| 1 | Replacement of the damaged TPN MCBDB by Supply and fixing4 way (4 + 12) horizontal type 3 phase and neutralMCB distribution board of sheet steel, IP-43 with metal door, suitable for flush mounting and surface mounting, with 100Amps copper bus bar for each phase with neutral bar, earth bar and cable ties for cable management, fully insulated busbar & shrouded neutral bars, pre-fitted masking sheet, reversible door with provision for fixing four pole MCB/Isolator /RCCB/RCBO as incomer and SPMCB\"s as outgoing etc. as per IEC 61439-3 and grouting in wall as required.(Make: Legrand/ L&T / Schneider Electric/ Siemens/ ABB) |
| 2 | Replacement of the faulty and burn out MCBs, Isolators etc. by new ones of following ratings MCBs and Isolators ISI marked as per IEC 60947-3 /MCBs 10 kA , C- Curve as per IEC 60947-2 in existing MCBDBs i/c connection testing etc. as required.(Make-Legrand / L&T / Schneider Electric / Siemens/Havells ) |
| 3 | 63Amps 4 pole Isolator |
| 4 | 6-32A SPMCB |
| 5 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 6 | 3 x 1.5 sq. mm |
| 7 | 6 x 1.5 sq. mm |
| 8 | 3 x 4 sq. mm |
| 9 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 10 | 20mm |
| 11 | 25mm |
| 12 | Supplying and fixing of flowing size hylam sheet cover i/c cutting for fixing switches/sockets and drilling hole for existing on the existing Switch board box etc complete as required. |
| 13 | Hylam sheet cover |
| 14 | Replacement of the following burnt out/damaged cable/wires/lugs/sockets etc. by new one of following types, sizes and ratings PVC insulated FRLS copper conductor single core stranded flexible cable i/c laying / drawing in existing conduit/pipe, connection, testing etc. as required. |
| 15 | 4sqmm |
| 16 | 1.5sqmm |
| 17 | Replacement of the burnt out cables/wirings by the following sizes PVC insulated & PVC sheathed copper conductor multicore cable i/c fixing/laying on wall/ceiling with C clamps etc. as required. |
| 18 | 3 coreX2.5sqmm |
| 19 | Replacement of faulty and damaged FTL fittings by new one of following ratings,LED Batten withpolycarbonate/Aluminium body suitable for operation on 140 volts to 270 volts AC, 50Hz i/c fixing and connection etc. as required. (Havells/Phillips / Surya / Polycab / Crompton) |
| 20 | 22W General purpose industrial compact batten suitable for Double LED Tube light with integral LED driver with single / double side connection options. (Make-Havells/Phillips/Bajaj/Wipro/Crompton) |
| 21 | Supply of the following electrical accessories/components for Electrical Light Fittings i/c testing etc. as required. |
| 22 | 14/15-watt BC LED Lamp (B22/E27) |
| 23 | Replacement of the lamp holders/ceiling roses etc. by new ones of reputed makes etc. as required. |
| 24 | Angle/batten Holder |
| 25 | Ceiling Rose |
| 26 | 5/6Amps 250 Volts 3 pin Plug top |
| 27 | 15/16Amps 250 Volts 3 pin Plug top |
| 28 | Replacement of the defective switches/sockets/lamp holders/ call Bells etc. by the new one of following ratings etc. as required. (Make- Anchor/Havells/Cona/ISI) |
| 29 | 6 /10 Amps 1 way piano type switch |
| 30 | 20 Amps 1 way piano type switch |
| 31 | 6Amps 3 pin piano type socket |
| 32 | 16 Amps 3 pin piano type socket |
| 33 | Rewinding of 1200mm/1400mm ceiling fan by superior quality super enameled copper conductor i/c heat varnishing, testing etc. as required. |
| 34 | Overhauling of Ceiling Fan i/c dismantling, heat varnishing of windings, greasing of bearings, refitting, testing etc. as required. |
| 35 | Replacement of the defective Capacitors / Fan regulators/ bearings for ceiling fans etc. by the new one of following ratings etc. as required. (Make- Anchor/Havells/Cona/ISI) |
| 36 | Stepped type Electronic Fan Regulator (Switch type) |
| 37 | 2.25 mfd 440 volts Capacitor for Ceiling Fan |
| 38 | Bearings forCeilingfans (6201 & 6202) etc. as required. (Make: SKF/SS) |
| 39 | Dismantling of ceiling fan and painting the same with one or more coats of spray painting with synthetic enamel paint of approved brand and manufacture to give an even shade, including cleaning of surface with detergent, reinstalling the same as required. |
| 40 | Supply/Fixingof exhaust fans by a new complete set forreplacement of faulty/burnt outof380mm /15\" heavy duty1400 RPM Exhaust Fans having maximum free air delivering capacity not less than 3250m3/ hour(1910 CFM) and maximum sound level not more than 60-65 db. with a capacitor start and run type, continuously rated, totally enclosed and ruggedly built motor having pre-lubricated double ball bearingwith Class \"A\" and \"E\" insulation suitable for operation on 230 volts single phase 50 HZ AC supply with features forsmooth &silent operation todeliver the maximum output at lower operating cost. The impeller of the Exhaust Fan isto bepropeller type andboth hub and impeller are to be dynamically balances and frames and arms mounted on rubber bushing so that, vibration are virtually eliminated. (Make- Almonard HD (ISI) / Crompton Greavesor similar superior make) |
| 41 | 380mm /15\" heavy duty1400 RPM, maximum free air deliverying capacity not less than 3250m3/ hour(1910 CFM) and maximum sound level not more than 60-65 db. |