| 1 | Wiring for light point/fan point/exhaust fan point/call bell point with 1.5sq.mm. FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with moduler switch,modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core e.t.c as required. Group C, P.S. No.-1.10.3 |
| 2 | Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core in surface/ recessed medium class PVC conduit, 2 way module switch, module plate suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core e.t.c as required. P.S. No.-1.11 |
| 3 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, as required. |
| 4 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire As per DSR no.-1.14.1 |
| 5 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire As per DSR no.-1.14.2 |
| 6 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire As per DSR no.-1.14.3 |
| 7 | 2 X 6 sq. mm + 1 X 4 sq. mm earth wire As per DSR no.-1.14.4 |
| 8 | 2 X 10 sq. mm + 1 X 6 sq. mm earth wire As per DSR no.-1.14.5 |
| 9 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch , connections etc. as required. P.S. No.-1.31 |
| 10 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 A & 15/16 A modular socket outlet and 15/16 A modular switch , connections etc. as required. P.S. No.-1.32 |
| 11 | All Incomer Feeders shall be provided with Multifunction Metering along with Phase Indicating Lights and other associated components such as CT, control MCB Terminal Block etc. and all Outgoing Feeders 100A & above shall be provided with 3 phase Ammeter along with phase Indicating Lights and other associated components such as CT, control MCB Terminal Block etc. The Feeders above shall be provided ac accommodated all Measuring Instruments shall be Digital type & all Indicating Lights shall be LED type.Wiring shall be done from 1100V Grade PVC Insulated copper flexible wire. All ACB shall be Electrically operated Draw-out type with Microprocessor Based O/L, S/C & E/F Release of Breaking/ Withstand Capacity (ICU/ICs/Icw) 50kA or more All MCCB shall be Thermal Magneetic/Microprocessor with O/L & S/C Protection along with Required Spreaders & Extended Rotary Handle with pad Locking facility of Breaking capacity (ICU/ICS) 36kA or more All MCB shall be Thermal 10kA \"C\" Curve. Cubicle type switch board shall be Cat-A and B only. P.S.-No-22.1Incoming 200 Amp.MCCB-1 NoOutgoing 63 Amp. MCCB-03 Nos. & 100 Amp MCCB- 01 No. |
| 12 | Supplying and fixing following ways,4 ways (4+12), Double door and 4 way Double door TPN MCBDB horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections,powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) P.S. No.-2.4.1 |
| 13 | Supplying and fixing Cable End Box (Loose wire box) Suitable for following triple pole and neutral, Sheet steel, MCB distribution board, 415 volts, on surface/recess, complete with testing and commissioning etc. as required. P.S. No.- 2.24.1 |
| 14 | Supplying and fixing Cable End Box (Loose wire box) Suitable for following Single pole and neutral, Sheet steel, MCB distribution board, 240 volts, on surface/recess, complete with testing and commissioning etc. as required. |
| 15 | For 8 way, Double door SPN MCBDB P.S. No.- 2.23.2 |
| 16 | For 12 way, Double door SPN MCBDB P.S. No.- 2.23.3 |
| 17 | Supplying and fixing following way Double door SPN MCBDB single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections,powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 18 | For 8 way, Double door P.S. No.-2.3.2 |
| 19 | For 12 way, Double door P.S. No.-2.3.3 |
| 20 | Supplying and fixing 63 A rating, 4 pole, 415V,MCB in the existing MCB DB complete with connections, testing and commissioning etc. as required. A/R |
| 21 | Supplying and fixing 32 A rating, two pole, 240V,MCB in the existing MCB DB complete with connections, testing and commissioning etc. as required. P.S. No.-2.10.3 |
| 22 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of Single poles in the exixting MCB DB complete with connections, testing and commissioning etc. as required. P.S. No.-2.10.1 |
| 23 | Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A 240 V \"C\"curve DP MCB complete with connections, testing and commissioning etc. as required. P.S. No.-2.16 |
| 24 | Supply and Burring of safe Earthing Electrode T-39, Zn-Zinc coated, Length 3000mm ,outer pipe 76.3mm x 3.2mm inner pipe 42.4mm x 2.6mm, Terminal Dia 12mm, coating 80-100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30cm square C.I frame with hinged cover & masonry housing (from electrode terminal to switch board, cost of 25x3 G.I strip will be extra ). Make as approved in U.P.P.W.D & C.P.R.I Certified . Quat. |
| 25 | Supplying and Laying 25 mmx 5 mm G.I Strip at 0.5 Meter below ground as strip earth electrod , including Connection / Termination with G.I nut, Bolt, Spring , washer etc as required Ps.S. No.-5.9 |
| 26 | Supply and fixing of hexagonal / Round G.P fan box of approved make Quat. |
| 27 | S/F Exhaust Fan 300mm sweep metallic Quat. |
| 28 | Supplying, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos, canopies, shackle kit, safty rop, copper winding, Power factor not less than 0.9, Service value (CM/M/W) minimum 6.00, Air delivery minimum 210 Cum/Min, 350 RPM (tolerance as per IS : 347-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temprature rise =75 degree C(max.), insulation resistance more than 2 mega phm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. P.S. No.-19.1 |
| 29 | Supplying and fixing call bell/ buzzer suitable for single phase, 230 V, complete as required. P.S. No.-1.38 |
| 30 | Supplyand fixing of LED Tube Light with heavy duty Metal Box type Tube Light fitting 1x22watt suitable for up to 1x22watt LED Polycarbonate tubelight complete Including tube suitable for bothsurface & suspended complete in all respect. 2620 system lumens, >120 Lm/W, PF>0.95, THD <10%, CRI>80, sheet thickness min 0.8mm, Tube with aluminium heat sink,>300V over voltage protection, 2.5 KV internal Surge Protection, with 5year warrantee.CAT AAA P.S. No.-23.07 |
| 31 | Supply and fixing of Recess/pendent mounting having having 1\" X 4\" Size 36 to 46 Watt seamlessly intergrated LED luminaire with High purity / transmisivity UV Stabilized Non yellowish diffuser/ Reflector for uniform light distribution, integral/detachable driver set, open and short circuit protection, suitable for 24 HrContinuous Operation, Complete in All respect.4320-5520 system lumens, >120 Lm/W, PF>0.95, THD<10% at full load, CRI >80, >300V over voltage protection, 4 KV internal Surge Protection, with 5 years warrantee P.S. No.-23.1 |
| 32 | S/O of LED Bulb 15W/17W Quat. |
| 33 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade on wall surface as directed by the Engineer-Incharge, complete in all respect. including excavation & refilling. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. |
| 34 | S/O of 25 sqmm 3-1/2 core armoured cable. P.S. No.- 20c.1.10 |
| 35 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750mm below ground level over a cushion of 75mm thick sand all around and protected with burnt bricks on sides and on top as directed by engineer - incharge complete in all respect.including excavation & refilling. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. |
| 36 | S/O of 120sqmm 3-1/2 core armoured cable. P.S. No.- 20a.1.15 |
| 37 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheated/XLPE aluminium conductor cable of 1.1 KV grade as required |
| 38 | 25 sq. mm 3-1/2 core P.S. No.-9.1.20 |
| 39 | 120 sq. mm 3-1/2 core P.S. No.-9.1.25 |
| 40 | Supplying and Laying of 1800mm x 900mm x 12mm thick Rubber mating of Tested Quality Quat. Please Enable Macros to View BoQ information |