| 1 | Supply installation testing & Commissioning of high mast lightingsystem (as per PLG 07 of ILP UK techinical report no 7 of ILE UK/IS:875 Part-1 – 2015//BSEN10025/and IS:2062 )consisting of totallyhot dip galvanised by piecewise single dipped method high mast,lantern carriage suitable for up to 12 nos luminaries with welded arm(excluding luminares), mast head frame assembly with full cover,including 1 No. LED 15 Watts aviation obstruction lights, doubledrum type self sustaining winch, integral power tool accesible fromdoor with padlocking arrangement (winch motor with control circuit)hot dipped galvanised heavy duty pipe lightening finial, Stainlesssteel 6 mm dia. wire ropes (AISI 316, 7 / 19 costruction 3 no. ropefor lantern carrage & 2 no. rope for winch assembly ) foundation bolt,torque limiter,EPR insulated PCP sheathed 5 core x 2.5 Sq.mmtrailing cable, including outdoor type control panel for auto on / off,reverse / forward motor operation. The mast is constructed from mildsteel plates (as per IS 5986 Gr. 510 ) cut and folded to form apolygonal section, telescopic jointed and welding as per BS5135.etc. as required on Existing Foundation. ( See table P - 03 forspecs.) OEM Must have Type test certificate for wind tunnel test .All as per pre approved by Engineer in-charge. All as per preapproved by Engineer in-charge. For additional technicalparameters of products/ work , refer Annexure \"A\" attached withthis BSR . 20.0 Mtr Hm (in 2 section) suitable for 12 No. Luminaries |
| 2 | Providing & Fixing of IP-65 Protected LED aviation obstruction lightluminaire comprising of die cast aluminium alloy housingwithPolycarbonate enclosure having more than 200 No\"s Low PowerLED\"s having minimum power consumption 15 watts complete in allrespect. All as per pre approved by Engineer in-charge. Foradditional technical parameters of products/ work , refer Annexure\"A\" attached with this BSR . aviation obstruction LED light luminaire Min. 15 Watts |
| 3 | Providing & Fixing of IK08 IP-66 protected high power LED floodlight system with single piece Pressure diecast aluminium housing,toughened glass diffuser with suitable lenses on LED to achievevarious beam angles, of high power LED of 3 to 5 watt each .Integrated potted driver as a unique BIS R number having efficiencymore than 85 % and in compliance to BIS certified and Trade markcertificate. The System level Luminaire efficacy >=125 lm/ wt. LEDdriver Input Voltage AC 120 to 270 V AC with High voltage Cutoff@>=300 V AC and Auto resetting Safety .Power Factor >0.95 ,THD(I) <10% , driver current <=750mA. driver should be Phase tophase protection of 440 V for 4 Hrs. Electrical Connector , SurgeProtection Min >=4KV internal and 10KV external but inside drivercompartment, System life of 50000 Burning hours with 70% of InitialLumens maintained, CRI>70 and CCT 5700K ±355K.Manufactures Word Mark/Name Engraved/Embossing/Screenprinting on die cast housing to allow traceability/authenticity. Fixtureshall be IS 10322 Complianced.OEM Must have its own in houseNABL lab setup for all testing facilities for LED fixtures.(LM79/LM80) Certificate/ report with liable warranty ofproduct/accessories from OEM shall be submitted. All as per preapproved by Engineer in-charge. For additional technicalparameters of products/ work , refer Annexure \"A\" attached withthis BSR . High Power LED Flood Light Minimum lumen output 25000 lm |
| 4 | Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type ofload and site requirement) 4 KV impulse withstand voltage, ISImarked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC60947-2, low watt losses, trip free mechanisum , energy limiting ofclass 3 as per IEC, minimum phase termination capacity of35sq.mm. , conductor line load reversibility , IP 20 contact protectionand fitted in existing distribution board/sheets, minimum electricaloperation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80A & above rating including making connections, testing etc. asrequired. OEM shall have submit NABL / CPRI / ERDA accrediatedlab type test reports & All as per pre approved by Engineer incharge. For additional technical parameters of product / work referAnnexure \"A\" attached with this BSR Single pole MCB 6 A to 32 A rating |
| 5 | Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed UnArrmoured Aluminium cable confirming to IS:1554 P-I / IS :7098 P -I of 1.1 KV with H4- Grade electrolytic aluminium conductorconfirming to IS 8130 of purity >99.6 %, Inner / outer sheathconfirming to IS:5831 in existing RCC / Hume / Stoneware / PVCpipe/ open duct/cable trench / Cable tray (with cable tie) includingtesting etc. as required of following size. OEM must have it\"s own inhouse NABL accrediated Laboratory for testing procedure as perIS:10810. For additional technical parameters of product / work referAnnexure \"A\" attached with this BSR 16.0 Sq. mm 4 core |
| 6 | Providing & Fixing of mechanical / digital time switch havingfollowing day / week programme and minimum 100 hours reserveand AC1 rating of 16-20 amperes including making connection,programming conforming to IEC 60730-1 and 60730-2-7 etc. asrequired. All as per pre approved by Engineer in-charge. Foradditional technical parameters of products/ work , refer Annexure\"A\" attached with this BSR . One day reserve (Analog type ) |
| 7 | Providing & Fixing of AC operated heavy duty 230 /440 Volt powercontactor as per PWD specification for electrical Works, ISI markedIS/IEC 60947-4-1 : 2000 having provision of mechanical interlocking,auxilary contacts, Din rail mounting type including makingconnections, testing etc. as required. All as per pre approved byEngineer in-charge. For additional technical parameters of products/work , refer Annexure \"A\" attached with this BSR .4 pole Power contactors with following AC 1 Rating 16 Amp. |
| 8 | Providing & Fixing of 110/220 V, unibody LED Indicating lamp IEC60947 with integral circuit, IP 65 above panel & IP 20 terminalblock, Approx. body dia for panel not less then 20 mm, length min.50mm, front LED cover dia min. 29 mm, contact material phospherbronze for Led, PCB contacts shall be of brass (tin plated), impulsedielectric tested for 2.5 KV, Rated insulation resistance shall be 100M ohm at 500VDC including connection etc. as required. All as perpre approved by Engineer in-charge. For additional technicalparameters of products/ work , refer Annexure \"A\" attached withthis BSR . Red/yellow/Green colour |
| 9 | Blue / white Colour |
| 10 | Providing & Fixing of IS: 13875 & IEC :61326 confirming LED Digitaltype (up to 500) V range Volt meter / Direct- Ammeter / CT oertatedammeter/ Frequency meter / KWH meter / Multi Function Meter /Power analyzer of class 1 accuracy as per IS : 1248 of size 96mm x96 mm including making connection by PVC insulated copperconductor with PVC sleeves / channel etc. as required. All as perpre approved by Engineer in-charge. For additional technicalparameters of products/ work , refer Annexure \"A\" attached withthis BSR . Three phase AMP+HZ+PF+KW+KVA+KVAR+T.ENERGY+THD-I, THD-V & RUN HRS |
| 11 | Supplying and fixing of Aluminium (IEC 60105 ISO 209-1,2) /Copper (IEC 60028) bus bar by means of SMC / DMC type insulatorwith standard short circuit withstand capacity , high tensile nutsand bolts spring washers in existing panel including bending , cuttingin required shape and size and colour coding with heat shrinkablePVC sleeves. All as per pre approved by Engineer in-charge. Foradditional technical parameters of products/ work , refer Annexure\"A\" attached with this BSR . Electrolytic grade Aluminium bus bar 6010 grade |
| 12 | SITC of IP-42 and general construction confirming to IS:8623 : 1993,wall/ free standing floor mounted dust and vermin proofcompartmentalised cubical panel as specifications and Otherparameters required as per point (a) ,(b), (c),(d), (e), (f), (g), (h) asbelow:-(a)Thickness of CRCA sheet shall be 2.0 mm, cable alleycompartments having concealed hinged type doors with key typelock with / without detachable extension type structure. Removable3 mm. thick sheet steel gland plates with appropriate size ofknockouts for cables shall be provided(b)complete panel shall undergo a process of degreasing, Waterrinsing, Activation, derusting, pickling in acid bath, phosphatising &shall be subjected to nine tank process and then Powder coated withapproved shade of minimum 70 microns on both side of panel. Thepanel having PE foam/ Neoprene rubber gasket of not less than3mm thickness ,required hardware , concealed hinged door with keytype locking arrangement for equipment/switchgear earthed with 2.5sq.mm braided copper wire.[c) Interconnection between bus bar and switchgears /cable shallbe rigidly supported and made out by flexible copper wires (up to 63amp ) and by solid bus bar (>63 amp ) . control wiring will be carriedout with 1.5 Sq.mm, Earth wire with 2.5 Sq.mm and CT with 2.5sq.mm flexible copper wire only. All joints / interconnections ofcopper bus bar shall be dully tinned . Clearance between main busbar and risers / metal parts shall be at least 10 mm additional towidth of bus bar Bus bar is insulated by Heat Shrinkable sleeves .Earth and Neutral bus bar shall be half of the size of phase bus bar.( Cost of Bus bar / Flexible wire for Interconnection between Mainbusbar and Switchgear is to be Paid Extra )(d)Wiring between components within switchgear and Incoming /outgoing cable shall be done through the terminal block only. Directconnection shall not be permitted. Each terminal block shall be onepiece moulded, barrier type, 650 volt grade, complete with washers,heads, studs with two nuts and identification strips and shall haveadequate continuous current rating. For tap-offs, adjacent terminalswith shorting strips shall be used. 10% Spare terminal blocks shallbe provided. Wire identification on marking strip shall correspond tothe designation of the wiring diagrams. All wire terminals on theequipment shall also be marked with designation corresponding tothose of the wiring diagram.(e)All wiring shall be enclosed in plastic channels and neatlybunched and closed in metering chamber, Wiring between terminalsof various devices shall be ‘point to point’ (no wire splitting or teeconnections) with wires neatly trucked along the back of the panels,adequately supported to prevent sagging.(f)Floor mounted panel shall be mounted on Base frame of ISMCchannel size 100 x 50 x 5 mm ( to be paid Extra )(g) Tests: The insulation resistance (with 1000 V Megger) and Highvoltage Power frequency test (by applying a voltage of 2.5KV for oneminute) shall be measured between phases, between phase andneutral and between phase and earth. both before and after highvoltage power frequency test. The insulation resistance shall not beless than three megaohm. CT Secondary current injection test shallalso be carried out.(h) only outer surface area on all sides shall be measured & panel tobe fabricated only from CPRI approved fabricator only (CPRI Testcertificates to be submitted)All as per pre approved by Engineer incharge. For additional technical parameters of products/ work , referAnnexure \"A\" attached with this BSR . |
| 13 | Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type ofload and site requirement) 4 KV impulse withstand voltage, ISImarked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC60947-2, low watt losses, trip free mechanisum , energy limiting ofclass 3 as per IEC, minimum phase termination capacity of35sq.mm. , conductor line load reversibility , IP 20 contact protectionand fitted in existing distribution board/sheets, minimum electricaloperation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80A & above rating including making connections, testing etc. asrequired. OEM shall have submit NABL / CPRI / ERDA accrediatedlab type test reports & All as per pre approved by Engineer incharge. For additional technical parameters of product / work referAnnexure \"A\" attached with this BSR Four pole MCB (With B/C curve tripping Characteristics) 40 A rating |
| 14 | Plate Earthing as per IS:3043 with Hot dipped G.I. Earth plate ofsize 600mm x 600mm x 6.0mm by embodying 3 to 4 mtr. below theground level with 20 mm dia. G.I. \"B\" class watering Pipe ,includingall accessories like nut, bolts, reducer, nipple, wire meshed funnel,and Heavy duty weather proof poly-propylene earth pit chamber withlockable Jam free lid suitable for safe working load 5000 Kg or moreof size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. andHeight 250 to 300 mm. and embodying the pipe complete withalternate layers salt and coke/ charcoal, testing of earth resistancefor value of 5 ohms or less as required & must record by engineerin-charge during site visit and ensure to enter in measurmentbook.All as per pre approved by Engineer in-charge. For additionaltechnical parameters of products/ work , refer Annexure \"A\"attached with this BSR . |
| 15 | Supply and Fixing GI flat (25x6mm) Strip. Having width- 25mm,Thickness- 6mm, Material- Hot dipped Galvanized Iron, Coatingthickness- Avg. 70 microns. & Complied as per IEC 62561-2 GI stripholder of material- Dow moulded compound, at spacing of 0.5 Mtr.having height- 19mm, Slot Size- 25x6 mm Etc. as required.All as perpre approved by Engineer in-charge. For additional technicalparameters of products/ work , refer Annex ure \"A\" attached withthis BSR . |
| 16 | Earth work in excavation in foundation, trenches etc. including dressing of sides and ramming of bottoms, including getting out the excavated material, refilling after laying pipe/ foundation and disposal of surplus excavated material at a lead upto 50m suitable site as per direction of Engineer for following depths, below natural ground / Road top level.In all types soils/ saturated soil such as moorum, sand, sandy silt, clay, black cotton soil, kankar, etc.Depth upto 1.5 m |
| 17 | Earth work in excavation in foundation, trenches etc. including dressing of sides and ramming of bottoms, including getting out the excavated material, refilling after laying pipe/ foundation and disposal of surplus excavated material at a lead upto 50m suitable site as per direction of Engineer for following depths, below natural ground / Road top level.In all types soils/ saturated soil such as moorum, sand, sandy silt, clay, black cotton soil, kankar, etc. Add extra for overall depth of excavation above 1.5 m and upto 3.0m over item no 4.10.1.1 |
| 18 | Providing and laying in position cement concrete of specified grade excluding the cost of centring and shuttering - All work upto plinth level : 1:4:8 (1 Cement : 4 fine/ coarse sand : 8 graded stone aggregate 40 mm nominal size). |
| 19 | Centring and shuttering with plywood or steel sheet upto two stories or height upto 7.5 metre above plinth level including strutting, propping etc. and removal of form for : |
| 20 | Reinforcement for R.C.C. work at all levels including straightening, cutting, bending, placing in position and binding all complete. Thermo-Mechanically Treated bars |
| 21 | Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. upto two stories excluding cost of centring, shuttering, finishing and reinforcement : 1:1:2 (1 cement : 1 coarse sand : 2 graded stone aggregate 20 mm nominal size) (As per design mix) Please Enable Macros to View BoQ information |