| Sl. No. | Item Description |
| 1 | Disconnecting and dismantling the existing indoor type 11 kV horizontal draw-out type VCB trolley, rupturing capacity 250/350 MVA, rated current 400/630/800/1200 A, from its installed location.Includes complete repair/overhauling as specified and directed by the Engineer-in-Charge.Note: Spare parts shall be measured and paid separately. |
| 2 | Note for Item No 01- Overhauling of VCB mechanism, including:(i) Inspecting and overhauling the manual/motorised spring-drive mechanism—motor, gear train, main shaft, interlocking assembly, stop bolt, closing spring assembly, small cam, motor cut-off limit switch, butterfly switch assembly—and applying multi-purpose grease for smooth operation.(ii) Inspecting and overhauling the tripping mechanism, earth-fault release, tripping coil, auxiliary switch, and entire control wiring system.(iii) Cleaning and inspecting insulators and vacuum interrupters using carbon-cleaner solution; applying dry graphite conductive sealant on electrical contact surfaces to prevent carbon deposition.(iv) Complete re-assembly of all components and testing the breaker by High Voltage (DC) test and meggerring before and after H.V. test, complete as specified. |
| 3 | Material and labour for painting of HT VCBcapacity 250/350MVA,11KV, 400/630/800/1200Amps, with onecoat of synthetic enamel paint over a coat ofred oxide primerafter cleaning, scraping, and filling ofcavitiesfor out side surface and in side surfaceof VCB and all as specified and as directed by Engineer-in-charge. |
| 4 | Material and labour for Opening the Bus-Bar Chamber, CT Chamber, PT Chamber and Metering Chamber of 11 kV indoor HT panel and carrying out complete servicing as directed.Note: Spare parts shall be measured and paid separately. |
| 5 | M & L for Inspecting/cleaning/overhauling of bus bar chamber by checking of bus bars, spout insulators, space heaters and removing dust with vacuum cleaner/Blower and moisture by hot air blower and checking tightness of bus bars, insulators and applying STRIPPEX(A), STRIPPEX(B)and HTtape and test with High Voltage(DC)and meggering before and after high voltage test complete.(ii) Inspecting/cleaning/overhauling of CT/PT chamberby checking of Bus bars, spout insulators, space heaters and checking of wiring system and removing dustwith vacuum cleaner/blower and moisture by hot air blower and checking tightness of bus bars, insulators and applying anti tracking paint on CT\"s and insulatorsand HT Tape. (iii) Inspecting/cleaning/overhauling meteringchamberby checking ofentire wiring system, all meters, selector switches, control fuses and removing dustwith vacuum cleaner/blower and moisture by hot air blower and checking tightness of wiring system. |
| 6 | Overhauling, calibration and secondary injection testing of over-current and earth-fault relays, including adjusting multiple settings using artificial load and carrying out complete operational and functional testing as specified. |
| 7 | M & L for Testing by primary injection through CTs on all multiple settings of over-current and earth-fault relays, including checking relay pick-up, polarities, ammeter functions and selector switch operation, complete as directed. |
| 8 | Dismantling, overhauling and testing Potential transformer capacity 11 KV / 110 volts, ACand replacement of worn out spares such as contacts, bushing, control wiring fibre plates, gaskets , transformer oil and applying multi grease to the mechenical parts & dry graphite conductive sealant to contacts etc & re-assembling the same and commissioning complete all as specified and directed by Engineer-in-Charge. (Note : Spare parts and oil will be measured and paid seperately) |
| 9 | Testing of dielectric strength of transformer oil of indoor type transformer, 11KV/433 volt, filteration of transformer oil by passing through filtration plant to remove moisture, impurities and improving di-electic strengthto above 40 KV for 1 minute including new transformer oilfor toping up & testing after filtration complete as specified. (Note: Transformer oil will be measured & paid seperately.) |
| 10 | Supply only transformer oil with 50KV di-electric strength for topping up and replacement of old/burnt transformer oil complete all as specified. |
| 11 | Supply and fixing in repair of breather with 500 Grams silica gel of indoor type transformer for 1600KVA, all as specified and directed by Engineer-in-Charge. |
| 12 | Material and labour for Spray Painting of Transformer 1600KVA ,11KV/440Volt capacity, indoor typewith twocoats of synthetic enamel paint over a coat ofred oxide primerafter cleaning, scraping, and filling ofcavitiesand all as specified and as directed. |
| 13 | Material and labour for disconnectingof LT and HTcable carefully from Transformer and draining out transformer oil, dismantling transformer 1600KVA ,11KV/440Volt, top coverand dismantling of 4Nos LT bushingand 3Nos of HT bushingincluding necessary tools and plant for attending leakage problem with replacement of oil seal, all gaskets,thermometer(oil temperature gauge)and reassembling complete all as directed.(Note : New Transformer oil and spare partswill be measured and paid separately excluding oil seal and thermometer i.e oil temperature gauge) |
| 14 | Material and labour in repair of burnt out studs and bushing with nuts of Transformer 1600KVA ,11KV/440Volt, any material by providing new copper alloy stud with nut,washers and bushing with oil seals on HT side all as directed. |
| 15 | Material and labour in repair for burnt out studs and bushing with nuts of Transformer 1600KVA ,11KV/440Volt, any material by providing new copper alloy stud with nut,washers and bushing with oil seals on LT side all as directed. |
| 16 | Supply and fix in repair of following spare partssuitable for GECHT VCB, 11 KV , 630/800/1000/1200 Amps indoor typecomplete all as specified and directed by Engineer-in-Charge. |
| 17 | Opening/ Closing Push Button Assembly |
| 18 | Motor Charging mechanism gear box |
| 19 | Limit Switches |
| 20 | Closing Coil Assembly |
| 21 | Tripping Coil assembly |
| 22 | Spring Charging Motor |
| 23 | Auxiliary Switch with link |
| 24 | Spring return latch |
| 25 | Vaccum Interupter assembly |
| 26 | Spout Insulator assembly (3Phase) feeder side |
| 27 | Spout Insulator assembly (3Phase) Bus bar side |
| 28 | Potential Transformer,11KV/110Volt/Rout3,100VA burden Trolly mounted with HRC Fuse |
| 29 | Current Transformers,50-30,5+5Amps, Class1 and 5p10,15VA,18.3kA/3Sec |
| 30 | TNC Switch |
| 31 | PF meters digital type 96x96mm |
| 32 | Indicating Lamps LED type |
| 33 | Supply and fix in repair strip-type heater of 80 Watt rating with control wiring suitable for indoor VCB, 11 kV switchgear panel board, complete as specified and directed by the Engineer-in-Charge. |
| 34 | Dismantling Air Circuit Breaker (ACB) of 4-pole/3-pole configuration, capacity 630/800/1200/2500 Amps, 415 Volts, draw-out or fixed type, from its installed location and carrying out complete repair/overhauling of the spring drive mechanism, operating coils, auxiliary switch, including setting and adjustment of overload coil, no-volt coil and tripping coil, applying multi-purpose grease to all mechanical parts, cleaning and inspecting male and female contacts and applying dry graphite conductive sealant to contact surfaces, checking the electrical wiring system, testing, reassembling all components in their respective positions and conducting final testing, complete as specified and directed by the Engineer-in-Charge.(Note : Spare parts will be measured and paid separately) |
| 35 | Material and labour for repairs, overhauling and servicing of existing LT indoor type electric panels associated with each transformer, after obtaining shutdown from the appropriate authority, including checking and tightening loose connections, cleaning inside and outside all connections, replacing cable glands, thimbles and lugs as per size of existing cables, applying petroleum jelly on contactors, providing new insulation tape on bus bars, repairing broken or hanging doors by fixing hinges or welding to make them serviceable, spray painting with approved silver colour paint or powder coating, and testing the entire panel board after completion of servicing to the satisfaction of the Engineer-in-Charge, complete as specified.Note: The quoted unit rate shall be deemed inclusive of taking out burnt ACB/MCB/MCCB/Voltmeter/Ammeter/CT/LED lamps of any type and description and refixing the same, which shall be measured and paid separately under respective supply-only items of this schedule. |
| 36 | (i) Cleaning inside the panel and all incoming and out going feedersi.eincluding MCCB/SFU/Changeover switches/Contactors/ ACB\"s thorouly with help of Vaccum Cleaner.(ii) Checking the loose connections of incoming and out going feeders and rectifify the same with help of new GI nut bolts and washers (iii) Replacing the burnt out color coated PVC Sleeve of main and fedders bus bar with appropriated size of New PVC heat shrinkable sleeves -01Job (iv) Replacing Burnt out Voltmeters/Ammeters/Indicating Lamps/Hrc Fuses-01Job. (Note: New items will be measured and paid separatly) (v) Replacing burnt out control wiring of Ammeter/Voltmeter/Indicating lamps and CT\"swith 2.5/1.5Sqmm copper single core,1100V grade copper conductor cable- 01Job (vi) Replacing Burnt out Bus Bar of incomming and out going feededs with approprieted size of new bus bar (Copper/Aluminum) -01Job ( Note : Bus Bar will measured and paid separately).(vi) Replacing Burnt out Insulators of incomming and out going feeders with approprieted size of new Insulators-01Job ( Note : Insulators will measured and paid separately) (vii) Spray Painting of Panel Board with one coat of synthetic enamel paint. |
| 37 | Supply and fix aluminium bus bar strips of any required size for extension of MCCB terminals for cable terminations inside the cable alley of LT panel board, duly supported on FRP/DMC support insulators, including necessary drilling, bending and shaping at site to obtain required size and profile, complete as specified and directed by the Engineer-in-Charge.Notes:(a) Size of the strip shall be determined based on the current-carrying capacity of the respective outgoing MCCBs.(b) Overall length of the strip shall be measured and paid after conversion into weight.(c) Cost of drilling, bending and grinding of strips at site is deemed included in the quoted rate and no extra payment shall be admissible.(d) Rate of bolts, nuts and other fixing hardware shall be included in the quoted rate. |
| 38 | Supply and fix copper bus bar strips of any required size for extension of MCCB terminals for cable terminations inside the cable alley of LT panel board, duly supported on FRP/DMC support insulators, including necessary drilling, bending and shaping at site to obtain required size and profile, complete as specified and directed by the Engineer-in-Charge.Notes:(a) Size of the strip shall be determined based on the current-carrying capacity of the respective outgoing MCCBs.(b) Overall length of the strip shall be measured and paid after conversion into weight.(c) Cost of drilling, bending and grinding of strips at site is deemed included in the quoted rate and no extra payment shall be admissible.(d) Rate of bolts, nuts and other fixing hardware shall be included in the quoted rate. |
| 39 | Supply and fix suitable type and size FRP/DMC bus bar support insulator (bridge insulator) for fixing extended aluminium/copper bus bars for cable terminations, including fixing to the panel body with galvanised steel bolts, nuts, washers and carrying out all necessary drillings, complete as specified and directed by the Engineer-in-Charge. |
| 40 | Material and labour for fault-finding in HT cables of any size and any length using a fault detection machine by thumping method and applying suitable high voltage to locate the fault point, complete as specified and directed by the Engineer-in-Charge. |
| 41 | Supply and fix straight-through jointing kit for 11 kV grade 3-core XLPE armoured aluminium conductor cable of size 120 to 185 sqmm, complete with heat-shrinkable jointing materials, accessories and testing, all as specified and directed by the Engineer-in-Charge. |
| 42 | All as per Item No-22.00as above but of size 240 to 300 sq mm x 3 core all as specified and directed by the Engineer-in-Charge. |
| 43 | Supply and fix indoor type end-termination jointing kit for 11 kV grade cable, complete with heat-shrinkable jointing materials and all accessories, suitable for 3-core XLPE armoured aluminium conductor cable of size 120 to 185 sqmm, complete as specified and directed by the Engineer-in-Charge. |
| 44 | All as per Item No-24.00as above but of size 240 to 300 sq mm x 3 core |
| 45 | Supply, laying, commissioning and testing of XLPE insulated, armoured, heavy-duty electric cable with aluminium conductor, 1100-volt grade, of size 10 sqmm × 2-core, laid in trenches, passed through pipes or fixed on walls, including proper termination using thimbles and removal of old unserviceable/damaged cables, complete as specified and directed. |
| 46 | All as per Item No 26.00as above but for 6 Sqmm x 4 core. |
| 47 | All as per Item No 26.00as above but for 10 Sqmm x 4 core. |
| 48 | All as per Item No-26.00as above but of size 16 sq mm x 4 core |
| 49 | All as per Item No-26.00as above but of size 25 sq mm x 4 core |
| 50 | All as per Item No-26.00as above but of size 35 sq mm x 4 core |
| 51 | All as per Item No-26.00as above but of size 50 sq mm x 3.5 core |
| 52 | All as per Item No-26.00as above but of size 70 sq mm x 3.5 core |
| 53 | All as per Item No-26.00as above but of size 95 sq mm x 3.5 core |
| 54 | All as per Item No-26.00as above but of size 120 sq mm x 3.5 core |
| 55 | All as per Item No-26.00as above but of size 150 sq mm x 3.5 core |
| 56 | All as per Item No-26.00as above but of size 185 sq mm x 3.5 core |
| 57 | All as per Item No-26.00as above but of size 240 sq mm x 3.5 core |
| 58 | All as per Item No-26.00as above but of size 300 sq mm x 3.5 core |
| 59 | Taking out carefully the old XLPE insulated, armoured heavy-duty electric cable with aluminium conductor, 1100-volt grade, from trenches, pipes or walls and keeping it safely at site for re-use, cable size 10 to 50 sqmm × 3.5-core, complete as directed by the Engineer-in-Charge. |
| 60 | Laying only the old XLPE insulated, armoured heavy-duty electric cable with aluminium conductor, 1100-volt grade, of size 10 to 50 sqmm × 3.5-core, in trenches, through pipes or fixed on walls, including proper connection by means of thimbles, complete as directed by the Engineer-in-Charge.(Cable taken out under Sch “A”, Item No. 40.00 shall be re-used.) |
| 61 | Excavation in trenches not exc 1.5 mtr wide and not exc1.5 mtr in depth for laying of cables etc. in any type of soil and getting out all as specified and directed by Engineer-in-Charge. Note : Rate includes removing of paver blocks carefully and stack properly for refixing after laying of cables . |
| 62 | Returning filling in including spreading, levelling, watering and well ramming in layers not exc 25 cm in soils. |
| 63 | Removing excavated material from the site of work to outside MD land complete all as specified. |
| 64 | Material and labour for dry clean river sand for cushioning of cable in trenches for cable protection including spreading, leveling and hand punning complete all as specified in SSR Part-I and as directed. Note :-Only compacted thickness of sand will be measured and paid separately. |
| 65 | Supply and fix machine-pressed precast concrete interlocking paver blocks of any approved shape and size, conforming to IS 15658:2006, 100 mm thick, M-50 grade, width not less than 0.45 m, for reinstatement of road cuts/footpaths carried out under Schedule “A” Item No. 40.00, complete as directed. |
| 66 | Supply and laying of un-reinforced precast concrete cable covers, Class LV Type 1, flat size 250 mm × 150 mm × 40 mm, complete as specified and directed. |
| 67 | Cutting existing road surfaces or hard standing 0.45 mtr depth (22 thick comprising bituminuous topping) for laying of pipes/cables and making good disturbed surfaces to match with existing surfaces. |
| 68 | M&L for PCC 1:2:4 type B2 (using 40 mm graded stone aggregate) for road/Hard standing cutting complete all as specified and as directed. |
| 69 | M&L PCC 1:2:4, type B1 (using 20 mm graded granite stone aggregate) as in coping for steel pole including necessary formwork complete all as specified. |
| 70 | M&L for replacement 100mm High density poly-ethylene pipes (HDPE) of pressure 6 kgf/cm2 pipe, for road crossing of cable or for cable protectionlaid in trenches or above ground surface after taking out old one all as specified and directed. |
| 71 | M&L for replacement 50mm High density poly-ethylene pipes (HDPE) of pressure 6 kgf/cm2 pipe, material grade PE 63 , for road crossing of cable or for cable protectionlaid in trenches or above ground surface after taking out old one all as specified and directed. |
| 72 | M&L for replacement 25 mm High density poly-ethylene pipes (HDPE) of pressure 6 kgf/cm2 pipe, material grade PE 63 , for road crossing of cable or for cable protectionlaid in trenches or above ground surface after taking out old one all as specified and directed. |
| 73 | M&L for GI pipe, light grade 40mm dia for road crossing of cable for cable protection or above ground surface including taking out old one all as specified and directed. |
| 74 | Supply and fix exhaust fan, steel-body, AC single-phase, 230 volts, 50 Hz, 200 mm sweep, complete with blades, frame and louvers, including connection with suitable size three-core flexible copper conductor cable, providing one 6 A one-way control switch, and incorporating a digital timer switch (110–240 VAC, 50/60 Hz, tolerance −20% to +10%, contact rating 16 A (NO) & 5 A (NC) at 240 VAC/24 VDC). The item includes programming of the digital timer, performance testing and necessary time-setting adjustment to ensure proper operation as per user requirement, complete as specified and directed by the Engineer-in-Charge. |
| 75 | Cutting a hole in the existing LT panel board of 3 mm thick steel sheet for fixing a 200 mm sweep exhaust fan, including proper gasket installation and finishing the surface on both sides of the hole, making good the disturbed area to match the existing finish, complete as specified and directed by the Engineer-in-Charge. |
| 76 | Supply and fix ON-LOAD change-over switch, 415 V, 4-pole, 100 Amps capacity, housed in sheet-metal enclosure, complete as specified and directed by the Engineer-in-Charge. |
| 77 | Supply and fix ON-LOAD change-over switch, 415 V, 4-pole, 200 Amps capacity, housed in sheet-metal enclosure, complete as specified and directed by the Engineer-in-Charge. |
| 78 | Supply and fix ON-LOAD change-over switch, 415 V, 4-pole, 250 Amps capacity, housed in sheet-metal enclosure, complete as specified and directed by the Engineer-in-Charge. |
| 79 | Supply and fix ON-LOAD change-over switch, 415 V, 4-pole, 400 Amps capacity, housed in sheet-metal enclosure, complete as specified and directed by the Engineer-in-Charge. |
| 80 | Material and labour for earthing complete with galvanised steel earth plate electrode 600 mm × 600 mm × 6 mm thick, buried directly in ground vertically in an earth pit not less than 2.25 m deep below normal ground level, with the top edge of the plate not less than 1.5 m below ground level. Electrode shall be connected to GI earth strip 32 × 6 mm using galvanised bolts, nuts, check nuts and washers. Work includes provision of charcoal and salt in alternate layers, 20 mm dia medium-grade MS watering pipe with funnel and wire mesh, PCC 1:2:4 type B-1 pit enclosure with XPM reinforcement not less than 4 kg/sqm, and earth pit cover.Includes returning, filling, removal of excavated soil, making good disturbed surfaces such as hard-standing areas, including refixing removed precast concrete interlocking paver blocks to match existing surfaces, complete after taking out old/unserviceable earthing and testing on completion, all as specified in Electrical Plate No. 3 of SSR Part-I and as directed by the Engineer-in-Charge. |
| 81 | Material and labour for galvanised iron earth strip 32 × 6 mm, buried in ground or fixed on walls/floors using suitable GI saddles and screws, beyond the initial 7.5 m length of earth lead, and connecting to the test point after removing old/unserviceable strip, complete as specified and directed by the Engineer-in-Charge. |
| 82 | Supply and fix test-point terminal block for connecting the earth pit to down-conductor/earth strip, made of gun-metal or phosphor-bronze, size 75 × 75 × 25 mm, drilled and tapped, including fixing with three numbers of 8 mm dia, 25 mm long hex-head screws, after removing old/unserviceable one, complete as specified and directed by the Engineer-in-Charge. |
| 83 | Supply and fix in replacement Solar LED standalone street light of 45 Watts, system voltage 24 V DC, minimumefficacy 120 lumen/watt (minimum total output ≥ 5400 lumens), with in-built MPPT charge controller and SCC. System shall include SPV panel 200 Wp (2 × 100 Wp), low-maintenance lead-acid tubular battery 120 Ah (2 × 60 Ah), and hot-dip galvanised tubular pole 6 m height above ground level with base plate and clamps. Item includes all accessories; pole/box with clamp painted with one coat of red oxide and two coats of synthetic enamel paint (blue/silver), and taking down existing battery box, complete all as specified.Note: Earthwork and PCC foundation shall be measured and paid separately. |
| 84 | Supply and fix in replacement mild-steel solar street-light battery box of 5 mm to 10 mm thickness, surface-finished, rectangular type, single phase, weight up to 10 kg, fixed to pole with 25 × 5 mm MS clamp, both battery box and clamp painted with one coat of red oxide and two coats of synthetic enamel paint (blue/silver), including taking down existing battery box, complete all as specified. |
| 85 | Taking down carefully street-light, flood-light, post-top or high-mast light fittings of any capacity from 40 W to 200 W, for repair or replacement, and refixing the same after completion of all repair work, complete as specified and directed by the Engineer-in-Charge.Note: Spares shall be measured and paid separately. |
| 86 | Supply only LED driver of 40/45 W LED Street light/Post top/Flood light fitting complete as specified.. |
| 87 | Supply only LED driver of 60/72 W LED Street light/Flood light fittingcomplete as specified.. |
| 88 | Supply only LED driver of 90 W LED Street light/Flood light fitting complete as specified.. |
| 89 | Supply only LED driver of100 W LED Flood light fitting complete as specified.. |
| 90 | Supply only LED driver of 160 W LED Flood light fitting complete as specified.. |
| 91 | Supply only LED driver of 200 W LED Flood light fitting complete as specified.. |
| 92 | Supply and fix in replacement PVC-insulated, PVC-sheathed, multi-stranded flexible copper conductor cable of size 2.5 sqmm × 3-core, drawn through existing conduit/pipe from junction box to fitting, including taking down old unserviceable cable, complete as specified and directed. |
| 93 | Material and labour for replacement of solar street-light hot-dip galvanised tubular pole, 80 mm diameter, 7.5 m long, complete with cast-iron base plate, finial taper plug, bolts, nuts and screws, applying one coat of steel primer and two coats of aluminium paint, and marking pole serial number as per existing sequence. Includes taking out old corroded or broken pole by cutting or digging, complete as specified and directed by the Engineer-in-Charge.Note: Earthwork and PCC foundation shall be measured and paid separately. |
| 94 | Material and labour for replacement of post-top lantern GI tubular pole, 50 mm diameter, 5 m long, applying one coat of steel primer and two coats of synthetic enamel paint (block colour), and marking pole serial number as per existing sequence. Includes taking out old corroded or broken pole by cutting or digging, complete as specified and directed by the Engineer-in-Charge.Note: Earthwork and PCC foundation shall be measured and paid separately. |
| 95 | M&L PCC 1:4:8, type D2 (using 40 mm graded granite stone aggregate) as in foundations, filling and mass concrete for steel pole complete all as specified. |
| 96 | Material and labour for replacement of steel tubular swaged pole, Type 410 SP-22, 8.5 m long, complete with cast-iron base plate, finial taper plug, bolts, nuts and screws, including applying one coat of red-oxide zinc-chrome primer and two coats of aluminium paint, and marking pole serial number as per existing number. The item includes taking out old unserviceable/broken pole by cutting or digging, complete as specified and directed by the Engineer-in-Charge. |
| 97 | Supply and fix in replacement GI pipe street-light bracket, 40 mm dia, 1 m long, bent to required shape, fixed to pole/wall using two numbers of flat-iron clamps 40 × 6 mm with nuts and bolts, including making all electrical connections and taking down the old bracket, complete as specified and directed. |
| 98 | Material and labour for TMT bars/mild-steel angle cross arms, bracings, supports, clamps and back plates fabricated from structural-steel sections, including nuts, bolts, washers, welding, cold/hot bending, and drilling of bolt holes, in any shape or size as indicated, complete with one coat of primer, one under-coat of aluminium paint and one finishing coat of aluminium paint (for supporting frames for flood-light fittings), all as specified. |
| 99 | Scraping old paint from steel/HDG tubular poles 5 m to 7.5 m above ground level, including street-light arms, applying one coat of steel primer and two coats of synthetic enamel paint (block colour for post-top lantern poles and blue colour for solar street-light poles). Includes marking pole numbers serially with 60-mm yellow-circle base sticker and radium-lettered white pole number, placed 150 cm above benching, complete as directed by the Engineer-in-Charge. |
| 100 | Supply and fix in replacement PVC-insulated, stranded copper conductor cable 2 × 2.5 sqmm + 1 × 1.5 sqmm, for connection from FRP looping box to street-light fitting connector, passing through the steel tubular pole, including all fixing arrangements and taking down old unserviceable wiring, complete as specified and directed. |
| 101 | Supply and fix in replacement FRP junction box, readymade, size 300 × 200 × 110 mm, with four-way connector blocks suitable for terminating up to 35 sqmm × 3.5-core cable (two numbers), complete with appropriate cable gland, thimbles, nuts and washers. Junction box shall be supported with flat aluminium clamps not less than 25 mm × 3 mm, fixed with suitable nuts, bolts and washers inside and outside the looping box. Includes fixing to electric pole and removal of old unserviceable box of any type, complete as directed. |
| 102 | S&F in replacement ofMCB TPN 32 Amp 10 kA, 415 V, 50 Hz, AC complete. |
| 103 | S&Fin replacement of MCB TPN 63 Amp 10 kA, 415 V, 50 Hz, AC complete. |
| 104 | S & F in repairs of Timer switch 3 phase, 63 Amps capacity 01 No including power contactor nominal rating 25 A- 02 No with all accessories as suitable for existing complete all as specified and directed . |
| 105 | Supply and fix in repairs LED flood-light fitting 150 W, minimum 120 lumen/watt efficiency, with secondary optics, pressure die-cast aluminium housing, aluminium extrusion heat sink, and IP66 protection, complete as specified and directed. |
| 106 | Supply and fix in repairs LED street-light fitting 120 W, minimum 120 lumen/watt efficiency, with secondary optics, pressure die-cast housing, aluminium-extrusion heat sink, and IP66 degree of protection, complete as specified and directed. |
| 107 | Supply and fix in repairs LED street-light fitting 70 W, minimum 120 lumen/watt efficiency, with secondary optics, pressure die-cast aluminium housing, aluminium-extrusion heat sink, and IP66 protection, complete as specified and directed. |
| 108 | Taking down old unserviceable post-top light fitting of any make or wattage and supplying and fixing LED post-top lantern 40 W, minimum 120 lumen/watt efficiency, made of cast aluminium with decorative opal polycarbonate diffuser and IP65 protection, complete as specified and directed. |
| 109 | Taking down old unserviceable post-top light fitting of any make or wattage and supplying and fixing LED post-top lantern 25 W, minimum 120 lumen/watt efficiency, made of cast aluminium with clear opal acrylic diffuser and IP65 protection, complete as specified and directed. |
| 110 | Taking down old unserviceable post-top light fitting of any make or wattage and supplying and fixing LED post-top lantern 45 W, minimum 120 lumen/watt efficiency, made of cast aluminium with innovative glare-free indirect lighting distribution and IP65 protection, complete as specified and directed. |
| 111 | Taking down old unserviceable bollard/garden light fitting of any make or wattage and supplying and fixing LED bollard light 9 W, minimum 120 lumen/watt efficiency, having high-impact-resistant and durable body, ingress-protected design, easy installation, and soft uniform illumination, complete as specified and directed. |
| 112 | Taking down old unserviceable LT panel and Supply, install, test and commissioningOutdoor type LT Pannel Board of size ( 1.75 mtr length x 0.55 mtr width x 1.50 mtr height) at Near RC Chamber ,CPRI approved cubical type made out of 2.0 mm thick CRCA sheet confirming to IS - 8623 totally enclosed double door hinged type front & rear opening weather dust and vermin proof with canopy slope top, powder coated painting, locking arrangement, entry holes and glands of suitable size for incoming / outgoing cables mounted on including MS angle iron stand fabricated out of 40 mm x 40 mm x 6 mm angles, copper Bus-bar 600 A capacity, internal copper control wiring of suitable size for instrument / indicators etc, suitable size of copper strip for power connections from Bus-bar, Multifunction meter - 01 No, RYB Indicating Lamps - 1 Set, complete including the following complete all as specfied and directed by Engr-in-charge.(i) S&F MCCB 4 Pole 400 Amps 415 Volts 36 KA - 01 No (Incoming) (ii)S&F MCCB 4 Pole 200 Amps 415 Volts 36 KA- 01 No (Outgoing)(iii)S&F MCCB 4 Pole 100 Amps 415 Volts 25 KA -02 Nos (Outgoing)(iv)S&F MCCB 4 Pole 63 Amps 415 Volts 16 KA-04 Nos(outgoing) |
| 113 | Taking down old unserviceable LT panel and Supply, install, test and commissioningOutdoor type LT Pannel Board of size ( 2.70 mtr length x 0.55 mtr width x 1.50 mtr height) at Back side of,CPRI approved cubical type made out of 2.0 mm thick CRCA sheet confirming to IS - 8623 totally enclosed double door hinged type front & rear opening weather dust and vermin proof with canopy slope top, powder coated painting, locking arrangement, entry holes and glands of suitable size for incoming / outgoing cables mounted on including MS angle iron stand fabricated out of 40 mm x 40 mm x 6 mm angles including provision of 2.70mtr x 0.35 mtrwidth steel sheet channel 2mm thick for mounting MCCB in panle box,internal copper control wiring of suitable size for instrument / indicators etc,, suitable size of copper strip for power connections from Bus-bar, Multifunction meter - 01 No, RYB Indicating Lamps - 1 Set, complete including the following complete all as specfied and directed by Engr-in-charge.(i) S&F MCCB 4 Pole 400 Amps 415 Volts 36 KA - 02 No (Incoming/Out going) (ii)S&F MCCB 4 Pole 200 Amps 415 Volts 36 KA- 02 No (Incoming/Outgoing)(iii)S&F MCCB 4 Pole 100 Amps 415 Volts 25 KA -06 Nos (Incoming/Outgoing)(iv)S&F MCCB 4 Pole 63 Amps 415 Volts 16 KA-04 Nos(Incoming/outgoing) |
| 114 | Taking down old unserviceable LT panel and Supply, install, test and commissioningOutdoor type LT Pannel Board of size ( 0.90 mtr length x 0.35 mtr width x 1.35 mtr height) at Near fire stn to CO house road ,CPRI approved cubical type made out of 2.0 mm thick CRCA sheet confirming to IS - 8623 totally enclosed double door hinged type front & rear opening weather dust and vermin proof with canopy slope top, powder coated painting, locking arrangement, entry holes and glands of suitable size for incoming / outgoing cables mounted on including MS angle iron stand fabricated out of 40 mm x 40 mm x 6 mm angles, copper Bus-bar 400 A capacity, internal copper control wiring of suitable size for instrument / indicators etc, suitable size of copper strip for power connections from Bus-bar, Multifunction meter - 01 No, RYB Indicating Lamps - 1 Set, complete including the following complete all as specfied and directed by Engr-in-charge.(i) S&F MCCB 4 Pole 200 Amps 415 Volts 36 KA - 01 No (Incoming) (ii)S&F MCCB 4 Pole 63 Amps 415 Volts 16 KA- 01 No (Outgoing)(iii)S&F MCB TPN 63 Amps 415 Volts 10 KA -02 Nos (Outgoing)(iv)S&F DP 0-32 Amps 240 Volts 10 KA-04 Nos(outgoing) |
| 115 | S&Fin replacement of MCCB TP 25 to 100Amp 16 kA, 415 V, 50 Hz, AC complete all as specified & directed. |
| 116 | S&Fin replacement of MCCB TP 125 Amp 16 kA, 415 V, 50 Hz, AC complete all as specified & directed. |
| 117 | S&Fin replacement of MCCB TP 200 Amp 36 kA, 415 V, 50 Hz, AC complete all as specified & directed. |
| 118 | S&Fin replacement of MCCB TPN 100Amp 16 kA, 415 V, 50 Hz, AC complete all as specified & directed. |
| 119 | S&Fin replacement of MCCB TPN 250Amp 36 kA, 415 V, 50 Hz, AC complete all as specified & directed. |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2025 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail