| 1 | PART - A : PLANT OPERATION & ASSOCIATED WORK |
| 2 | Operation of 180 KLD MBBR technology based sewage treatment plant (STP), 30 KLD Effluent Treatment Plant along with Delay Tanks & Collection wells at Homi bhabha cancer hospital & research center visakhapatnam in daily three shifts i.e 24x7x365 days basis for twelve months as per schedule. The Item Includes Manpower (2 Mechanic+3 Operator+1 Helper cum Safiawala with suitable avaliable of reliver) Chemicals, Cleaning of all tanks quaterly, etc. |
| 3 | PART - B : COMPREHENSIVE MAINTENANCE incl ASSOCIATED COMPONENTS (All Electrical Components including wiring & cabling, panels, Motors, Earthpits Maintainance etc.,) |
| 4 | Comprehensive maintenance of pump sets along with Electrical panels & Mechanical components (please refer ANNEXURE-H for list of pumps and its auxilary components) |
| 5 | Comprehensive maintenance of Air Blowers as per clause no. 4 of schedule I of Specifications. |
| 6 | Air blowers for Equalization tank, FAB reactor tank and Sludge Holding Tank(2Nos x 4 times in one year ) - STP |
| 7 | Air blowers for Equilisation tank & Sludge holding tanks (2Nos x 4 times in one year) - ETP |
| 8 | Comprehensive maintenance of Air Diffusion system of Different Capacitiesas per clause no. 5 of schedule I of Specifications. (Tank cleaning will be measured & paid seperately). |
| 9 | Air Diffsuion system for Equilization Tank & sludge Holding Tank (Type of diffuser: Coarse type & Air flow rate : 6 - 8 m3 / hr, Pressure Rating : HDPE/UPVC - 10 kg / cm2 , size of diffuser : 90 mm dia MOC : EPDM)(1No x 4 times in one year) - STP |
| 10 | Air Diffsuion system for FAB Reactor Tank (Type of diffuser: Fine Bubble type & Air flow rate : 10 - 12 m3 / hr, Pressure Rating : HDPE/UPVC-10 kg / cm2 , size of diffuser : 90 mm dia & MOC : EPDM)(1No x 4 times in one year) -STP |
| 11 | Air Diffsuion system for Equilization Tank & sludge Holding Tank (1No x 4 times in one year) ( Coarse type & Air flow rate : 4 - 6 m3 / hr, Pressure Rating : HDPE/UPVC - 10 kg / cm2 , size of diffuser : 90 mm dia & MOC : EPDM) - ETP |
| 12 | Comprehensive maintenance of Filter Press as per clause no. 6 of schedule I of Specifications. |
| 13 | Filter press (1No x 4 times in one year) - STP |
| 14 | Filter press (1No x 4 times in one year ) - ETP |
| 15 | Comprehensive maintenance of Ozonator as per clause no. 7 of schedule I of Specifications. |
| 16 | Ozonator System and its accessories (1Nos x 4 times in one year) |
| 17 | Comprehensive maintenance of (UV) Ultraviolet light as per clause no. 8 of schedule I of Specifications. |
| 18 | Ultraviolet light (1Nos x 4 times in one year) |
| 19 | Multi Grade Filter & Activated carbon filter and associated works as per clause no. 9 of schedule I of Specifications. |
| 20 | Multi Grade filter (1Nos x 4 times in one year ) |
| 21 | Activated carbon filter (1Nos x 4 times in one year ) |
| 22 | Comprehensive maintenance of Agitators (Including Motors and all its accessories & Fittings) of different Capacities. |
| 23 | Anoxic Tank Agitator (1No x 4 times in one year)- STP |
| 24 | NaOH Dosing system Agitator (1No x 4 times in one year)- ETP |
| 25 | Alum Dosing system Agitator (1No x 4 times in one year) - ETP |
| 26 | Poly Dosing system Agitator (2No x 4 times in one year) - ETP |
| 27 | Poly Dosing system Agitator (2No x 4 times in one year) - ETP |
| 28 | Comprehensive maintenance of Filtration Unit of Armas VH-070 (1No x 4 times in one year) |
| 29 | Comprehensive maintenance of ELECTROMAGNETIC ONLINE DIGITAL FLOW METER of Flowtech Make with model FMIPL-EMFM-F-C-PL-EL1-AC1-M-I-040. (3Nos x 4 times in one year). Which includes Calibiration, Repair/Replacement. |
| 30 | Comprehensive maintenance of ONLINE PH ELECTRODE WITH DIGITAL INDICATOR of Forbes Marshall Make. (3Nos x 4 times in one year). Which includes Calibiration, Repair/Replacement. |
| 31 | Carring out calibration of various pressure gauges through accredited laboratory including making proper setting for with in range indication if required & submitting its original calibration certificate having one year\"s validity before due date complete as per site requirment |
| 32 | Collection of Samples (Total 5 Samples - STP Inlet & Outlet, ETP Inlet & Outlet & at Delay tank/or as specified by EIC) from site on monthly basis, delivery and testing of same at NABL accredited lab. Sample testing includes the parameters like PH, COD, BOD,TSS Oil & grease, Dissolved oxygen (D.O), Chloride & Sulphate. Submission of its originaltest report before 1st week each next month as per instruction and as directed by engineer in charge. Note: Sealed container for sample collection is in scope of contractor. |
| 33 | Carrying out complete comprehensive maintainance including cleaning of lamella clarfier with flocculator & Tube settler with inclined plate mechanism and attending all noticed issues/deficiencies in all respect including supply & fixing of all required materials/spares/hardwares, carrying out repair or replacement of all worn out / damaged parts /inclined FRP plates, carrying out all related works etc. complete as per site requirement. This work includes to carry out complete cleaning of tank to replace damaged FRP plates by removing all existing excretal, sewage, sludge, muddy water etc. complete by mechanical manual means and disposal of the same including making required pumping arrangement, lifting, loading, unloading, transportation. taking all safety precautions, etc. complete as per site requirement & as directed by E.I.C.(Half Yearly) |
| 34 | Supply, installation, testing & commissioning of following items for Ultra voilet light system (1 No) as directed & as per instruction of EIC. (Make: - M/s Alpha UV make , model no. HF6-HD |
| 35 | Ballast-270104006 |
| 36 | UV lamp-270134027 |
| 37 | Quartz Sleeve |
| 38 | Supply, filling, setting, testing & commissioning of all required medias in appropriate quantum in Activated Carbon Filter of size 1.6m (D) x 1.875 (H) of STP adopting standard practices / OEM recommendations including removal of all old medias, cleaning, supply & fixing of all required hardwares / spares, disposal of all old medias, carrying out all related works etc. complete as per site requirement. Please refer clause no. 10 of schdule I of specifications for details. (Yearly Once) |
| 39 | Supply, filling, setting, testing & commissioning of all required medias in appropriate quantum in Multi Grade Filter of size 1.2m (D) x 1.875 (H) of STP adopting standard practices / OEM recommendations including removal of all old medias, cleaning, supply & fixing of all required hardwares / spares, disposal of all old medias, carrying out all related works etc, complete as per site requirement. Please refer clause no. 11 of schdule I of specifications for details. (Yearly Once) |
| 40 | Supply & filling, setting of MBBR media including adopting standard practices / OEM recommendations including removal of all old media, cleaning, supply & fixing of all required hardwares / spares, disposal of all old media, carrying out all related works etc. complete as per site requirement.. (Yearly Once) |
| 41 | Preparing & Submitting the Half-yearly Compliance Report as per the Conditions (Which include as Quaterly Testing of Ambient Air Quality Monitoring (PM2.5, PM10, SO2, NOx, CO, O3, Pb, NH3, As, Ni, C6H6), Stack Emissions of DG Set (2 Nos) (SPM,SO2,Nox, Metals, etc), Noise Monitoring (Day & Night), Inlet & Outlet Parameters of STP&ETP, Bio Assay Test (90% survival of fish after 96 hours in 100% effluent) etc.,) as per Consent for Establishment (CFE), Consent for operation (CFO) and Environmental Clearance (EC) to Andhra Pradesh Pollution Control Board (APPCB)/CPCB through offline/online. The Bidder Should Submit the Compliance reports audited by through NABL accredited third party. |
| 42 | PART - C : Civil Works |
| 43 | Supply of RO membranes for 1000LPH RO Plant (Preferd makes Hydronatic, Filmtec, Toray, LG) |
| 44 | Providing and fixing 10 mm thick acid and/or alkali resistant tiles of approved make and colour using acid and/or alkali resisting mortar bedding, and joints filled with acid and/or alkali resisting cement as per IS : 4457, complete as per the direction of Engineer-in- Charge. In flooring on a bed of 10 mm thick mortar 1:4 (1 acid proof cement: 4 coarse sand) Acid and alkali resistant tile |
| 45 | Providing and fixing 10 mm thick acid and/or alkali resistant tiles of approved make and colour using acid and/or alkali resisting mortar bedding, and joints filled with acid and/or alkali resisting cement as per IS : 4457, complete as per the direction of Engineer-in- Charge: In dado/skirting on 12 mm thick mortar 1:4 (1 acid proof cement: 4 coarse sand) Acid and alkali resistant tile |
| 46 | Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade : One or more coats on old work (including scrapping and applying red oxide primer) |
| 47 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipes & fittings (T,L, Flanges,Sockets, Union etc)with one step CPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge : |
| 48 | 15 mm nominal dia Pipes |
| 49 | 20 mm nominal dia Pipes |
| 50 | 25 mm nominal dia Pipes |
| 51 | 32 mm nominal dia Pipes |
| 52 | 40 mm nominal dia Pipes |
| 53 | 50 mm nominal dia Pipes |
| 54 | 65 mm nominal dia Pipes |
| 55 | 80 mm nominal dia Pipes |
| 56 | 100 mm nominal dia Pipes |
| 57 | Providing, laying & testingof following classes MS pipes conforming to IS 3589 and 1239 including fittings like elbows, tees, flanges, tapers, nuts, bolts, gaskets including transportaiton and painting with two coats of red oxide paint and one coat of enamel paint and all labour charges and cost of all accessories etc., complete. Makes: As per list of recommended brands. |
| 58 | 40 mm dia |
| 59 | 50 mm dia |
| 60 | 65 mm dia |
| 61 | 80 mm dia |
| 62 | Percentage increase on the value of O&CMC for the next successive year after completion of initial year. (This will be awarded based on the satisfactory performance of the initial year). |