| 1 | M&L dismantling ofACSR conductor of any type/ size on existing LT poles, etc including binding on to insulators with and including aluminium wire three phase and neutral complete all as specified and directed . |
| 2 | Taking down staying assemlbly all specified and directed |
| 3 | Taking down cross arms all specified and directed |
| 4 | Taking down insulator any typeall specified and directed |
| 5 | Supply, laying andTesing LT UG XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 120 Sq mm 3.5 core as per IS specifications complete all as specified and directed |
| 6 | Supply, laying and TestingLT UG XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 70 Sq mm 3.5 core as per IS specifications complete all as specified and directed |
| 7 | All as per ser item No 6 here in before but of 50 Sqmm 3.5 core |
| 8 | All as per ser item No 6 here in before but of 35 Sqmm 3.5 core |
| 9 | All as per ser item No 6 here in before but of 25 Sqmm 4 core |
| 10 | All as per ser item No 6 here in before but of 16 Sqmm 4 core |
| 11 | All as per ser item No 6 here in before but of 16 Sqmm 2 core |
| 12 | All as per ser item No 6 here in before but of 10 Sqmm 4 core |
| 13 | All as per ser item No 6 here in before but of 10 Sqmm 2 core |
| 14 | Excavation in trenches not exc 1.5 meter wide and not exc 1.5 metre in depth and getting outin soft/loose soil, for laying underground pipe etc., complete all as specified and directed . |
| 15 | Returning, filling in incl spreading ,levelling watering and well ramming in layer n exc 25cm thick each layer , in soil, complete all as specified and directed . |
| 16 | Removing excavated surplus materialto a distance n exc 50m and depositing where directed at level n. exc 1.5m above the starting point in any type of soil, complete all as specified and directed . |
| 17 | Material and Labour of DWC HDPE Pipe of standard IS 16205 Part 24of outer dia 63 mm with coupler including complete fitting and Fixturelaid in trenches / surface etc. complete all as specified and directed by Engr in Charge |
| 18 | Material and Labour of DWC HDPE Pipe of standard IS 16205 Part 24of outer dia 50 mm with coupler including complete fitting and Fixturelaid in trenches / surface etc. complete all as specified and directed by Engr in Charge |
| 19 | Material and Labour of DWC HDPE Pipe of standard IS 16205 Part 24of outer dia 40 mm with coupler including complete fitting and Fixturelaid in trenches / surface etc. complete all as specified and directed by Engr in Charge |
| 20 | Supply and fix of 2 runs of 1.5 Sqmm+ 1.5 Sqmm earth wirePVC FRLS insulated stranded copper cable for connection of street light including PVC conduit 20 mm external dia, medium grade, fixed on pole with proper clamping/ saddling etc complete all as specified and directed. |
| 21 | Supply and fixing LED street light fitting 70 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermalmanagement in multiple optics complete with IP 65/66 protection complete. all as specified and directed. |
| 22 | Supply and fixing of PVC Terminal /junction 4 Nos aluminium bus bar mounted on DMC insulator andMCB SP 20 Amps, 10 KA, Size 310 x 210 x 120mm and fixed with MS flat iron clamps to pole complete all as specified and as directed. |
| 23 | S&Fbracket made of GI pipe light grade 40mm bore bend to shape in 120 degree of 1.2 m in length suitable for fixing street light luminaire and fixed on wall/pole including necessary MS clamps, nuts, bolts etc complete all as specified and as directed. |
| 24 | Supply & fabrication of outdoor type Feeder fillerboard factory made CPRI approved tested for IEC 61439 standards with IP 54 grade of protection and installed at a height of 1 feet oversuitable PCC plat form fabricated with suitable angle iron (50x50x6mm thick) bottom leg supports for resting independently cubical ,compartmental type with double hinged front openable doors, half turn type operating knobs for incoming feeders and out going feeders made of 2 mm thick CRCA sheet metal powder coated for outer sheet of panel and 3.1 mm thick CRCA sheet for patition and compartment doors andwith suitable capacity of Copper bus bar not less than160 Ampscapacityfor each phases supported by suitable insulators and covered with colour coded heat shrinkable sleeves along with wiring of panel with suitable size of copper conductor cable for accesories including provision of necessary cable entry/exit boxescomplete all as directed by Engr-in-Charge. Incomer :-(I)MCCB current rating 125 Amp breaking cap 36KA ICS = 100%,4P 415 Volts AC-1 nosOut going :-(II) MCB TPN \"C\" curve 40 Amps 10KA 4P 415 Volt AC-1 Nos(III) MCB SPN \"C\" curve 63 Amps 10KA 2P 230 Volt AC-8 Nos(IV) MCB SPN\"C\" Curve 40 Amps 10KA 2P 230 Volt AC-3 Nos(V) MCB SPN \"C\" curve 20 Amps 10KA 2P 230 Volt AC-3 Nos ( Street light + spare2) |
| 25 | Supply & fabrication of outdoor type Feeder fillerboard factory made CPRI approved tested for IEC 61439 standards with IP 54 grade of protection and installed at a height of 1 feet oversuitable PCC plat form fabricated with suitable angle iron (50x50x6mm thick) bottom leg supports for resting independently cubical ,compartmental type with double hinged front openable doors, half turn type operating knobs for incoming feeders and out going feeders made of 2 mm thick CRCA sheet metal powder coated for outer sheet of panel and 3.1 mm thick CRCA sheet for patition and compartment doors andwith suitable capacity of Copper bus bar not less than160 Ampscapacityfor each phases supported by suitable insulators and covered with colour coded heat shrinkable sleeves along with wiring of panel with suitable size of copper conductor cable for accesories including provision of necessary cable entry/exit boxescomplete all as directed by Engr-in-Charge. Incomer :-(I)MCCB current rating 125 Amp breaking cap 36 KAIcs =100% 4P 415 Volts AC-1 nosOut going:-(II) MCB TPN current rating40 Amps 10KA 4P 415 VoltIcs =100% AC-1 Nos(III) MCB SPN current rating63 Amps 10KA 2P 230 Volt AC-7 Nos(IV) MCB SPN Current rating 40 Amps 10KA 2P 230 Volt AC-4 Nos(V) MCB SPN Current rating 20 Amps 10KA 2P 230 Volt AC-3 Nos ( Street light + spare2) |
| 26 | Supply & fabrication of outdoor type Feeder fillerboard factory made CPRI approved tested for IEC 61439 standards with IP 54 grade of protection and installed at a height of 1 feet oversuitable PCC plat form fabricated with suitable angle iron (50x50x6mm thick) bottom leg supports for resting independently cubical ,compartmental type with double hinged front openable doors, half turn type operating knobs for incoming feeders and out going feeders made of 2 mm thick CRCA sheet metal powder coated for outer sheet of panel and 3.1 mm thick CRCA sheet for patition and compartment doors andwith suitable capacity of Copper bus bar not less than160 Ampscapacityfor each phases supported by suitable insulators and covered with colour coded heat shrinkable sleeves along with wiring of panel with suitable size of copper conductor cable for accesories including provision of necessary cable entry/exit boxescomplete all as directed by Engr-in-Charge. Incomer :-(I)MCCB current rating 125 Amp 36 KA Ics= 100% 4P 415 Volts AC-1 nosOut going:-(II) MCB TPNCurrent Rating 40 Amps 10KA 4P 415 Volt AC-1 Nos(III) MCB SPN current rating 63 Amps 10KA 2P 230 Volt AC-6 Nos(IV) MCB SPNcurrent rating 40 Amps 10KA 2P 230 Volt AC-8 Nos(V) MCB SPN current rating 20 Amps 10KA 2P 230 Volt AC-3 Nos ( Street light + spare2) |
| 27 | Supply & fabrication of Outdoor type LT panel board factory made CPRI approved tested for IEC 61439 standards with IP 54 grade of protection and installed at a height of 1.5 feet oversuitable PCC plat form fabricated with suitable angle iron (50x50x6mm thick) bottom leg supports for resting independently cubical ,compartmental type with double hinged front openable doors, half turn type operating knobs for incoming feeders and out going feeders made of 3.15 mm thick CRCA sheet metal powder coated for outer sheet of panel and 3.15 mm thick CRCA sheet for patition and compartment doors andwith suitable capacity of Copper bus bar not less than250Ampscapacityfor each phases supported by suitable insulators and covered with colour coded heat shrinkable sleeves along with wiring of panel with suitable size of copper conductor cable for accesories including provision of necessary cable entry/exit boxescomplete all as directed by Engr-in-Charge. Incomer :-(I)MCCB current rating 250 Amp short circuits breaking cap15 KA Ics =100% 26 KA rms4P 415 Volts AC-1 nos(ii) Digital VoltmeterNos-1(III) Digital Ammeter Nos-1(IV) Phase indicating lamp Nos-3Out going(I) MCCB Current cap150 Amps rated short circuits 15 KA short circuits Ics =100% 26 KA rms4P 415 Volt AC-1 Nos(II) MCCB current cap 125 Amps rated short circuit 15 KA Breaking cap 26 Ics 100% 4P 415 Volt AC-2 Nos(III) MCCB current cap 100 Amps breaking cap 15 KA short circuits Ics 100% 26 Ka4P 415 Volt AC-1 Nos |
| 28 | S&Fof GI Tube 80 MM Light Grade laid in trenches under roador fixed to wall as mechanical protection for UG Cables complete all as specified and as directed. |
| 29 | S&Fof GI Tube 50 MM Light Grade laid in trenches under roador fixed to wall as mechanical protection for UG Cables complete all as specified and as directed. |
| 30 | M & L for earthing complete with galvanised steel earth plate electrode 600 x 600 x 6.0 mm thick burried directly in gorund (earth pit not less than 2.25 Mtr normal ground level),and top edge of earth plate not less than 1.5 mtr below normal ground level, connected to galvanised earth strip 32 x 6 mmmeans of bolts, nuts & check nuts, and washers of galvanised iron protection pipe light grade of 40 mm dia and watering pipe medium grade of 20 mm dia and filled with alternate layer of charcoal and common salt, watering funnel with wire mesh, earth pit chamber and cover CI frame PCC 1:3:6 type C-2 all as shown in electrical plate No-3 of SSR part-I of 2009 connected to earthing test point all as specified and indicated including all earth work excavation, returning filling and disposal of surplus soil and testing on completion. |
| 31 | M & L for earthing complete with galvanised steel earth plate electrode 600 x 600 x 6.0 mm thick burried directly in gorund (earth pit not less than 2.25 Mtr normal ground level),and top edge of earth plate not less than 1.5 mtr below normal ground level, connected to galvanised earth wire 4 .0 mm diammmeans of bolts, nuts & check nuts, and washers of galvanised iron protection pipe light grade of 40 mm dia and watering pipe medium grade of 20 mm dia and filled with alternate layer of charcoal and common salt, watering funnel with wire mesh, earth pit chamber and cover CI frame PCC 1:3:6 type C-2 all as shown in electrical plate No-3 of SSR part-I of 2009 connected to earthing test point all as specified and indicated including all earth work excavation, returning filling and disposal of surplus soil and testing on completion. |
| 32 | Schedule of Credit |