| 1 | M&L for Servicing of Terrace Booster Pump including, Oiling/ Greasing of Gland, Checking Supply Connection from Starter Kit & Making Sure of Free Rotation of Gland complete all as specified and directed. |
| 2 | M&L for Repairing of Terrace Booster Pump Starter Kit complete all as specified and directed. |
| 3 | M&L for servicing of Jockey Pump, which Includes, Checking Connections, Checking Automation Settings for ON & OFF Function, Oiling & greasing, complete all as specified and directed. |
| 4 | Supply & Installation of Hose Reel Plastic Nozzle with Two Modes of Jet Spary Systemin replacement of old U/s Nozzle complete all as specified and directed. |
| 5 | Supply & Installation of 15 metre long, 63mm dia Reinforced Rubber Lined (RRL) hose conforming to IS 363 Type A with SS instantaneous couplings conforming to IS 903 and Hoses shall be stored in side the hose cabinetin replacement of old U/s RRL complete all as specified and directed. |
| 6 | Supply & Installation of SS Short Branch Pipe with 20 mm Dia Nozzle in place of old unserviceable pipe confirming IS 903in replacement of old U/s pipe complete all as specified and directed. |
| 7 | Supply & Installation of 50 metre Rubber Hose Pipein place of old unserviceable pipe complete all as specified and directed. |
| 8 | Supply & Installation of Hydrant Valve Female Coupling Commercialin place of old unserviceable valve complete all as specified and directed. |
| 9 | Supply & Installation of SS Opaque Type 63 mm Dia Cast Iron ISI Marked Hydrant Valves with Proper Fittingsin place of old unserviceable valve complete all as specified and directed. |
| 10 | Supply & Installation of Double Door Hose Box Cabinet with Proper Frame to Mount which Includes proper Grouting using Concretein replacement of old U/s hose box complete all as specified and directed. |
| 11 | Supply & Installation of 25 mm Ball Valve completein replacement of old U/s valve complete all as specified and directed. |
| 12 | Supply & Installation of Hydrant Valve Cast Iron Hand Wheelin replacement of old U/s valve complete all as specified and directed. |
| 13 | Supply & Installation of Hydrant Washersin replacement of old U/s washer complete all as specified and directed. |
| 14 | Supply& Installation of Cap & Chainin replacement of old U/s complete all as specified and directed. |
| 15 | Supply & Installation of Keysin replacement of old U/s keys complete all as specified and directed. |
| 16 | Supply& Installation of Key Glass in replacement of old U/s ccomplete all as specified and directed. |
| 17 | Supply & Installation of Cabinet Glassin replacement of old U/s complete all as specified and directed. |
| 18 | Supply & Installation of 4 Way Black Capsin replacement of old U/s complete all as specified and directed. |
| 19 | M&L for dismantling the existing unserviceable under mentioned sluice valve from the existing pipe line & handed over to contractor as sch of credit andS&F sluice valve CI body ISI marked high pressure class PN 1.6 heavy duty with flanged ends cast iron wheel with SS spindle (ISI marked) conforming to IS:14846-2000, short body all as specified including nuts, washers and gasket complete all as specified and directed.a) Size 63mm dia Bore |
| 20 | b) Size 80mm dia Bore |
| 21 | c) Size 100mm dia Bore |
| 22 | d) Size 150mm dia Bore |
| 23 | Taking up damaged / broken Cast Iron water main (including all fitting) with spigot and socket ends and lead joints including burning out joints and recovering lead etc for:-(a) 100 mm bore |
| 24 | (b )150 mm bore |
| 25 | Material and labour for cast iron pipes with spigot and socket ends centrifugally cast class \"LA\" in any required length laid in trenches for :- (a) 100 mm bore |
| 26 | (b )150 mm bore |
| 27 | Taking out the unserviceable lead joints including spun yarn and M&L for run lead joint for spigot and socket pipes and fittings of following sizes :-(a) 80 mm bore |
| 28 | (b) 100 mm bore |
| 29 | (c) 150 mm bore |
| 30 | M & L for cutting the existing cracked CI / DIpipe line and M&L for fixing of mechanical joint made of CI / MS incl with tyton rubber ring , nut, bolts / stud , washer etc complete suitable forfollowing dia pipes. (a) 80 mm bore |
| 31 | (b) 100 mm bore |
| 32 | (c) 150 mm bore |
| 33 | M&L for Dismantalingof existing main squirrel cage induction motor pump setby uncruwing/cuttingnut bolts,cable connections ,earth connectinons and trasportation to workshop for periodical maintenance /servicing of motor pump set including varnishing of winding with graded varnish ,heating of winding in oven at specified tempreture and dehydrate the winding complete.greasing of bearing and bushing ,scraping of old paint, prepairing the surface by using redoxide primer and paiting of motor as per colour code and mark the MES/SM number.Split opening of pump ,checking of bearing /busing impellers ,greasing of bearing /busing ,empellar replace whether required as existedand assembling complete motor pump set by replacement of nut bolts gland packing ,papper packing ,etc. and testing complete all as specified and directed :-(a) squirrel cage induction motor pump 40 HP (Location At Point Auditorium) |
| 34 | All as per item hereinabove but for squirrel cage induction motor pump 50 HP (Location At Point Auditorium) complete all as specified and directed |
| 35 | All as per item hereinabove but for Jackey pump 15 HP (Location At Point Auditorium, New Multi Pump House) complete all as specified and directed |
| 36 | All as per item hereinabove but for squirrel cage induction motor pump 60 HP (Location At New Multi Pump House) complete all as specified and directed. |
| 37 | All as per item hereinabove but for squirrel cage induction motor pump 5/7.5 HP complete all as specified and directed. |
| 38 | Supply and fix in repairs water pressure gauge along with stop cock of same size, necessary GI fittings and making hole at new place if required on GI/MS/CI pipe at places complete all as specified and directed. |
| 39 | M & L for rendering1:4 cement plaster 15 mm thick on fair faces of brick work or concrete surfaces complete all as specified and directed. |
| 40 | M & L for two coats of white wash on new surfaces including primmer and preparation of surfaces complete all as specified and directed. |
| 41 | Supply and replace existing defective single function voltmeter 3 phase digital type (0 to 500) complete all as specified and directed. |
| 42 | Supply and replace existing defective single function digital 3 Phase 3 Line AC Ammeter CT Selectable complete all as specified and directed. |
| 43 | Supply and replace existing defective phase indication lamps in panel at pump house complete all as specified and directed. |
| 44 | M&L for PCC 1:4:8 Type D2 (40mm graded) in foundations, filling and mass concrete complete all as specified and directed. |
| 45 | M&L for pre-cast cement concrete block masonary with solid blocks exc.10 cm in width and setting in mortar complete (Type C1 - 1:3:6) complete all as specified and directed. |
| 46 | M&L for Surface Dressing n.exc 15 cm deep and getting out green vegetation, roots etc around pump house/ OHT / 2 Pole/4 Pole structure etc complete all as specified and directed. |
| 47 | M & L for painting double coat AS PER COLOR CODING complete all as specified and directed for following items:-(a) Panels |
| 48 | (b) 100/150 mm CI Pipe |
| 49 | (c) 80 mm / 50mm/ 40 mm GI pipe |
| 50 | (d) Pumps of any capacity |
| 51 | Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5 m in depth and getting out in soft loose soil complete all as specified and directed. |
| 52 | Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5 m in depth and getting out in hard dense soil complete all as specified and directed. |
| 53 | Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25cm complete all as specified and directed |
| 54 | Removing excavated material not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed |
| 55 | Taking up or down GI tubing & connectionsin trenches, wall / floor including cleaningfor removal to store complete all as specified and directed of size:-(a) 80 mm bore pipe |
| 56 | (b) 50 mm bore pipe Note :- (a) to (b) Excavation & earth work shall be measured & paid separately. |
| 57 | Supply and laying tubes, Galvanised,\"medium \" grade, with all fittings and fixed to walls, ceiling or laying in floors,trenches complete all as specified for following size:-(a) 80 mm bore pipe |
| 58 | (b) 50 mm bore pipe |
| 59 | Supply & fixing Gun metal gate /globe valve ISI markedwith iron wheel head, screwed both ends for iron pipe including taking up or down unserviceable Gun metal globe /gate valve of following size:-(a) 80 mm bore pipe |
| 60 | (b) 50 mm bore pipe |
| 61 | Supply & fix in repairs cast iron bends (any radius and angle) tappers any type (Straight, Bend, increasing, decreasing or double socket). Tee pieces single branch. \"Y\" junction, double bernach, cross (all socket or socket spigot) collars, caps, caps & plugs for 80mm to 150 mm dia cast iron pipes with spigot and sockets end complete all as specified and directed |
| 62 | M & L for PCC 1:2:4 type B2 using for drain wall make good the damage surface & floor road etc complete all as specified and directed |
| 63 | M&L for plastering to valve pit chamber with 1:4 cement plaster rendering 10 mm thick on fair faces of brick work or concrete surface complete all as specified and directed |
| 64 | M & L for valve pit chamber internal dimension of 900 x 900 x 900mm built in brick masonry in cement mortar (1:6) including waster concrete PCC (1:4:8) mixed type D2 100mm thick. Plastering to brick work cement mortor 1:6. 15mm thick internally and externally including provision of 3.15mm thick MS sheet cover fixed with angle iron frame of size 50x50x6 abandon in PCC 1:2:4 mixed type B-1 including copping of 100mm thick with PCC 1:3:6 type C2 painting to steel and iron work two coat of synthetic enamel paint over one coat of red oxide of primer necessary earth work and excavtion in any type of soil complete with locking arrangement all as specified. Inclusive of dismantling of existing damage valve pit chamber and disposed of the retrieved material complete all as specified and directed. |
| 65 | M&L for repair to existing valve pit chamber, plastering to brick work / solid block masonary work cement mortar 1:6, 15 mm thick internally, removing damage / defective angle iron frame including sheet cover, repair coking with 1:3:6 - 10 mm thick including provision of 3 mm thick MS sheet cover fixed with angle iron frame of size 50 x 50 x 6 mm embedded in PCC 1:2:4 type B-1. Painting to steel and iron earth with coat of syntheticenamel paint over one coat of red oxide primer complete with locking arrangement complete all as specified and directed |
| 66 | Supply and fix in replacment of damaged rubber or fibre board gaskets for flanged joints complete all as specified and directed of following size of pipes:(a) 80 mm dia |
| 67 | (b) 100 mm bore |
| 68 | (c ) 150 mm bore |
| 69 | Dismantling the unserviceablesluice valve and Repair / servicing by opening stuffing box, MS Nut, Bolts etc. for replacement and repairing of spindle, check nut etc and reassembling repaired sluice valve and making functional and refixing the same including replacement of Gasket, Gland Packing etc of complete all as specified and directed of following:-(a) size 100 |
| 70 | (b) size 150 mm |
| 71 | (c)size 80 mmNote for item No 52.00(a) to (c):- Parts of the sluice valve shall be measured and paid for seperately under relevant items. Howeverunit rate is deem to be included for replacement of rubber gaskets, gland packing of required size and replacement of unserviceable nuts, bolts and washers. |
| 72 | Supply and fix stainless steel spindle with check nut / Hub nut (Gun Metal) and collars suitable for existing sluice valve of following size of any make complete all as specified and directed of following :-(a)150 mm |
| 73 | (b) 100 mm |
| 74 | (c) 80 mm |
| 75 | Supply only of following items complete all as specified and directed :-(a)Glands rope for packing (6 mm to 18 mm) |
| 76 | (b) Lead Wool |
| 77 | Supply and replacement of male, female coupling (valve caps) made out of cast iron body and mounted on sluice valves for operating spindle of sluice valves of sizes from 80 mm to 150 mm dia complete all as specified and directed. |
| 78 | Supply and fixing of sluice valve operating rod made out of 30mm dia solid MS rod one side duly welded with female copling of sluice valve complete all as specified and directed.Note : Sluice valve female coupling will be supplied under relevant item of this schedule. |
| 79 | M&L for dewatering & Cleaning of the under ground tank for water and removing accumulated silt / sludge from bottom of sump (Approx 20-30 cm thick) along with foreign materials including dewatering of the sump well complete and removing to a distance exceeding 50 m but not exc. 100m including cleaning and watering rubbing with coir brush for walls and bottom of the reservoir with fresh water by adding bleaching powder for disinfection(approximate area not exc. 450 Sqm), clean the all valve pit chamber by removing mud dust internally and remove grass/vegetation up to 30 cm all side of valves pit chamber. clean valves and chamber cover and apply one coat of red enamal paint to the cover and black enamel paint over valves body marks with white paint and including white washing with one coat of lime andpainting the date of cleaning, due date of cleaning and capacity of tank andrepair to the water tank etc complete all as specified and as directedatFire Pumping Station, Points Auditorium DIAT (DU) Girinagar, Pune - 25. |
| 80 | All as per item hereinabove but for water (storage tank) at Main Building basement (Technical Area)Girinagar, Pune - 25. |
| 81 | All as per item hereinabove but for water (RCC storage tank for Each building) at New Multi Girinagar, Pune - 25. |
| 82 | All as per item hereinabove but for water (RCC storage tank for Each building) at Points hostel DIAT Girinagar, Pune - 25. |
| 83 | S&F MCCB 250 Amps 3P, 36 KA in replace of old unserviceable MCCB complete all as specified and directed. |
| 84 | S&F MCCB 125 Amps 3P, 25 KA in replace of old unserviceable MCCB complete all as specified and directed. |
| 85 | Supply and fixing in repairs L&T FASD STARTER, relay range not less than 75A, 3 Phase, ML4 FASD*, coil voltage 380 V maximum motor rating at 3 phase, 415 V, 50 Hzcomplete all as Specified and directed. |
| 86 | Supply and fixing in repairs fully automatic details delta starter ML 6 FASD, relay range not less than 110Amp, AC1 125A, AC3 110 A, coil voltage 380 V; maximummotor rating at 3 phase, 415 V, 50 Hz complete all as Specified and directed. |
| 87 | Supply and fixing in repairs fully automatic details delta starterMK2 DOL, relay range not less than 32 Amp coil voltage 380 V;motor rating at 3 phase, 415 V, 50 Hz complete all as specified and directed. |
| 88 | Supply and fixing in repairs fully automatic details delta starter MU2 DOL, relay range not less than 38 Amp coil voltage 380 V;motor rating at 3 phase, 415 V, 50 Hz complete all as specified and directed. |
| 89 | Supply and fix non return valve, both end flanged, CI body of class 1.0 PN including dismantling old u/s non return valve complete all as specified & directed of following sizes: -(a) 150 mm dia |
| 90 | (b) 63 mm dia |
| 91 | Refilling cost of 6 KG ABC Fire Extinguisher complete all as specified & directed. |
| 92 | Supply & Installation in repairs cost of 4.5 KG CO2 Fire Extinguisher complete all as specified & directed. |
| 93 | Supply & Installation in repairs cost of 6 KG ABC Fire Extinguisher complete all as specified & directed. |
| 94 | Supply & Installation in repairs cost of 4 KG ABC Fire Extinguisher complete all as specified & directed. |
| 95 | Refilling cost of 4 KG ABC Fire Extinguisher complete all as specified & directed. |
| 96 | S&F in repairs 15mm thick suitable size MS sheet cover for valve pit chamber fixed with angle iron frame of suitable size complete all as specified & directed. |
| 97 | M & L for Rectifing defects of Fire water pipelines , pumping/supply mains GI/CI/DI pipelines alongwith fittings/valves of any sizes50 mm to 150 mm complete removing, cleaning and refixing including replacement of the unserviceable parts complete all as specified and directed. Note:- (i) Rate for any fittings and other items for rectifying defects shall be measured and paid under respective item of schedule.(ii) All tools required for carrying out the works shall be deemed to be including in the quoted rate.(iii) The above work shall be carried out on requirement basis on complaints received in the MES service centre. |
| 98 | ML forfor conduct weekly fire drill at various locations of DIAT (DU)& MILIT in the presence of rep of MES and keep in recored complete all as specified and directed. |
| 99 | Supply only clean agent gas 45Kg Capacity including clamping, bolts/ Nuts/ washers complete all as specified and directed. |
| 100 | Supply only Master Valve required as on site complete all as specified and directed. |
| 101 | Supply only 150 Bar Brass Co2 slave Valve for 45 kg Cylinder complete all as specified and directed. |
| 102 | Supply only 1/2\"PVC Lay Flat Water Pump Discharge Hose With Aluminum Pin Lug Fittings, Heavy Duty Reinforced Pool Backwash Hose Assembly complete all as specified and directed. |
| 103 | Supply only only Brass NRV 1/2 Inch (Non Return Valve 1/2 Inch) including all required fittings complete all as specified and directed. |
| 104 | Supply only Interconnecting hose 1/2\"\"With Aluminum Pin Lug Fittings, Heavy Duty Reinforced Pool Backwash Hose Assembly complete all as specified and directed. |
| 105 | Supply only Cylinder Battery Frame with manifold complete all as specified and directed. |
| 106 | Supply onlySafety relief valve as required at site complete all as specified and directed. |
| 107 | Supply onlyBleeder valve 1/2\"\" dia complete all as per specified and as directed. |
| 108 | Supply onlyPressure Switch required as per site or as per Engr-in-charge complete all as specified and directed. |
| 109 | Supply only Discharge Nozzle as per required on site complete all as specified and directed. |
| 110 | Supply only smoke detector complete all as specified and directed.Make Ravel Cat No. Smoke d--RE-326S2L or equivalent. |
| 111 | Supply only Fully Automatic Abbort Manual Call Point Operating Voltage 24VDC,IP-50, Operating Current 30mA, color MCP Yellow complete all as specified and directed. |
| 112 | Supply only Fully Automatic Emergency Release Manual Call Point Operating Voltage 24VDC, IP-50, Operating Current 30mA, color MCP Green complete all as specified and directed. |
| 113 | Supply only Hooter Mini Horn with BackBox, Operating Voltage 24V DC, Operating Current 40mA, Sound Level 85dB@1m, Operating Temperature 0 – 49° C / 32-120° F, Sounder Type - Piezo Electric Type, Tone Type- Fire Engine Siren, Material : ABS Plastic, Colour : Red Dimensions : 96 H mm X 76 L mm X 28 D mm, Back Box : 95 H mm X 75 L mm X 58 D mm, Mounting Type : Surface / Flush Mount complete all as specified and directed. |
| 114 | Supply, Installation, testing & commissioningof 2 Zone Gas Release Fire Alarm Panel, Display size 16 x 2 LCD Dot Matrix Display, Power Source 120 - 220V AC, 60 / 50 Hz, Standby Time 24V DC, complete all as specified and directed. |