Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | Stage 1 upto Plinth SURFACE EXCAVATION N.EXC (NOT EXCEEDING) 30 CM DEEP AND AVERAGING 15CM DEEP AND GETTING OUT IN SOFT/LOOSE SOIL. |
| 2 | EXCAVATING IN TRENCHES, N EXC 1.5 M WIDE AND N EXC 1.5 M IN DEPTH; FOR FOUNDATION, ETC. OR FOR SHAFTS, WELLS, CESSPITS, MANHOLES, PIER HOLES, ETC. N EXC 10 SQ M ON PLAN AND N EXC 1.5 M IN DEPTH FOR PLINTH BEAMS, DWARF WALL , STEPS AND GETTING OUT IN SOFT/LOOSE SOIL. |
| 3 | Anti terminate treatmentM & L TREATING THE BACKFILL IN CONTACT WITH FOUNDATION AT THE RATE OF 7.5 LITRES OF EMULSION PER SQUARE METRE OF VERTICAL SURFACE (AREA OF THE SUB STRUCTURE IN CONTACT WITH BACKFILL TO BE MEASURED) |
| 4 | M & L TREATING THE BOTTOM AND SIDES OF EXCAVATION AT THE RATE OF 5 LITRES OF EMULSION PER SQUARE METRE OF SURFACE AREA |
| 5 | M & L TREATING THE TOP SURFACE OF FILLED EARTH AT THE RATE OF 5 LITRES OF EMULSION PER SQUARE METRE OF SURFACE |
| 6 | M & L TREATING THE SOIL ALONG WITH EXTERNAL PERIMETER OF BUILDING AT THE RATE OF 2.25 LITRE OF EMULSION PER METRE OF THE PERIMETER WALL |
| 7 | M& L TREATING THE SOIL UNDER PLINTH PROTECTION AT THE RATE OF 5 LITRES OF EMULSION PER SQUARE METRE OF SURFACE AREA |
| 8 | MOORUM/RED BAJRI FILLING IN FLOORS OR PAVINGS, LAID IN LAYERS N EXC. 15CM THICK, SPREAD, LEVELLED AND RAMMED INCLUDING WATERING |
| 9 | M & L CEMENT CONCRETE IN FOUNDATIONS, FILLING AND MASS CONCRETE 1:2:4 TYPE B-2 USING 40 MM GRADED AGGREGATE (FOR PLINTH BEAMS/ DWARF WALL) & L CEMENT CONCRETE IN FOUNDATIONS, FILLING AND MASS CONCRETE 1:2:4 TYPE B-2 USING 40 MM GRADED AGGREGATE (FOR PLINTH BEAMS/ DWARF WALL) |
| 10 | M & L CEMENT CONCRETE IN FOUNDATIONS, FILLING AND MASS CONCRETE 1:4:8 TYPE D-2 USING 40 MM GRADED AGGREGATE (FOR TOE WALL / STEPS) |
| 11 | RETURNING, FILLING IN, INCLUDING SPREADING, LEVELLING, WATERING AND WELL RAMMING IN LAYERS NOT EXC 25 CM IN SOFT/ LOOSE SOIL. |
| 12 | REMOVING EXCAVATED MATERIAL IN SOFT/ LOOSE SOIL N EXC. 50M AND DEPOSITING WHERE DIRECTED AT A LEVEL N EXC. 1.5 M ABOVE THE STARTING POINT |
| 13 | M & L RCC- M-40 (DESIGN MIX) USING 20MM GRADED AGGREGATEFOR FOUNDATION ,INCLUDING RAFTS AS MASS CONCRETE |
| 14 | M & L FORM WORK FOR ROUGH FINISHED SURFACES OF CONCRETE MEASURED FLAT FOR FOUNDATION |
| 15 | M & L REINFORCEMENT STEEL (TMT BARS) FE 500D FOOTING S & F TMT BARS 10MM DIA & OVER OF GRADE FE 500 INCL CUTTING, BENDING, BINDING & PLACING IN POSITION WITH BINDING WIRE. 12MM |
| 16 | M & L RCC- M-30 (DESIGN MIX) USING 20MM GRADED AGGREGATE FOR COLUMN FROM PILECAP TOP TO PLINTH BEAM TOP |
| 17 | M & L FORM WORK FOR ROUGH FINISHED SURFACES OF CONCRETE MEASURED FLAT FOR COLUMN FROM PILECAP TOP TO PLINTH BEAM TOP |
| 18 | M & L REINFORCEMENT STEEL (TMT BARS) FE 500D FROM PILECAP TOP TO PLINTH BEAM TOP.S & F TMT BARS 10MM DIA & OVER OF GRADE FE 500 INCL CUTTING, BENDING, BINDING & PLACING IN POSITION WITH BINDING WIRE.16 MM |
| 19 | DITTO BUT 5 TO 10MM DIA IN STIRRUPS, SPACERS & BINDERS8 MM |
| 20 | M & L RCC- M-30 (DESIGN MIX) USING 20MM GRADED AGGREGATE FOR PLINTH BEAMS |
| 21 | M & L FORM WORK FOR ROUGH FINISHED SURFACES OF CONCRETE MEASURED FLAT FOR PLINTH BEAMS |
| 22 | M & L REINFORCEMENT STEEL (TMT BARS) FE 500D FOR PLINTH BEAMS S & F TMT BARS 10MM DIA & OVER OF GRADE FE 500 INCL CUTTING, BENDING, BINDING & PLACING IN POSITION WITH BINDING WIRE12MM |
| 23 | M & L REINFORCEMENT STEEL (TMT BARS) FE 500D FOR PLINTH BEAMS S & F TMT BARS 10MM DIA & OVER OF GRADE FE 500 INCL CUTTING, BENDING, BINDING & PLACING IN POSITION WITH BINDING WIRE16MM |
| 24 | DITTO BUT 5 TO 10MM DIA IN STIRRUPS, SPACERS & BINDERS8MM |
| 25 | M & L RCC- M-30(DESIGN MIX) USING 20MM GRADED AGGREGATE FOR GRADE SLAB |
| 26 | M & L FORM WORK FOR ROUGH FINISHED SURFACES OF CONCRETE MEASURED FLAT FOR GRADE SLAB |
| 27 | M & L REINFORCEMENT STEEL (TMT BARS) FE 500D FOR GRADE SLAB S & F TMT BARS 10MM DIA & OVER OF GRADE FE 500 INCL CUTTING, BENDING, BINDING & PLACING IN POSITION WITH BINDING WIRE. 8 MM |
| 28 | M & L REINFORCEMENT STEEL (TMT BARS) FE 500D FOR GRADE SLAB S & F TMT BARS 10MM DIA & OVER OF GRADE FE 500 INCL CUTTING, BENDING, BINDING & PLACING IN POSITION WITH BINDING WIRE. 12 MM. |
| 29 | M & L BRICK WORK WITH SUBCLASS ‘B’ BRICKS, STRAIGHT OR CURVED ON PLAN EXC 6M MEAN RADIUS, BUILT IN CM (1:6). |
| 30 | Stage 2, Plinth Beam Top to Roof Slab M & L RCC- M-30 (DESIGN MIX) USING 20MM GRADED AGGREGATE FOR COLUMN FROM GROUND FLOOR TO ROOF SLAB |
| 31 | M & L FORM WORK FOR ROUGH FINISHED SURFACES OF CONCRETE MEASURED FLAT FOR COLUMN FROM GROUND FLOOR TO ROOF SLAB |
| 32 | M & L REINFORCEMENT STEEL (TMT BARS) FE 500D FOR COLUMN FROM GROUND FLOOR TO ROOF SLAB S & F TMT BARS 10MM DIA & OVER OF GRADE FE 500 INCL CUTTING, BENDING, BINDING & PLACING IN POSITION WITH BINDING WIRE. 16 MM |
| 33 | DITTO BUT 5 TO 10MM DIA IN STIRRUPS, SPACERS & BINDERS.8 MM |
| 34 | M & L RCC- M-30(DESIGN MIX) USING 20MM GRADED AGGREGATE FOR ROOF SLAB BEAMS |
| 35 | M & L FORM WORK FOR ROUGH FINISHED SURFACES OF CONCRETE MEASURED FLAT FOR ROOF SLAB BEAMS. |
| 36 | M & L REINFORCEMENT STEEL (TMT BARS) FE 500D FOR ROOF SLAB BEAMS S & F TMT BARS 10MM DIA & OVER OF GRADE FE 500 INCL CUTTING, BENDING, BINDING & PLACING IN POSITION WITH BINDING WIRE12 MM |
| 37 | M & L REINFORCEMENT STEEL (TMT BARS) FE 500D FOR ROOF SLAB BEAMS S & F TMT BARS 10MM DIA & OVER OF GRADE FE 500 INCL CUTTING, BENDING, BINDING & PLACING IN POSITION WITH BINDING WIRE16 MM |
| 38 | DITTO BUT 5 TO 10MM DIA IN STIRRUPS, SPACERS & BINDERS. 8 MM |
| 39 | M & L RCC- M-30(DESIGN MIX) USING 20MM GRADED AGGREGATE FOR ROOF SLAB SLAB |
| 40 | M & L FORM WORK FOR ROUGH FINISHED SURFACES OF CONCRETE MEASURED FLAT FOR ROOF SLAB SLAB |
| 41 | M & L FORM WORK FOR ROUGH FINISHED SURFACES TO EDGES OF CONCRETE MEASURED FLAT FOR GROUND FLOOR SLAB EXC 10 CM BUT NOT EXC 20 CM WIDE |
| 42 | M & L REINFORCEMENT STEEL (TMT BARS) FE 500D FOR ROOF SLAB SLAB S & F TMT BARS 10MM DIA & OVER OF GRADE FE 500 INCL CUTTING, BENDING, BINDING & PLACING IN POSITION WITH BINDING WIRE. 8 MM |
| 43 | M & L REINFORCEMENT STEEL (TMT BARS) FE 500D FOR ROOF SLAB SLAB S & F TMT BARS 10MM DIA & OVER OF GRADE FE 500 INCL CUTTING, BENDING, BINDING & PLACING IN POSITION WITH BINDING WIRE. 12 MM |
| 44 | M & L RCC- M-30(DESIGN MIX) USING 20MM GRADED AGGREGATE FOR CHAJJA @ GROUND FLOOR |
| 45 | M & L FORM WORK FOR ROUGH FINISHED SURFACES OF CONCRETE MEASURED FLAT FOR CHAJJA @ GROUND FLOOR |
| 46 | M & L REINFORCEMENT STEEL (TMT BARS) FE 500D FOR CHAJJA @ GROUND FLOORS & F TMT BARS 10MM DIA & OVER OF GRADE FE 500 INCL CUTTING, BENDING, BINDING & PLACING IN POSITION WITH BINDING WIRE 10 MM |
| 47 | STAGE 3 PCC BLOCK MASONRY-GROUND FLOORM & L PRE CAST CEMENT CONCRETE BLOCK MASONRY WITH SOLID PCC BLOCKS OF GRADE C5 CONFORMING TO IS-2185 PART-I, IN CM 1:6, EC., 10CM IN WIDTH AND SETTING IN MORTOR COMPLETE ALL AS SPECIFIED AND AS DIRECTED. |
| 48 | STAGE 4 PLASTER WORK GROUND FLOORM & L RENDERING 10MM THICKON FAIR FACES OF BRICKWORK OR CONCRETE SURFACES IN CM (1:6) TO BE FINISHED EVEN AND SMOOTH (WITHOUT USINGEXTRA LIME OR CEMENT)GROUND FLOOR |
| 49 | M & L RENDERING 5MM THICK ON FAIR FACES OF BRICK WORK OR CONCRETE SURFACES IN CM (1:3) OVER SOFFIT OF RCC SLABS LANDING, WAIST SLABS, BEAMS, ROOF/CHAJJA PROJECTION ROOF CEILING ETC. TO BE FINISHED EVEN AND SMOOTH (WITHOUT USING EXTRA LIME OR CEMENT) GROUND FLOOR |
| 50 | M & L RENDERING 15MM THICK ON FAIR FACES OF BRICK WORK OR CONCRETE SURFACES - 10MM THICK FIRST COAT IN CM ( 1:6 ) & 5MM THICK SECOND COAT IN CM ( 1:4 )GROUND FLOOR |
| 51 | SUPPLY ONLY WPC |
| 52 | Stage 5 Joinery Ground floor WOODEN PANELLED SHUTTERS, 35 MM THICK |
| 53 | WOODEN DOOR FRAME,60 MM THICK |
| 54 | SS BUTT HINGE 100LONG PER LEAF |
| 55 | SS ALDROP ROD DIA 16 MM SIZE 200-300 MM LONG |
| 56 | SS TOWER BOLT DIA 10MM SIZE 200MM LONG AT TOP |
| 57 | SS TOWER BOLT DIA 10MM SIZE 150 MM LONG AT BOTTOM\MIDDLE |
| 58 | SS TYPE \"D\" HANDLE 150 LONG |
| 59 | 300 LONG FI HOLD FAST (FOR ONE DOOR) |
| 60 | SS DOOR STOPPER CSS 141 OF MAKE CROWN OR EQUIVALENT |
| 61 | ALUMINIUM DOORS, WINDOWS & VENTILATORS FRAMES |
| 62 | ALUMINIUM DOORS, WINDOWS & VENTILATORS LOCK RAILS FRAMES |
| 63 | GLASS PANELS FOR ALLUMINIUM DOORS,WINDOWS & VENTILATORS |
| 64 | WIRE CLOTH FOR ALLUMINIUM DOORS,WINDOWS & VENTILATORS |
| 65 | ROOLING SHUTTER |
| 66 | Stage 6Surface finishes ground floor M & L TWO COATS OF ACRYLIC WASHABLE DISTEMPER OVER ONE COAT OF PRIMER ON INTERNAL WALL WITH WALL CARE PUTTYGROUND FLOOR |
| 67 | M & L THREE COATS WHITE WASH ON WALL ON CEILINGGROUND FLOOR |
| 68 | M & L TWO COAT OF EXTERIOR EMULSION PAINT OVER ONE COAT OF PRIMER ON EXTERNAL WALL WITH WALL CARE PUTTYGROUND FLOOR |
| 69 | STAGE 7 FLOORING GROUND FLOOR- PCC TYPE FLOORING100 MM THICK PCC M20 TYPE A1 LAID OVER 150 MM THICK HARD CORE OVER RAMMED APPROVED WELL RAMMED EARTH FILLING. FINISHING OF PCC BY VACUUM DEWATERING METHOD WITH BROMMING |
| 70 | STAGE 9 ROOF TREATMENTRCC ROOF SLAB LAID TO SLOPE WITH APP WATER PROOFING MEMBRANCE TREATMENT INCL BITUMINOUS ALUMNIUM PAINT FOR INACCESSIBLE ROOF. ALL AS SPECIFIED |
| 71 | WPC |
| 72 | STAGE 10 MISC ITEMSSITE CLEARANCE |
| 73 | STRUCTURAL STEEL |
| 74 | SHEAR KEY’S |
| 75 | FIRE BOQPUMPSTaking from store ,shifting with carefully and Installation, testing and commissioning of Electric driven Main Fire Pump suitable for automatic operation and consisting of following, complete in all respects, as required :(a) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520.(b) Suitable HP Squirrel cage induction motor, TEFC, synchronous speed 1500 RPM, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class-\"F\" insulation, conforming to IS-325.(c) M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required.(d) Suitable cement concrete foundation duly plastered with anti-vibration pads.2850 lpm at 70 m Head,(Supplied by ChPA Free of cost) |
| 76 | Taking from store ,shifting with carefully and Installation, testing and commissioning of diesel engine driven main fire pump suitable for automatic operation and consisting of following, complete in all respects, as required : (Diesel Driven Pump)Horizontal type, multistage, centrifugal pump of cast of iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520.Suitable HP, 1500 RPM water cooled with radiator, diesel engine conforming to relevant IS standard complete with auto starting mechanism, 12 /24 volts electric starting equipment, diesel tank, exhaust pipe extended upto 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red colour etc. as required.M.S fabricated, common base plate, coupling, coupling guard, foundation bolts etc. as required.Suitable cement concrete foundation duly plastered and with anti-vibration pads.2850 lpm at 70 m Head,(Supplied by ChPA Free of cost) |
| 77 | Taking from store ,shifting with carefully and Installation, testing and commissioning of electric driven pressurisation pump suitable for automatic operation and consisting of following, complete in all respects, as required : (Jockey Pump)Horizontal type, multistage, centrifugal pump of cast iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS : 1520.Suitable HP squirrel cage induction motor TEFC type suitable for operation on 415 volts, 3 phase 50 HzAC supply with IP 55 class of protection for enclosure, horizontal foot mounted type with Class-\"F\" insulation, conforming to IS : 325.M.S.fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required.Suitable cement concrete foundation duly plastered and with anti-vibration pads.180 lpm at 70 m Head, (Supplied by ChPA Free of cost) |
| 78 | CONTROL PANEL Fabrication, supply, Installation testing & commissioning of Electrical control panel of cubical construction, floor mounted type, fabricated out of 2mm thick CRCA sheet,compartmentalised with hinged lockable doors, dust and vermin proof, powder coated of approved shade after 7 tank treatment process, cable alley, interconnection with suitable size copper conductor cable/solid copper strip, having switchgears and accessories, mountings and internal wiring, earth terminals, numbering etc. complete in all respect, suitable for main fire pump, pressurisation pump &diesel pump set complete as per CPWD specification with following in coming and Outgoings, suitable for operation on 415V, 3 phase, 50Hz Ac Supply with enclosure protection class IP 42 as required : Incomings400A, 50kA 4 Pole MCCB, Ics=100% Icu ratingDigital Voltmeter 0-500V with selector switchAmmeter (0-630 A) with selector swtich & CTs etc.LED type RYB phase indicating lamps, ON, OFF, tripindicating lampsSet of Copper Bus Bar 800Amps OUTGOING ( Note : All outgoing feeders for pumps should have digital Ammeter with selector switches, and LED type ON, OFF, trip indicating lamps)Main Fire Pump250 A, 50kA TPN MCCB, Ics=100% Icu, with fully automatic Star/Delta starter suitable for 100 hp pump with overload protection, current sensing type single phase preventer complete with all accessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation Jockey Pump 63 A, 50kA TPN MCCB, Ics=100% Icu, with suitable HP fully automatic Star/Delta starter with overload protection, current sensing type single phase preventer complete with all accessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation.DIESEL ENGINE CONTROL Control for diesel engine comprising - Automatic/Manual selctor switch & 3 attempts starting device, timers and relays as required, push buttons, start/stop in manual mode Indicating lamp for high/ Low Lub. Oil pressure, High Water Temp and Engine on indication Battery charger suitbale for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC volt meter, and 0- 20 A DC Ammeter All standard relays and accessories for automatic operation of diesel engine System Controller PUMP HOUSE ROOM FEEDER 63 A, 50kA TPN MCCB, Ics=100% Icu- 2nos |
| 79 | PIPES & ACCESSORIES Providing laying, testing & commissioning of \"C\" class heavy duty GI Pipe conforming to IS 1239 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required.150 mm. Dia |
| 80 | Providing, laying, testing & commissioning of \"C\" class heavy duty G.I. pipe conforming to IS 1239 includingwelding, fittings like elbows, tees, flanges, tapers, nuts, bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required25 mm dia |
| 81 | Providing, laying, testing & commissioning of \"C\" class heavy duty G.I. pipe conforming to IS 1239 includingwelding, fittings like elbows, tees, flanges, tapers, nuts, bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required32 mm dia |
| 82 | Providing, laying, testing & commissioning of \"C\" class heavy duty G.I. pipe conforming to IS 1239 includingwelding, fittings like elbows, tees, flanges, tapers, nuts, bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required50 mm dia |
| 83 | Providing, laying, testing & commissioning of \"C\" class heavy duty G.I. pipe conforming to IS 1239 includingwelding, fittings like elbows, tees, flanges, tapers, nuts, bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required65 mm dia |
| 84 | Providing, laying, testing & commissioning of \"C\" class heavy duty G.I. pipe conforming to IS 1239 includingwelding, fittings like elbows, tees, flanges, tapers, nuts, bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required80 mm dia |
| 85 | Providing, laying, testing & commissioning of \"C\" class heavy duty G.I. pipe conforming to IS 1239 includingwelding, fittings like elbows, tees, flanges, tapers, nuts, bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required100 mm dia |
| 86 | Providing, laying, testing & commissioning of \"C\" class heavy duty G.I. pipe conforming to IS 1239 includingwelding, fittings like elbows, tees, flanges, tapers, nuts, bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required150 mm dia |
| 87 | Providing, laying, testing & commissioning of \"C\" class heavy duty G.I. pipe conforming to IS 1239 includingwelding, fittings like elbows, tees, flanges, tapers, nuts, bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required200 mm dia |
| 88 | Supplying and fixing Single headed external yard hydrant valve with 1 No. 63 mm dia instantaneous FMGunmetal/Stainless Steel coupling and cast iron wheel, ISI marked, conforming to IS 5290 (type A) with blank Gunmetal/Stainless Steel cap and chain as requiredSingle headed Gunmetal |
| 89 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required :50 MM DIA |
| 90 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required :65 MM DIA |
| 91 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required :80 MM DIA |
| 92 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required :100 MM DIA |
| 93 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : 150 MM DIA |
| 94 | Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked completewith nuts, bolts, washers, gaskets and conforming to IS 780 of following sizes as required50 MM DIA |
| 95 | Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked completewith nuts, bolts, washers, gaskets and conforming to IS 780 of following sizes as required100 MM DIA |
| 96 | Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked completewith nuts, bolts, washers, gaskets and conforming to IS 780 of following sizes as required150 MM DIA |
| 97 | Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flanges & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required. |
| 98 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required :50 MM DIA |
| 99 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required :100 MM DIA |
| 100 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required :150 MM DIA |
| 101 | Providing, installation, testing and commissioning of stainless steel Y- strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange.150 MM DIA |
| 102 | Providing, installation, testing and commissioning of stainless steel Y- strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange.50 MM DIA |
| 103 | Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required :Gun Metal |
| 104 | Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required. 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585 20 mm nominal internal dia gun metal globe valve & nozzle. Drum and brackets for fixing the equipment’s on wall. Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket.40 M |
| 105 | Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required :Gun metal |
| 106 | Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required :3 way - 150 mm dia M.S. Pipe |
| 107 | Supplying and fixing air vessel made of 250 mm dia, 8mm thick MS sheet, 1200 mm in height with air releasevalve on top and flanged connection to riser, drainarrangement with 25 mm dia gun metal wheel valvewith required accessories, pressure gauge andpainting with synthetic enamel paint of approved shadeas required. |
| 108 | Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required. |
| 109 | Providing & fixing flow switch in following sizes M.S. pipe including connection etc as required.150 mm dia |
| 110 | Supply and installation of 200 liters capacity 2 mm thick GI priming tank with suitable MS Stand and required Valves , water level tube & Float valve etc as per site requirement . |
| 111 | Supply and installation of 100 liters capacity 2 mm thick GI priming tank with suitable MS Stand and required Valves, Water level tube & Floatvalve etc as per site requirement . |
| 112 | Supply and installation of Pressure Gauge with required valves & Nipples. |
| 113 | Supply and installation of 150 mm dia Marine Foot valve with required Brass nut and bolts and packing etc. |
| 114 | Supply and installation of 65 mm dia Marine Foot valve with required Brass nut and bolts and packing etc. |
| 115 | Demolishing cement concrete manually/ by mechanical means including disposal of material within 50 metres lead as per direction of Engineer - in - charge.Nominal concrete 1:3:6 or richer mix (including equivalent design mix) |
| 116 | Demolishing cement concrete manually/ by mechanical means including disposal of material within 50 metres lead as per direction of Engineer - in - charge. 1:1.5:3 (1 Cement: 1.5 coarse sand (zone-III) including manufactured sand derived from Recycled Concrete Aggregate (RCA) up to 25% : 3 graded stone aggregate 20 mm nominal size including Recycled Concrete Aggregate (RCA) up to 25%). |
| 117 | Excavating trenches by mechanical / manual means of required width for pipes, cables, etc including excavation for sockets, and dressing of sides, ramming of bottoms, for all depth, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within a lead of 50 mPipes, cables etc. exceeding 80 mm dia. But not exceeding 300 mm dia |
| 118 | Dismentalling,removing & Handing over to store with safe condition Existing Fire Pumps like Electric driven pumps (2 nos) ,Dieseal driven pump , Jockey pump, Air vessel, Pipelines, Pressure switches, Fire panel, wires,cables,Light fixtures & pressure gauges etc. |
| 119 | Removing of Existing 150mm dia GI Bend removing re fixing of new bend with one coated of zinc primary and two coats of approved colour etc.. |
| 120 | Painting Steel work with Deluxe Multi Surface Paint to give an even shade. Two or more coat applied @ 0.90 ltr/10 sqm over an under coat of primer applied @ 0.80 ltr/10 sqm of approved brand and manufacture |
| 121 | Supply and installation of rubber expansion bellow EPDM 150mm length, with stand 10kg/cm2 and PN10150 mm dia |
| 122 | Supply and installation of rubber expansion bellow EPDM 150mm length, with stand 10kg/cm2 and PN10100 mm dia |
| 123 | Supply and installation of rubber expansion bellow EPDM 150mm length, with stand 10kg/cm2 and PN1065 mm dia |
| 124 | Supply and installation of rubber expansion bellow EPDM 150mm length, with stand 10kg/cm2 and PN1050 mm dia |
| 125 | ELECTRICAL BOQ LED Batten light (System lumen efficacy ≥105 <120 lm/Watt)Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency>85% ,Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI>80, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K/6000°K/6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. Complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthling etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output. LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as Asper BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).Powder coated die cast / Extruded aluminium Body (Thickness ≥ 1.20 mm)36 watt |
| 126 | LED Street light fixture, powder coated pressure die cast aluminium body (System lumen efficacy ≥105 <120 lm/Watt) Supplying, installation, Testing &Commissioning of Street light LED fixture powder coated pressure die cast aluminium body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driverefficiency >85%,THD < 10% as per IEC 61000-3-2 , P. F.≥0.95, IP- 66,IK-10, CRI >80, under voltage and over voltage protection, EMIEMC As per CISPR -15, lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED, Driver & electrical circuitry) of minimum50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin),SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy≥105 <120 lm/Watt output. LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall beas approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).45 watt |
| 127 | Brush Less Direct Current (BLDC) Motor Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal (Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, remote (preferably mobile app based) for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Ceiling Fan compliant to IS 374:2019 fan Supply, earthling etc. complete as req1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |
| 128 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required.Group C |
| 129 | Wiring for light/ power plug with 2X4 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit along with 1 No. 4 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable for loop earthing as required. |
| 130 | Wiring for circuit/ sub main wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 131 | Wiring for circuit/ sub main wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.4 X 6 sq. mm + 2 X 6 sq. mm earth wire |
| 132 | Wiring for circuit/ sub main wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 4 X 16 sq. mm + 2 X 6 sq. mm earth wire |
| 133 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. |
| 134 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 135 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. |
| 136 | Installation, Testing and Commissioning of pre-wired, fluorescent fitting / compact fluorescent/ LED fitting of all types, complete with all accessories and tube/lamp etc. directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS/HFFR PVC insulated, copper conductor, single core cable and earthing etc. as required. |
| 137 | Installation, Testing and Commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS/HFFR PVC insulated, copper conductor, single core cable, including providing and fixing phenolic laminated sheet cover on the fan box etc. as required. |
| 138 | Supplying and fixing extra conduit down rod of 20 cm length G.I. pipe 15 mm dia, heavy gauge including painting etc. as required. (Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored) |
| 139 | Numbering of ceiling fan/ exhaust fan/ fluorescent fittings as required |
| 140 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note: Vertical type MCB TPDB is normally used where 3 phase outlets are required.)4 way (4 + 12), Double door |
| 141 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, Ics=100% Icu and Operational Voltage 690V etc. as required.100 A, 16 KA,TPMCCB |
| 142 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole |
| 143 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole |
| 144 | Supplying and fixing 30 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top along with 30 A \"C\" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 145 | Supplying and fixing Cable End Box (Loose Wire Box) suitable for triple pole and neutral, sheet steel, Vertical MCB distribution board, 415 Volts, on surface/ recess, complete with testing and commissioning etc. as require |
| 146 | Hot Dipped Galvanized Iron Cable TraySupplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, join with connectors, suspended from the ceiling with two numbers GI Suspenders i/c base of suitable size GI angle, GI bolts & nuts, fastener etc. as required.150 mm width X 50 mm depth X 1.6 mm thickness |
| 147 | Hot Dipped Galvanized Iron Cable TraySupplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, join with connectors, suspended from the ceiling with two numbers GI Suspenders i/c base of suitable size GI angle, GI bolts & nuts, fastener etc. as required.225 mm width X 50 mm depth X 1.6 mm thickness |
| 148 | Hot Dipped Galvanized Iron Cable TraySupplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, join with connectors, suspended from the ceiling with two numbers GI Suspenders i/c base of suitable size GI angle, GI bolts & nuts, fastener etc. as required.300 mm width X 62.5 mm depth X 2.0 mm thickness |
| 149 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having lockingArrangement and watering pipe of 2.7 Meter long etc.with charcoal/ coke and salt as required. |
| 150 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 151 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required |
| 152 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.Above 95 sq. mm and upto 185 sq. mm |
| 153 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 154 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) |
| 155 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.Above 95 sq. mm and upto 185 sq. mm (clamped with 40x3mm MS flat clamp) |
| 156 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 X 70 sq. mm (35mm) |
| 157 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3½ X 185 sq. mm (45mm) |
| 158 | Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required100 mm dia |
| 159 | Supplying of following sizes of 1.1 KV grade multicore aluminium conductor XLPE insulated armoured cable conforming to IS: 7098 (Part - I) complete with all amendments etc. as required.3.5C x 240 Sq.mm Alu XLPE Armoured Cable |
| 160 | Supplying of following sizes of 1.1 KV grade multicore aluminium conductor XLPE insulated armoured cable conforming to IS: 7098 (Part - I) complete with all amendments etc. as required.3C x 70 Sq.mm Alu XLPE Armoured Cable |
| 161 | Supplying of following sizes of 1.1 KV grade multicore aluminium conductor XLPE insulated armoured cable conforming to IS: 7098 (Part - I) complete with all amendments etc. as required.3C x 4 Sq.mm Copper XLPE Armoured Cable |
| 162 | Supplying of following sizes of 1.1 KV grade multicore aluminium conductor XLPE insulated armoured cable conforming to IS: 7098 (Part - I) complete with all amendments etc. as required.3C x 2.5 Sq.mm Copper XLPE Armoured Cable |
| 163 | Supplying and making end termination with brass compression gland and Copper lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3C x 4 Sq.mm Copper XLPE Armoured Cable |
| 164 | Supplying and making end termination with brass compression gland and Copper lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3C x 2.5 Sq.mm Alu XLPE Armoured Cable |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2025 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail