| 1 | Materials and labour for earthing complete with Copper earth plate electrode 600 mm x 600 mm x 3.15 mm thick, burried directly and preferably vertically in ground, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 m below ground level connetced with copper strip of 20 x 3mm sizeby means of nuts, bolts, check nuts and washers made of galvanised iron or steel earthing lead to be protected by galvanised iron pipe of 40mm bore (light grade) and other end connected to earthing test point or lightening arrestor or main controlling switch as directed including providing funnel with 20mm bore galvanised iron pipe (medium grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia TMT bar @ 15 cm C/C bothways and suitable handle made of 10mm dia) including necessary earth work in excavation in hard/dense soil, returning filling and removal of surplus earth upto a distance not exceeding 50 m etc all as shown on electrical plate No. 3 of MES Schedule Part-I(2009) complete including testing on completionincluding taking down of unserviceable earthing complete all as specified and as directed. Notes:-(i) Main earthing strip from earth plate electrode to rest point upto length of 7.5 meters length shall deemed to be included in the unit rate quoted against this item. (ii) On testing after completion if the desired resistenance is not obtained the contractor shall redo the earthing without any extra cost to the department. |
| 2 | Materials and labour for earthing complete with galvanised iron earth plate electrode 600 mm x 600 mm x 6 mm thick, burried directly and preferably vertically in ground, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 m below ground level connected with GI strip of size 25x4mmby means of nuts, bolts, check nuts and washers made of galvanised iron or steel earthing lead to be protected by galvanised iron pipe of 40mm bore (light grade) and other end connected to earthing test point or lightening arrestor or main controlling switch as directed including providing funnel with 20mm bore galvanised iron pipe (medium grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia TMT bar @ 15 cm C/C bothways and suitable handle made of 10mm dia) including necessary earth work in excavation, returning filling and removal of surplus earth upto a distance not exceeding 50 m etc all as shown on electrical plate No. 3 of MES Schedule Part-I(2009) complete including testing on completion including taking down old unserviciable earthing set all as specified and as directed.Notes:-(i) Main earthing strip from earth plate electrode to rest point upto length of 7.5 meters length shall deemed to be included in the unit rate quoted against this item. (ii) On testing after completion if the desired resistenance is not obtained the contractor shall redo the earthing without any extra cost to the department. |
| 3 | Materials and labour for earthing complete with galvanised iron earth plate electrode 600 mm x 600 mm x 6 mm thick, burried directly and preferably vertically in ground, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 m below ground level connetced with galvanised wire of 4mm diaby means of nuts, bolts, check nuts and washers made of galvanised iron or steel earthing lead to be protected by galvanised iron pipe of 15mm bore (light grade) and other end connected to earthing test point or lightening arrestor or main controlling switch as directed including providing funnel with 20mm bore galvanised iron pipe (medium grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia TMT bar @ 15 cm C/C bothways and suitable handle made of 10mm dia) including necessary earth work in excavation, returning filling and removal of surplus earth upto a distance not exceeding 50 m etc all as shown on electrical plate No. 3 of MES Schedule Part-I(2009) complete including testing on completion including taking down of unserviceable earthing complete all as specified and as directed.Notes:-(i) Main earthing strip from earth plate electrode to rest point upto length of 7.5 meters length shall deemed to be included in the unit rate quoted against this item. (ii) On testing after completion if the desired resistenance is not obtained the contractor shall redo the earthing without any extra cost to the department. |
| 4 | Supply & Fix Earth continuity conductor or main earthing lead fixed to wall on battenor recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required Copper earth strip 20 x 3 mm with saddles/fasteners/insulators and fixing screws etc including taking down unserviceable earthing complete all as specified |
| 5 | Supply & Fix Earth continuity conductor or main earthing lead fixed to wall on battenor recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required Aluminium earth strip 25 x 3 mm with saddles/fasteners/insulators and fixing screws etc including taking down unserviceable earthing complete all as specified |
| 6 | Supply & Fix Earth continuity conductor or main earthing lead fixed to wall on battenor recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required GI earth strip 25 x 4 mm with saddles/fasteners/insulators and fixing screws etc including taking down unserviceable earthing complete all as specified |
| 7 | Material & Labour in replacement of test terminal block made of gun metal or phosphorus bronze size 75mmx75mmx25mm drilled and screwed including 3 Nos 8mm dia 25mm long hexagonal head screwscomplete all as specified and as directed. |
| 8 | Supply & Fixing in replacement of air termination single pointed aluminium rod 12mm dia 300mm long for lightning protection complete all as specified and as directed. |
| 9 | Supply & Fixing in replacement of air termination single pointed copper rod 12mm dia 300mm long for lightning protection complete all as specified and as directed. |
| 10 | Supply and fixing steel tubular swaged pole, type 410 SP 31 (Overall length 9.00 meter) conforming to IS-2713 (Part 1 to 3) 1980 complete with cast iron base plate, finial taper plug, bolts, nuts and washers, screws. Pole shall be painted with two coat of black bituminous throughout internally and externally upto planting depth and the remaining external portion shall be painted with two coats of aluminum paints over a coat of red oxide primer includingpainting from bottom to 1.2m height alternative with 30cm red and whitestrip and writing pole no with black paint on yellow background complete all as specified and as directed.Note: (a) Earth work and PCC shall be measured and paid separately under relavent items of schedule \"A\"/BoQ.(b) Design / drawing of HT pole and dimension is to be obtained from OEM/auth dealer/supplier and same is to be got approved fromAGE(I) before placing order to the manufacturer. |
| 11 | Supply and fixing steel tubular swaged pole, type 410 SP 55 (Overall length 11.00 meter) conforming to IS-2713 (Part 1 to 3) 1980 complete with cast iron base plate, finial taper plug, bolts, nuts and washers, screws. Pole shall be painted with two coat of black bituminous throughout internally and externally upto planting depth and the remaining external portion shall be painted with two coats of aluminum paints over a coat of red oxide primer includingpainting from bottom to 1.2m height alternative with 30cm red and whitestrip and writing pole no with black paint on yellow background complete all as specified and as directed.Note: (a) Earth work and PCC shall be measured and paid separately under relavent items of schedule \"A\"/BoQ.(b) Design / drawing of HT pole and dimension is to be obtained from OEM/auth dealer/supplier and same is to be got approved fromAGE(I) before placing order to the manufacturer. |
| 12 | Supplying, Laying connecting & testing XLPE insulated, PVC sheathed, armoured HT electric power UG cable (heavy duty with stranded aluminum conductor)of size 95 Sqmm, 3 core, 11000 Volts(Earthed) grade, conforming to IS-7098 (Part-II) laid through duct/ pipe / in trench etc. with cable glands & suitable size of aluminium lugs including taking down of unserviceable cable complete all as specified and as directed.Note : Earth work, precast cable cover protection and sand cushioning and GI Pipe Shall be measured and paid separately under relavent item of schedule \"A\"/BoQ. |
| 13 | Supplying, Laying connecting & testing XLPE insulated, PVC sheathed, armoured HT electric power UG cable (heavy duty with stranded aluminum conductor)of size 95 Sqmm, 3.5 core, 11000 Volts(Earthed) grade, conforming to IS-7098 (Part-II) laid through duct/ pipe / in trench etc. with cable glands & suitable size of aluminium lugs including taking down of unserviceable cable complete all as specified and as directed.Note : Earth work, precast cable cover protection and sand cushioning and GI Pipe Shall be measured and paid separately under relavent item of schedule \"A\"/BoQ. |
| 14 | Supply, fixing, commissioning & testing of XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, Electric power cable (heavy duty) with aluminium conductors, 1100 volts, grade cross sectional area 70 sqmm 3.5 corelaid through duct/ pipe / in trench etc. with cable glands & suitable size of aluminium lugs including taking down of unserviceable cable complete all as specified and as directed.Note : Earth work, brick protection and sand cushioning and GI Pipe Shall be measured and paid separately under relavent item of schedule \"A\"/BoQ. |
| 15 | Supply, fixing, commissioning & testing of XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, Electric power cable (heavy duty) with aluminium conductors, 1100 volts, grade cross sectional area 50 sqmm 3.5 corelaid through duct/ pipe / in trench etc. with cable glands & suitable size of aluminium lugs including taking down of unserviceable cable complete all as specified and as directed.Note : Earth work, brick protection and sand cushioning and GI Pipe Shall be measured and paid separately under relavent item of schedule \"A\"/BoQ. |
| 16 | Supply, fixing, commissioning & testing of XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, Electric power cable (heavy duty) with aluminium conductors, 1100 volts, grade cross sectional area 25 sqmm 4 core laid through duct/ pipe / in trench etc. with cable glands & suitable size of aluminium lugs including taking down of unserviceable cable complete all as specified and as directed.Note : Earth work, brick protection and sand cushioning and GI Pipe Shall be measured and paid separately under relavent item of schedule \"A\"/BoQ. |
| 17 | Supply, fixing, commissioning & testing of XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, Electric power cable (heavy duty) with aluminium conductors, 1100 volts, grade cross sectional area 16 sqmm 4 core laid through duct/ pipe / in trench etc. with cable glands & suitable size of aluminium lugs including taking down of unserviceable cable complete all as specified and as directed.Note : Earth work, brick protection and sand cushioning and GI Pipe Shall be measured and paid separately under relavent item of schedule \"A\"/BoQ. |
| 18 | Supply, fixing, commissioning & testing of XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, Electric power cable (heavy duty) with aluminium conductors, 1100 volts, grade cross sectional area 10 sqmm 4 core laid through duct/ pipe / in trench etc. with cable glands & suitable size of aluminium lugs including taking down of unserviceable cable complete all as specified and as directed.Note : Earth work, brick protection and sand cushioning and GI Pipe Shall be measured and paid separately under relavent item of schedule \"A\"/BoQ. |
| 19 | Supply, fixing, commissioning & testing of XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, Electric power cable (heavy duty) with aluminium conductors, 1100 volts, grade cross sectional area 16 sqmm 2 core laid through duct/ pipe / in trench etc. with cable glands & suitable size of aluminium lugs including taking down of unserviceable cable complete all as specified and as directed.Note : Earth work, brick protection and sand cushioning and GI Pipe Shall be measured and paid separately under relavent item of schedule \"A\"/BoQ.e |
| 20 | Excavation in trenchesnot exceeding 1.5m wide and not exceeding 1.5m in depth for foundations, manholes, etc. or for laying cables/pipes, erecting poles, etc. not exceeding 10sqm on plan and getting out in soft / loose soil complete all as specified and as directed. |
| 21 | All as per item No 21 above but depth exc 1.5m but n.exc 3mcomplete all as specified and as directed. |
| 22 | Returning, filling in, including, spreading, leveling, watering and well ramming in layers not exceeding 25cm deep as in any type of soil complete all as specified and as directed. |
| 23 | Removing excavated materialsto a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point in any type of soil including spreading in low lying area and leveling complete all as specified and as directed |
| 24 | Materials and labour for sand filling around the cable with approved quality coarse sand for sand cushioning of Under ground cableincludingspreading and punning down to 18 cm thickness complete all as specified and as directed.(Compacted thickness shall be measured) |
| 25 | Supplying and laying un-reinforced precast concrete cable cover, class HVP, type 1, with peak, size 300mm x 180mm x 40mmin trenches on cable as cable protection across the length of the cable (width wise)complete all as specified and as directed. |
| 26 | Materials and labour for brick protection cover to underground cables with sub class ‘B’ over burnt brick of size 23 X 11.5 X 7.5 cm, (locally available best quality), laid dry and flat abutting each other with gaps not exceeding 10mm complete all as specified and as directed. |
| 27 | Supply and laying GI tubing 80mm bore light grade with fittings laid in trenches for protection of HT/LT underground cables/ roof conductor including taking down oldunserviceable pipes complete all as specified and as directed.. |
| 28 | Supply and laying GI tubing 50mm bore light grade with fittings laid in trenches for protection of HT/LT underground cables/ roof conductor including taking down oldunserviceable pipes complete all as specified and as directed.. |
| 29 | Supply and laying GI tubing 40mm bore light grade with fittings laid in trenches for protection of HT/LT underground cables/ roof conductor including taking down oldunserviceable pipes complete all as specified and as directed.. |
| 30 | Material and Labour for PCC 1:3:6 type C-2 using 40 mm graded crushed stone aggregate for errection of Stay rod, filling and mass concrete etc all as specified and directed by Engr-in-Charge. |
| 31 | Material and Labour for PCC 1:2:4 type B-1 using 20 mm graded crushed stone aggregate for coping of pole, filling of road cutting and mass concrete etc complete all as specified and directed by Engr-in-Charge. |
| 32 | Material and labourfor HT 11 KV (Earthed) grade heat shrinkable jointing kit outdoor type complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 70 to 95 sqmm including taking down of unserviceable jointing kit complete all as specified and as directed. |
| 33 | Material and labourfor LT 1.1 KV (Earthed) grade heat shrinkable straight through jointing kit complete with jointing material and accessories suitable for 4/3.5 core XLPE armoured aluminium conductor cable of size 10 to 16 sqmm including taking down of unserviceable jointing kit complete all as specified and as directed. |
| 34 | Material and labourfor LT 1.1 KV (Earthed) grade heat shrinkable straight through jointing kit complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 25 to 50 sqmm including taking down of unserviceable jointing kit complete all as specified and as directed. |
| 35 | Material and labourfor LT 1.1 KV (Earthed) grade heat shrinkable straight through jointing kit complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 70 to 95 sqmm including taking down of unserviceable jointing kit complete all as specified and as directed. |
| 36 | Material and labour for testing earth resistance between conductor and earth value for buildings and lightning conductors including writing date of testing and next due date with synthetic enamel paint in approved fonts over the earth pit complete all as specified and as directed.Note:(i) Testing shall be done from testing agencies approved by the GE.(ii) Test certificates shall be submitted in duplicate to claim any payment against the item.(iii) Periodicity of testing on each earthing shall be twice within currency of contract or as directed by the Engineer-in-charge.(iv) Two numbers of testing in one earthing shall be measured as one unit for payment purposes. |
| 37 | Supply and fixedin repair of triple pole, mechanically operated air break isolator (GOD), vertical mounting, rotating type, mounted on insulator and steel frame with operating mechanism worked from ground level with all accessories viz. gun metal moving contacts, spring loaded gun metal fixed jaws, knife copper jumper strip, etc. suitable for 11000V grade, with 9 insulator of rating upto 200A complete all as specified and as directed. |
| 38 | Supply and fixedin repair of HT lightening arrestor, set of three, expulsion type with all fittings, of transmmission class discharge capacity 65kA suitable for 11KV complete all as specified and as directed |
| 39 | Supply and fix in repair of cross arms. Bracings, support channel, backplate hooks etc fabricated from structural steel, sections (MS Channel) of required size and shape including nuts, bolts,washers, welding, bending , cutting cold or hot, drilling holes for inserting bolts as indicated and directed including painting with one coat of red oxide primer and two coats of silver aluminium paint complete all as specified. |
| 40 | Material and Labour for dehydration and filtration of existing transformer oil of transformers at different locations with filtration machine and heating system to get the minimum di-electric strength of oil 50kV (minimum) without disturbing the power supply system and refilling/ topping up transformer oil conforming IS-335-1993 /replacement of unserviceable transformer oilcomplete all as specified and as directedNotes: (a)Transformer oil required extra for filling/topping up shall be measured and paid separately under the relevant item of this schedule.(b) Cost of oil testing and required T&P shall be deemed to be included in the quoted rate. |
| 41 | Material and Labour for draining out old transformer oil and supply, filling/ topping up oil of transformer oil of dielectric strength not be less than 60kV and conforming to IS-335 of 1993 up to desired levels as required for transformers at different locations complete all as specified and as directed. |
| 42 | Supply and fixing breather assembly including silica gel, indicating type, 4 to 6mm standard size of the particle, blue colour for transformer of capacity from 63 to 150kVA including removing of old unserviceable breather complete all as specified and as directed. |
| 43 | Supply and fix in repair of brass terminal stud with nuts, check nuts, oil seal and washer for HT side suitable for 100/150kVA transformer complete all as specified and as directed. |
| 44 | Supply and fix in repair of brass terminal stud with nuts, check nuts, oil seal and washer for HT side suitable for 100/150kVA transformer complete all as specified and as directed. |
| 45 | Material & Labour for preparation of old surfaces of transformers, any type (power or distribution) of capacity upto and including 100 to 150kVA (in situ) outdoor type, installed at various locations, by cleaning, scrapping, rubbing/ polishing etc. and spray painting with two coats of Duco paint (Grey) and writing the SM MES No of transformer on body of transformer with synthetic enamel paint (of approved tint) in suitable font and size (as approved) complete all as specified and as directed |
| 46 | Supply and fix in repair of drain valve of transformer 100 KVA to 150 KVA of existing make complete all as specified and as directed. |
| 47 | Supply and fix in repair of top cover gasket of transformer 100 KVA to 150 KVA of existing make complete all as specified and as directed. Note :- Quoted rate also includes cost of body opening, refixing and replacement of nut bolts etc. |
| 48 | Material & Labourforpreparation of surfaces viz. scrapping old paints, smoothening, etc. and painting to steel tubular poles, 9m high, with two coats of synthetic enamel paint upto a height of 1.5m from ground, in alternate stripes in black & yellow, including painting of pole coping with synthetic enamel paint (black tint) and writing (font 1/2\"x3\") pole numbers with white synthetic enamel paint on circular base, marking of HT/LT, painting of balance portion of pole, cross arms, brackets with two coats of aluminum paint with all necessary staging, safety precautions, etc. as required complete all as specified all as directed. |
| 49 | Supply & fixedin repairs of 4 pole onload change over switch, 415V, 50Hzwith SS enclosure of 100A capacity fixed to panel board with necessary arrangement including nuts, bolt, lugs, glands, etc. complete all as specified and as directed. |
| 50 | Supply & fixedin repairs of MCCB 4 pole 35kA, 250A, 415V, 50Hz, with thermal magnetic release setting, fixed to panel board with necessary arrangement including nuts, bolt, lugs, etc. complete all as specified and as directed. |
| 51 | Supply & fixed in repairs MCCB 4 pole 35kA, 200A, 415V, 50Hz, with thermal magnetic release setting, fixed to panel board with necessary arrangement including nuts, bolt, lugs, etc. complete all as specified and as directed. |
| 52 | Supply & fixed in repairs MCCB 4 pole 35kA, 160A, 415V, 50Hz, with thermal magnetic release setting, fixed to panel board with necessary arrangement including nuts, bolt, lugs, etc. complete all as specified and as directed. |
| 53 | Supply & fixed in repairs MCCB 4 pole 25kA, 125A, 415V, 50Hz, with thermal magnetic release setting, fixed to panel board with necessary arrangement including nuts, bolt, lugs, etc. complete all as specified and as directed. |
| 54 | Supply & fixed in repairs MCCB 4 pole 25kA, 100A, 415V, 50Hz, with thermal magnetic release setting, fixed to panel board with necessary arrangement including nuts, bolt, lugs, etc. complete all as specified and as directed. |
| 55 | Supply & fixed in repairs MCCB 4 pole 16kA, 63A, 415V, 50Hz, with thermal magnetic release setting, fixed to panel board with necessary arrangement including nuts, bolt, lugs, etc. complete all as specified and as directed. |
| 56 | Supply & fixed in repairs MCCB 3 pole 16kA, 32-40 Amps, 415V, 50Hz, with thermal magnetic release setting, fixed to panel board with necessary arrangement including nuts, bolt, lugs, etc. complete all as specified and as directed. |
| 57 | Supplying, Installing, Commissioning and Testing of CPRI Prototype tested, Factory made, Free Standing Floor Mounted, Dust and Vermin proof LT Panel board, Compartmentalised, Outdoor type, fabricated with 3.15mm thick CRCA Sheet and shall be given pre-treatment for degreasing, phosphatising etc. in seven tank process and shall be powder coated with RAL7035 coat with matt finish after due preparation of surfaces. The panel shall consist ofaluminium bus bars of high conductivity of suitable size and shall be provided with colour coded heat shrinkable sleeves mounted on porcelain insulator supports, suitable double Compression Copper Cable Glands and panel shall be provided with separate compartments for each switch, with gland plates, lifting hooks, shutter type ventilating louver at both top & bottom duly internally secured with wire mesh, with suitable internal wiring with copper cable of suitable size, including instrumentation such as Ampere Meter, Volt Meter, Phase Indicating LED Lamps [RYB], Selector Switches etc with double stud hinged door, front openable with locking arrangement including interlocking with switch gears and suitable for 1100 Volts Grade, 3 Phase, 415 Volts, 4 Wire, 50 Hz, AC Supply and to withstand short circuit fault level of not less than 100KA and degree of protection shall be IP 54. (Cont...) |
| 58 | The panel shall be fixed with angle iron frame made of angles of size 40X 40 X 5mm at Corners and ISMC of suitable size for base, embedded 600 mm below ground level in PCC 1:2:4, Type B–1 using 20mm grade stone aggregate, 600 mm above ground level complete including connecting up with existing incoming and outgoing cables etc. and comprising the following :[a] MCCB, 125 Amps, FP, 25KA, 415 Volts, 3 Phase, AC, 50 Hz – 1 No. [Incoming][b] Aluminium bus bar 400 Amps for phases and 300 Amps for Neutral of suitable size and length duly insulated with colour code.[c]Multifunctioning meter (Next Gen) - 01 No [d] Colour Coded LED Phase Indicating Lamps for each Phase – 1 Set. OUTGOING :-(a) MCCB 4 Pole 63 Amps, 16 KA Breaking capacity - 03Nos(b) MCB SPN 32A, 10 KA Breaking capacity - 04 Nos. |
| 59 | Supply, install, testing and commisioning of bus bar chamber of suitable size, CPRI approved, cubical floor mounted outdoor type, factory made, totally enclosed, dust and vermin proof, made out of 3.15mm thick MS sheet duly powder coated both side in and out, having suitable locking arrangments both at front and rear side, aluminium bus bar of 200A rating, duly drilled holes for connections and mounted on epoxy based post insulators for 3 phase, 500V, 50Hz AC supply, including cable gland, angle iron of size 40x40x4mm framed support (bottom portion of the panel), grouted in foundation in PCC 1:2:4 type B1 using 20mm graded stone aggregates complete all as specified and as directed.Note: Excavation, earthwork in any type of soil, PCC foundation for panel and grouting, etc. shall be deemed to be inlcuded in the quoted rate |
| 60 | Material and Labour for (cold bitumen)for filling/repair of road cutting with road patch material ready mix liquid asphalt with chemicals, anti striping agents, graded aggregates and additives laid in layers of 50mm and compacted with rammer or a wooden mallet complete as per manufacturer instructions and as directed by Engr-in-Charge. |
| 61 | M&L for Danger notice plate of1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S clamps, bolts and nuts of approved size, for LT, 20x15cm size ncluding dismanting old unserviceable plate complete all as specified and as directed. |
| 62 | M&L for Danger notice plate of1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S clamps, bolts and nuts of approved size, for HT, 20x15cm size ncluding dismanting old unserviceable plate complete all as specified and as directed. |
| 63 | M & L for preparation of old painted surface of LT Panel/Distribution box installed at E/M Installations at Aizawl Mil Stn area of any size by removing all dirt, dust,etc and painting complete surface including connected accessories such as angle Iron channel etc of any description with one coat of synthetic enamel paint of approved colour including writing of identification complete all as directed by Engineer-in-Charge. |
| 64 | M&L hard core of gauge n.exc 63mm deposited spread and leveled in layers n.exc 15cm thick, watered and rammed to true surface broken stone or boulders or aggregate around 4 pole , 2 pole structure and transformer etc. complete all as per directed by Engr-in-charge. |
| 65 | S & F in reapir of Cable Route Indicator made of CI Disc, 150mm dia, with inscription of HT/LT Cable fixed to MS angle of size 40 X 40 X 6mm, 450mm long with bolts & nuts, duly grouted in PCC, 1:3:6, Type C1 complete including necessary excavation and earth work complete all as specified and as directed. |
| 66 | Supply and fixing in repair of 415V 10KA \"C\" curve miniature circuit breaker (MCB) of TPN 63 to 100Amps current carrying capacity in the DB complete with connection testing and commissioning complete all as specified and as directed. |
| 67 | Supply and fixing in repair of 415V 10KA \"C\" curve miniature circuit breaker (MCB) of TP 32 to 63Amps current carrying capacity in the DB complete with connection testing and commissioning complete all as specified and as directed. |
| 68 | Supply and fixing in reapirof240V, 10KA \"C\" curve miniature circuit breaker (MCB) of SPN and current carrying capacity 32 Amps in the MCB DB complete with connection testing and commissioning complete all as specified and as directed. |
| 69 | Supplying, laying / fixing, testing and commissioning of electric cable, grade aluminium conductor XLPE insulated, 6Sqmm, 2 core, 1100 volt earthed grade, Un-armoured cables conforming to IS-7098 (Part-I)-1988, stranded, XLPE insulation, PVC tape inner sheath laid in trenches, passing through ducts, etc. fixed on poles, etc. including taking out old damaged cable complete all as specified and as directed.Note: Excavation/earthwork, bricks, sand cushioning and GI pipe will be measured and paid separately. |
| 70 | Supplying, laying / fixing, testing and commissioning of electric cable, grade aluminium conductor XLPE insulated, 10Sqmm, 2 core, 1100 volt earthed grade, Un-armoured cables conforming to IS-7098 (Part-I)-1988, stranded, XLPE insulation, PVC tape inner sheath laid in trenches, passing through ducts, etc. fixed on poles, etc. including taking out old damaged cable complete all as specified and as directed.Note: Excavation/earthwork, bricks, sand cushioning and GI pipe will be measured and paid separately. |
| 71 | Supplying and laying in repairs synthetic Rubber insulated mats 2 mm thick for voltage upto 3.3 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m complete all as specified and as directed. |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2025 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail