement parts etc complete.Note :- (i) All unserviceable spare part will be measured & paid separately under relevant item of this BOQ(ii) Unit rates quoted by tenderers shall deem to include for, bolts, washers, lugs, thimble, wires and petty items required for efficient and smooth functioning of the equipment without any extra cost. |
| 112 | Supply only Shunt release |
| 113 | Supply only Under voltage release |
| 114 | Supply only Earth fault release |
| 115 | Supply only Remote fault indicator |
| 116 | Supply only Microswitch for indication |
| 117 | Supply only lockable trip push button |
| 118 | supply only locking ACB in isolating position |
| 119 | Supply only locking ACB in any position |
| 120 | Supply only racking interlock |
| 121 | Supply only door interlock |
| 122 | Supply only machinal operation counter |
| 123 | Supply only Mounting kit for front mounted counter |
| 124 | Supply only spring charge indication microswitch |
| 125 | Supply only racking pad lock assembly |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2025 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail