Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | Servicing and checking of EXISITING 11 KV Breakers02 Numbers INCOMERs any make and typemake VCB with blower, cleaning of existing HT panel inside, outside with tighting of all bus bar, nut & bolt, alignment, adjustment of gaps between phase to phaseas per manufacturer recommend action Checking and tightening of control wiring circuit as charging motor closing coil and tripping coil circuit, Manually tripping testing of VCB, Cleaning, removal of dust and dirt to male/Female contacts, greasing & lubrication all moving fixed part including replacement of minor parts such as spring, washers etc. for smooth mechanical operation etc. complete with testing commissioning as required. Servicing, Calibration, testing of ( one earth fault one over current) with secondary injection testing of 11 KV /VCB, Operational testing through relay front pad as well as push button, Testing/ Calibration of safety relays, Tripping testing of VCB through over current and earth fault relay,testing and servicing of the existing 11 kV VCB panel, including high pot testsand submission of test certificates with proper sealing. Primary injection testing to verify tripping functionality. Opening of HT panel, removal of moisture from busbars, insulators, HT cable box, and heating of P.T. and C.T. chambers. Relay settings to be checked and configured as per the protection scheme. During breaker racking, inspection of jaw-type male/female contacts connected to the busbar is included—cleaning or replacement shall be done if found carbonized or damaged. Final insulation resistance (megger) testing of all components to be completed as per standard procedures and safety norms. Note : Minor spare part are deemed to be included in quoted rates for making functional & major spare may be pay separety as mentioned below. |
| 2 | Servicing and checking of EXISITING 33 KV Breakers along with 33kV CR Panel indoor typeat MALPURA MRSany make and typemake VCB with blower, cleaning of existing HT panel inside, outside with tighting of all bus bar, nut & bolt, alignment, adjustment of gaps between phase to phaseas per manufacturer recommended, Checking and tightening of control wiring circuit as charging motor closing coil and tripping coil circuit, Manually tripping testing of VCB, Cleaning, removal of dust and dirt to male/Female contacts, greasing & lubrication all moving fixed part including replacement of minor parts such as spring, washers etc. for smooth mechanical operation etc. complete with testing commissioning as required. Servicing, Calibration, testing of ( one earth fault one over current) with secondary injection testing of 33 KV /VCB, Operational testing through relay front pad as well as push button, Testing/ Calibration of safety relays, Tripping testing of VCB through over current and earth fault relay,testing and servicing of the existing 33 kV VCB panel, including high pot testsand submission of test certificates with proper sealing. Primary injection testing to verify tripping functionality. Opening of HT panel, removal of moisture from busbars, insulators, HT cable box, and heating of P.T. and C.T. chambers. Relay settings to be checked and configured as per the protection scheme. During breaker racking, inspection of jaw-type male/female contacts connected to the busbar is included—cleaning or replacement shall be done if found carbonized or damaged. Final insulation resistance (megger) testing of all components to be completed as per standard procedures and safety norms. Note : Minor spare part are deemed to be included in quoted rates for making functional & major spare may be pay separety as mentioned below. |
| 3 | M&L for calibration ofHT VCB indoor type 11 KV & 33kV CR Panel VCBwith calibration of all protective devices or relay according to load, minor repair to wiring connector block etc all as specified and directed by E-in-Charge.Note:- (i) Calibration is to be done by auth service person. |
| 4 | S/I/T/C of AC Power MFM for 3 phase power supply Input Voltage Max continuous input voltage 125% of nominal value Technical SpecsVA Burden Nominal input voltage burden < 0.4 W approx. Nominal input current burden < 0.1 W approx. Auxiliary Supply burden < 6 VA approx Accuracy Reference Conditions 23°C +/- 2°C Voltage ±0.5% of Nominal value (±20 to ±120%) Current ±0.5% of Nominal value (±5 to ±120%) Power ±0.5% of Nominal value (±5 to ±120%) Energy Class 0.5 Temperature Drift 0.05%/°C Input Current Display Type 1 line 8-digit LED Display Display Height 9 mm Overload Indication -oL- (Above 126% of nominal value) Display Range Voltage 0 to ±9999 Current 0 to ±9999 Power 0 to ±9999 Energy (Import & Export) 0 to 99999999 Shunt Setting Range 50 ~ 150 mV No of Channels 1 Current Sensor External Shunt Full Scale Setting Range 1 A to 20 kA Max continuous input current 125% of nominal value 61 ~ 200 VDC Nominal Input Voltage Range 10 ~ 60 VDC 201 ~ 1000 VDC Auxiliary Supply Operating Measuring Range Voltage ±5 to ±125% of nominal value Current ±0.2 to ±125% of nominal value Nominal Value 230 V AC-DC, 50/60 Hz for Higher Aux Higher Aux 60 V – 300 V AC-DC, 45 to 65 Hz range Uncertainty ±2 minutes / month (23°C +/- 2°C) Real Time Clock (RTC) Lower Aux 20 V – 60 V AC-DC 24 V AC-DC for Lower Aux 3 92mm+0.8 Panel Cutout 92mm+0.8 Dimensions Details96mm Overload Withstand 2 x rated value for 1 second, repeated 10 times at 10 second intervals Overload Withstand 20x rated value for 1 second, repeated 5 times at 5 min intervals NOTE: Variation due to influence Quantity is 100% of class index built with Data LoggingUser Selectable parameters (1 to 30) can be logged at regular intervals (1 to 60 min) with Date & Time stamp in internal memory and can be accessed via Modbus l Max Records can vary from 8532 to 91010 depending upon number of selected parameters Load |
| 5 | Contd....from item No 4Analysis Logging of Energy consumed and Peak Demand (Power & Current) in a day and in a month fortracking of load behaviour l Daily Data is available for last 1 year and Monthly Data is available for last 14 years Direct Remote Access (optional) l Remote configurationof the Instrument and access of measured parameters via MODBUS l Programmable baud rates up to 57.6kbps 1 - line 8 digit Ultra-bright LED Display l 1 - line LED display provides easily readable data on meter front with a display range of 99999999 Reverse Locking l Energy and Ampere Hour accumulation can be blocked for Reverse Power and Current resp l Reverse condition can be set as Import or Export Onsite Configuration can be done via Front Keys, USB Serial Interface or RS485 (MODBUS) Relay Functions l Limit Switch - For protection against over-shoot or undershoot of any selected parameter l Pulse Output - To drive an external counter for energy measurement l Timer - Cyclic ON-OFF operation of relay for user-dened cycles with programmable ON-OFF Delays l Remote Operation - Relays can be activated remotely via Modbus l Reverse Locking Alarm l RTC Relay - Relay can be activated & deactivatedwith ON & OFF Time on any or all Days of Week Enclosure Protection for dust and water l Conforms to IP 54 (front face) as per IEC60529 Compliance to International Safety standards l Compliance to International Safety standard IEC 61010 - 1 - 2010 EMC Compatibility l Compliance to International standard IEC 61326 – 2012 MAKE ELEMEASURE/SCHNEIDER/SECURE but with Software Programmer |
| 6 | Dismantling of old pully system and mercury / thermal based sensors and protection and replacement withMicro controller-based indicator with inbuilt Temperature measurement in single enclosure along with necessary space heaters suitable as per required for each VCBIncorporates highly stable built-in or Remote Temp. sensor. 3 Digit, 0.56\" bright LED display for displaying RH & Temperature. Process parameter Hi and Low status indication for channel.along with Tubular space heater suitable for connection to the single phase AC supply in each panel (both control and relay panel in case of duplex type) complete with switches and thermostat located at convenient position shall be provided at the bottom side of the cubicle to prevent condensation of moisture. The watt loss per unit surface temperature of the heater shall be low enough to keep surface temperature well below allowable heat. The wattage of the heater shall be such as to keep 10° C above average ambient temperature in the rainy season but the temperature shall not under any circumstances damage the insulation of the wiring of the panel.User selectable set limits for process value violation. Inbuilt buzzer to audible process value violation. Password protection for calibration and programming mode. Software Calibration for 2 channels. etc. Programmable devise address, baud rate, (max no. of device is 1-256). Remote programmable from master device. User programmable offset correction. Compact, All Stainless-Steel enclosure with 35 mm depth for installation in prefab panels. Brick and modular wall mounting and flush mounting. Inputs two numbers temp & RH, Temperature input integral or remote optional, Humidity input integral or remote optional, transmitting power supply – 220/24/5 V DC 100 MA WITTH ISOLATION BASED SMPS TYPE, Indication Temperatures, Channel-1: 3 digit Seven segments 0.56” RED display. Channel-2: 3 digit Seven segments 0.56” RED display. 5-LEDs for visual alarms, buzzer for audible alarm, LED for 485-comm. Control action PID control |
| 7 | Contd....from item No 5with auto tuning , ON - OFF control(For RH: ON-OFF control only) Proportional band (P) 1.0 to 400.0°C Functional specifications Humidity Temperature 3 digit LED display RH Sensor input Sensor enclosed with unit ON-OFF control 7A SPDT Relay output 0% - 100% Humidity control range 3 digit LED display RTD Input (PT100) ON-OFF / PID control Auto tune / Self tune PID 7A SPDT Relay output Temperature unit °C / °F selectable 0 to 99.9 min 0 to 999 sec Integral time (I) Derivative time (D) 0.1 to 99.9 sec 0.1 to 99.9°C Cycle time Hysteresis width 95% RH Temperature Humidity (non - condensing) Environment specifications Operating : 0°C to 50°C; Storage : -20°C to 75°C Supply voltage 90 to 270V AC / DC (AC : 50 / 60 ) Auxiliary supply specifications Power consumption 4 VA max @ 230V AC Mounting Panel Weight Mechanical specifications Cable length 1 meter Dimensions (mm) Sensor Information 52 x 28.8 x 18 Manual reset value -19.9°C to 19.9°CMAKE ABB/SChneider /L&T /SiemensMINIMUM 1SO 9001:2015 CERTFIED. |
| 8 | Dismantling of Old unserviceable power back up system & Supply, testing, commissioning ripple free power supply unit with First Stage conversion: Power factor correction along with H.F. filter and input AC voltage rectification and conversion in high voltage DC. ii) Second Stage Conversion: Rectified high voltage DC is stored in capacitors. High voltage DC is then converted in to a very high frequency AC (20 KHz and higher). Conversion of high voltage DC to high frequency AC is achieved by means of very powerful and ultra-fast semiconductor switching devices. High frequency AC is stepped down to the required level by means of a small high frequency transformer with following specifications OUTPUT POWER FACTOR –O.8 LAG.OUTPUT FREQUENCY – 50 HZ+/-0.5% . WAVE FORM – 20 MILLI SEC PURE SINE WAVE . RESPONSE TRANSIENT - <8% ON 90% LOAD CREST FACTOR – 3:1 . DISPLAY – SUPPLY ON, BATTARY HIGH/LOW, OVERLOAD, OUTPUT HIGH/LOW, CHARGING ON, MAINS LOW/HIGH, BYEPASS, FAULT, OVERHEATPROTECTION-OUTPUT OVERVOLTAGE,OUTPUT UNDER VOLTAGE, OVERLOAD, SHORT CIRCUITOVERLOAD CAPACITY- 110%- 08 MIN, 125%- 90 SEC,150%- 45 SECLIQUID CRYSTAL DISPLAY- INPUT VOLTAGE/FREQUENCY. OUTPUT VOLTAGE/FREQUENCY,LOAD%,CHARGING CURRENT, TRANSFER TIME/ SWITCHING TIME-0 MILLI SECSWITCHING MODE – WITHOUT ANY SWITCHGEAR HUMIDITY – 5% T0 95% NON CONDENCED.Stepped down AC is rectified by ultra-high-speed diodes to DC of desired voltage and filtered by means of high frequency filters and pure DC voltage is stored in capacitors Make ABB/Schneider/Siemens approved by GE minimum ISO 9001:2015 Certified . Note :- The Entire work at siteis to be executed onlyby OEM approved by GE.Original OEM is entitled for work . Contractor has to ensure it.Necessary test certificates to be approved by Engg-in-Charge first before execution at site |
| 9 | Dismantling of old AC to DC converter any type existing at site and replacement with multiple output portson line and replacing with new digital converter power supply unit switch mode power supply unit Voltage influence ≤0.5% / V Temperature influence: ≤0.01% / °CAmbient conditions Ambient temperature:-25 to +55°CStorage temperature: -25 to +70°C Transport temperature:-25 to +70°C Relative humidity: 15% to 85% Double Conversion On Line. • Continuous Voltage & Frequency Regulation • High Power Density • Wide Input Voltage Range • Input Supply voltage 360- 450 volts three phase input Frequency regulation range, AC input 47-55 Hz Supply voltage fail. bridging time at 100 % load 10 ms min. Max. deviation of output with static load change ± 2.5 % Max. deviation of output with dyn. load change 5 % (load change 10-90 %) Short-circuit protection overcurrent switch-off with automatic restart Overload protection over temperature and overcurrent switch-off Reset after thermal overload switch-off disconnection of AC input voltage 30 s min. StandardsIsolation testing 2.5 kV AC routine test,overvoltage category , degree of pollutionElectromagnetic compatibilityInput current harmonics no limitationEfficiency at nom. load approx.79-84 % Indication of operational states green LED, output voltage OK Operating temperature 0 °C ... +55 °C Storage temperature -25 °C ... +75 °C. Original OEM is entitled for work . Contractor has to ensure it.Necessary test certificates to be approved by Engg-in-Charge first before execution at site . |
| 10 | Disconnecting of existing old battery bank set up User Replaceable, Batteries type SMF back up not less than 08 Hr at full loadconsidering KW Output power a) Open circuit voltage b) Full load voltage c) Full load current d) Current Resolution e) Mode of operation 360V DC 40 A (Current should be adjustable from 0.1A to 40 A with resolution of 1A) 1 A Constant current (Independent of the load voltage) mode Cooling water temperature, water flow (if water cooling is used) b) Stack temperature c) Over voltage d) Over current e) Single phasing f) Emergency Off g) Panel door All Sensors’ NO/NC input will be provided by IPR for interlock purpose except overvoltage, over current, single phasing, emergency off and panel door interlocks. All functioning of these interlocks using dummy inputs of 0 to 5 V /NO /NC as applicable. The interlocks operation should be implemented using PLC (Programmable Logic Control) and HMI (Human Machine Interface). Calibration certificate of all sensors and meters in the power supply unit will have to be submitted along with the delivery of the power supplyOriginal OEM is entitled for work . Contractor has to ensure it.Necessary test certificates to be approved by Engg-in-Charge first before execution at site |
| 11 | Dismantling of old change over system & replacement withcomplete Automation unit& Manual Bypass • Faster Recharge Time • Cold Start • IGBT Based with Isolation Transformer • Intelligent Battery Management • Lightning and Surge Protection • Sine Wave Output • Network Grade Line Conditioning • Emergency Power Off • Unattended Safe & Graceful Shutdown • Alarms and Indicators • Power Chute Software (OPTIONAL) • Auto sensing and programmable Frequency suitable for existing breakerpanel fitted with spring charge motors andMotor unitsfor switching on and offbreaker at the mode power failure from state electricity board Multiple output voltage (a) 110 Volts DC (+ or -) 0.5% 10 A accuracy,(b) 400 Volts AC (+ or -) 0.5%3 Phase10 A accuracy, & 220 Volts AC (+ or -) 0.5% 10 AforMotor unit ofexisting breakers withaccuracy with load sustaining capacityand No volt coil of allbreakers spring charge motors Over load : 110% of rated load, Power factor ≥ 90%, with feature of suitable for existingbreaker to handle tripping & Auto sensor to detect built with AND Gate software for prompt recharge in all respect either in all tripping or at the mode of power failure with standard battery selection, indications, Mains, Emergency, Over load, reverse polarity battery charging with SMPS ON/OFF switch. Meters & display a) Input Voltage b) Input Current c) Output Voltage d) Output Current e) Water Temperature f) Digital Multifunction All reading should be displayed on HMI. The kW, kVA, PF, V, I readings should be displayed by separate energy meter on the front panel. Make: -ABB / Schneider/Exide/ Or Minimum ISO 9001 :2015 Certified approved by GEThe Contractor has to submit Original Purchase Vouchers, Guarantee Certificate from OEM before installation. |
| 12 | Dismantling of old battery bank and S & F of in replacement of Battery Backup 360 Volts 42 AH system with relays AC & DC operatable with extra relaying schemes attached to the equipment including part of the network with their own relaying system. Equipped withbackup relay’s to operate in any failure of tripping of circuit breaker due to main relays capable to sustain Mechanical defect of moving parts of the main relay, Failure of DC power supply to the relay,Failure of tripping pulse to the contactor/ MCCB from relay, Failure of current or voltage to the relay from existingcircuits etc.Equipeed with another line of protection as back up relaying. essentially have everything separate from main relaying scheme. just because backup relay must not fail to operate in the event of failure of main relays. in spite disconnect main relays from the system for preventive maintenance or trouble shootings. Because of presence of backup relays, no interruption has to take place for any equipment or circuit. During this time back up protection scheme takes care of the protection of the system. As the back relaying is second line of protection it must be slow in action than main relay so that it can only be operated when the main relaying scheme of the system/equipment fails. Make SIEMENS/ABB/ Exide . Original OEM is entitled for work . Contractor has to ensure it.Necessary test certificates to be approved by Engg-in-Charge first before execution at site . |
| 13 | Dismentaling of old unservicable fuse kit, kat , existing IDMT O/C & E/Frelays,burnt contactoresreplacement with new microprocessor typesolid state electronic ON LOADprotection system with Plug Setting Multiplier of Relay, Time Setting Multiplier of Relay, Time vs. PSM Curve settings,Calculation of Relay Operation Time,1. Current setting. 2. Fault current level. 3. Ratio of current transformer. 4. Time / PSM curve. 5. Time setting.Output impedance shall be 3.0 to 5.0 percent,The cardshall be manufactured such that it will maintain electrical properties, even under severe overload, under/over voltage and under/over frequency conditions. Input correction range shall be -30% to +20% of nominal input voltage. The system design shall be capable of operating at an input frequency range of -15% to +10% of nominal, without clearing protective devices or causing component failure within the Microprocessor Card.Upon turn on or restart, the output of the Microprocessor Card shall not exceed the specified output regulation limits. if the input voltage or frequency exceeds programmable minimum or maximum set points for a programmable time period (factory set for 10 seconds), the Microprocessor Card shall electronically shut off. When electrical parameters are back within acceptable limits for a programmable time period (factory set for 60 seconds), the Microprocessor Card shall automatically restart to provide conditioned power to the load. If the input parameters are within acceptable limits, but the output voltage is outside of acceptable programmed limits, the Microprocessor Card shall electronically shut off and require a manual restart. The Microprocessor Card shall be capable of operating at 100% rated load capacity continuously, 200% rated load for 10 seconds, 500% rated load for 1 second and 1000% rated load for 1 cycle. Operating efficiency shall be a minimum of 96%, typical at full load. Transverse-mode noise attenuation shall be 3dB down at 1000Hz and 40dB down per decade to below 50dB with a resistive load. Common-mode noise attenuation shall be 140dB or greater. |
| 14 | Contd....from item No 11The Microprocessor Card shall respond to any line voltage variation in 1/2 cycle while operating linear or non-linear loads, with a load power factor of 0.60 of unity. Peak detection of the voltage sine wave shall not be permitted to avoid inaccurate tap switching due to input voltage distortion.Line Voltage Regulation and Correction Time: Output regulation shall be +5%, -6%, given an input voltage variation of -30% to +30% for nominal, when within +/-5% of the nominal frequency. The Microprocessor Card output voltage shall be corrected to within +5%, -6% or less within 1 cycle per tap for an under voltage condition. For an over voltage condition, the output shall correct within 1 cycle directly to the appropriate tap without stair-casing intermediate taps. Typical correction time shall be 1 to 2 cycles. Load Regulation: No load to full load regulation shall be 3% typical under linear loading. Note: The Microprocessor Card shall be adjusted so that the combination of line voltage regulation and linear load regulation results in a maximum output voltage variation of +7% to -8% from nominal, when within +/-5% of the nominal frequency.Operating Frequency: The Microprocessor Card shall be capable of operating at +10% to -15% of the nominal frequency, 50Hz or 60Hz, with programmable high and low limits to alarm and electronically shut down the Microprocessor Card. Limits shall be set to +/-2Hz from nominal and electronic shutdown shall occur if limits are exceeded for 10 seconds. Once back within limits for a programmable time period of 60 seconds, the Microprocessor Card shall automatically restart. 2.5 Site Specific Data:Input Over Current Protection: The Microprocessor Card shall be provided with an integral, three pole, molded case, manually operated, thermal magnetic input circuit breaker rated at 125% of the full load input current. In addition, the system input current, Phase R, Y and B, shall be monitored and digitally displayed. A |
| 15 | Contd....from item No 11.01programmable over current alarm shall be provided. Bypass Switch: The Microprocessor Card shall be provided with an integral break before make rotary bypass switch. The Microprocessor Card shall be either on line or bypassed with one turn of the switch. On models where the input and output nominal voltages are different, a regulator bypass shall be provided in which the shielded isolation transformer will remain on line to provide voltage transformation and isolation. On models where the input and output nominal voltages are the same, an integral break before make rotary maintenance bypass switch shall be provided to wrap around and isolate the Microprocessor Card. In this case, an input neutral conductor(s) shall be provided and the bypass switch shall bypass the output neutral, as well as, the phase conductors. The bypass switch circuitry shall be wired such that it cannot switch the unregulated power directly to the active load. Bypass switch actuation shall trip the Microprocessor Card input breaker, so that the facility load must then be reconnected using the input breaker.Alarms: The Microprocessor Card shall be provided with an input over/under voltage, input over current, over/under frequency, voltage phase reversal, voltage phase imbalance, output over/under voltage, and output over current alarms. The alarms shall automatically reset upon return to nominal operating conditions. Remote communication of alarms via a contact closure shall be provided. Optional digital communication via RS232 and RS485 shall be made available. The Microprocessor Card shall be provided with individual “Fuse Failure” indicator lights, phase R, Y and B, on the front panel for diagnostic purpose.The Microprocessor Card shall be equipped with True RMS Measurement, Stores last 15 faults,Detection of fault with display of parameter value, USB configuration with PRKAB, CBCT open detection circuitEarth Leakage Re to Detect and protect instruments from leakage |
| 16 | Contd....from item No 11.02current,Dual Color LED for fault indication, : A digital input meter shall be provided to display line voltages, line currents, frequency, kVA, kW, and power factor. A separate digital output meter shall be provided to display line to line voltages, line to neutral voltages, phase currents and neutral current. Both meters shall have programmable minimum and maximum value set points, recorded in EEPROM. Both meters shall be capable of optional remote communications via RS232 and RS485. Input/Output Cable Connections: The Microprocessor Card shall have provisions for the installation of cable lugs directly to the input/output bus bars or conductors to the input/output terminals provided.Grounding Cable Lugs: The Microprocessor Card shall have provisions for the installation of cable lugs directly to the ground bus bar or conductor to the terminal provided.MAKE / ABB/ CG/C&S/ASHIDA MIN ISO 9001:2015 CERTFIED APPROVED BY GEONLY Original OEM is entitled for work . Contractor has to ensure it.Necessary test certificates &Latest Purchase Vouchers to bescrutnised / approved by Engg-in-Charge & GE first before execution at site . Any Defect occuring during this period due to bad workmanship of material, manufacturing defect shall be rectified or replaced free of cost. The contractor shall furnish written gaurantee on letter head for above mentioned to the GE immidiately after completion of work.Contractor has to ensure Post Audit of work, without that completion will not be issued. |
| 17 | Dismantling of old U/S protection , alarm & replacement with new, installation , testing , commissining of DC Failure protection system unit suitable for 33kV Control Panel and exisiting Breaker withIndication by High bright LED Built in test & accept push buttons Built in audible alarm Suitable for wide range of DC supply Three No’s. normally open contacts also given for externel application like remote window or alarm High barrier withShrouded connectors for easy & safety terminations suitable for11 KV/ 33 KVswitchgear with built inTECHNICAL SPECIFICATION: Input DC Supply : 20 to 250V DC. Input AC Supply : 230V AC ± 20%. Audible alarm output : 90dB at 1 Meter – Intermittent sound. Response time : Less than 100 msec. (Indication & alarm When DC fails).Output relay contacts : 1 NO Contacts Contact rating : 5A at 230VAC/30VDC Mounting Type : Flush mounting. Make ISO 9001:2015 Certified or approved by GE or accepting Officer . ONLY Original OEM is entitled for work . Contractor has to ensure it.Necessary test certificates &Latest Purchase Vouchers to bescrutnised / approved by Engg-in-Charge & GE first before execution at site . Any Defect occuring during this period due to bad workmanship of material, manufacturing defect shall be rectified or replaced free of cost. The contractor shall furnish written gaurantee on letter head for above mentioned to the GE immidiately after completion of work. Make Partner/Seco /ISO 9001 : 2015 Certified |
| 18 | Supply, installation ,testing and commissioningof 3 Phase Digital Micro Chip Programmer Main Automatic voltage , current , Power Factor analyserwith Automatic Micro processorbuilt with integrated operationaldifferential voltage relay built with vaccume impregnated balance core transformer type with Voltage, Frequency and Zero Sequence Voltage with VECTOR SHIFT Detection 88 -264 V delta to delta3 phaseDelta Mode 11 KV EHT operatedfor over voltage sensorcircuit up to 15 KV ( HT side), & lower voltage sensor circuit starting from 08 KV ( HT side) s & unbalance voltage scanner with 01 voltadjustable in each sensitivity relay set unit consisting of vacuum impregnated step down transformer standingprimary voltage up to 300 volts with 1100 volts insulation & standing 1100 volts for 03 sec Secondary with potential voltage 20 volts . Trip setting : Phase failure 3 sec Max. factory Set. Under Voltage and over voltage =2KV to 15KV AC (Adjustable Individually , Adjustable Recovery Time =2 sec Min Power On Delay=10 sec Max. Mode of Operation =Auto/Manual Display= LED displays Monitoring =Phase to Phase Ambient Temperature Operation=-10 C to +55 C Storage -25 C to 80 CInsulation resistance =>100M ohm @ 500V DCDielectric strength= a) 36KV AC, 50Hz for 3seconds (Between carrying& non-current carrying parts) b) 1.5KV AC, 50Hz for 1 minute. (Between contacts & control circuit) c) 750V AC, 50Hz for 1 minute.(Between non-continuous relay contacts) Inrush current delay 1 to 60 sec selectable complete sensores of Volts & Amps individual line current with suitable rupturing 25 KA not exceeding 50 KA to flowshunt trip commandfitted protection unit suitable for load66 KV VCB Breakersthree phase type including inductive , capacitive / reactive loads withTraditional power controllers in phase angle firing mode , Harmonic distortion reducer merging to Earthing with trip relay if it approaches to saturation point includingOptimize the losses intransformers, cables and switchgears. , CO2 emissions. |
| 19 | Contd....from item No 13Reduced disturbances on surrounding electronic equipment. having following password protected featuresPhase Unbalance, Phase Reversal, Phase Missing, Under Voltage and Over Voltage Monitor and Control, Neutral Open Protection. Under Frequency ,Over Frequency Input voltage 11KV/110V AC(3Ph-4W) Input Frequency 50 Hz ±2%, Power consumption 15VA / 3W, Control output 2c/o rated for 10A @ 250VAC /28VDC resistive load, Setting Accuracy – voltage ± 4V , Trip time delay 1 to 250secs settable for UB, OV, UV,Trip time accuracy ± 1% of set delay ±2sec. Trip setting :Phase failure 3 sec Max. factory set. Phase Reversal Instantaneous tripPhase Un balance 1 to 20% (Adjustable)Under Voltage and over voltage 5V to 60V AC (Adjustable Individually)Over current protection with IDMT curve Under current protection Current loss protection Current unbalance protection equipped with 4 Digits ultra-bright Seven segment LED Display Trip relay cum DPM with Class 0.5 True RMS measurement capable to measures distorted waveform up to 15 Harmonic. Previous fault Storage Instrument memorizes the last 15 faults occurred. LED indications - LED indication for Relay-1 and Relay-2 status. - Trip indication on 4 Digit display. - Dual colour LED for per phase indication green colour for normal condition and Red colour for faulty condition. AND function User can use ANDing function to set trip on any two-fault condition. Configuration via USB-based software programmer with configuration to the Meter using USB-based Auto / Manual reset In auto mode instrument automatically clears itself... User selectable 3 phase 3W or 4W User can on site program the network connection as either 3P4W / 3P3W network using front panel keys Adjustable set point for - Over current - Under current - Current loss - Current Unbalance Adjustable time delay for - Over current - Under current - Current loss - Current Unbalance Trip or Buzzer mode Relay can be used to protect the system or simply to control the buzzer. |
| 20 | Contd....from item No 13.01Trip mode is for protection purpose and Buzz mode is for buzzer control. User Selectable CT Secondary The input rated current can be programmed on site as 1A to 5A using front panel keys. Compliance to International Safety standard Nominal Input Current (AC RMS) 5 A System CT Secondary Values 1 A to 5 A programmable on site System CT Primary Values 1 A to 999 kA programmable on site Auxiliary Supply Auxiliary Supply Voltage 60 V – 300V AC-DC - Aux Supply Frequency 45 to 66 Hz range Overload Withstand Current 20 x for 1 second, repeated 5 times at 5 min Operating Measuring Ranges Current Range 5...140% of CT Secondary Frequency 40...70Hz Reference condition for Accuracy Reference Condition 23°C +/- 2°C - Input waveform Sinusoidal (distortion factor 0.005) - Input Frequency 50 or 60 Hz ±2%-- Auxiliary supply voltage Nominal Value ±1% - Auxiliary supply frequency Nominal Value ±1% Trip, Reset Delays, Power ON ±140 msec or ±5% of Set Delay, Whichever is Greater (WIG) Influence of Variations Temperature coefficient : 0.05%/°C for current Applicable Standards EMC IEC 61326-1:2012, Table 2 - Immunity IEC 61000-4-3. 10V/m min – Level 3 industrial Low level - Safety IEC 61010-1-2010, Permanently connected use - IP for water & dust IEC60529 - Pollution degree: 2- Installation category: 300V CAT III / 600V CAT II- High Voltage Test 2.2 KV AC, 50Hz for 1 minute between all Electrical circuits. Environmental Operating temperature -10 to +55°C On Delay programable 1sec to 30 sec as desired at siteMax. Mode of Operation |
| 21 | Contd....from item No 13.02Auto/Manual Display 7 segment LED displays Monitoring Phase to Neutral Ambient Temperature Operation -10 C to 55 C Storage -25 C to 80 C Humidity MAX 85% RH @ 40 C Service life (under no load) 10 operations minimum Electrical life (under full load) 10 operations minimum Insulation resistance >100M ohm @ 500V DC Dielectric strength 2.5KV AC, 50Hz for 1 minute (Between current carrying& non-current carrying parts)1.5KV AC, 50Hz for 1 minute. (Between contacts & control circuit) 750V AC, 50Hz for 1 minute. (Between non-continuous relay contacts) Electrical Connection Screw type terminals with self-lifting clamps (Make:-L&T/ ABB/ SCHNEIDER/PARTNER ). ONLY Original OEM is entitled for work . Contractor has to ensure it.Necessary test certificates &Latest Purchase Vouchers to bescrutnised / approved by Engg-in-Charge & GE first before execution at site .Any Defect occuring during this period due to bad workmanship of material, manufacturing defect shall be rectified or replaced free of cost. The contractor shall furnish written gaurantee on letter head for above mentioned to the GE immidiately after completion of work.Contractor has to ensure Post Audit of work, without that completion will not be issued. |
| 22 | New Supply, installation, commissioning of programmers equipped with real time power analyser / recorder complete with capacity to undertake multipleMODBUS DATA multifunctional meters with following specifications as 4G/ 3G/ 2G / Ethernet based IIoT Controller with modem input supply 230VAC, 0.5A max with multi-protocol capability Processor: Cortex-A53 64-bit SoC @ 1.2GHz RAM: 1GB Flash memory: 12GB Operating temperature: -20 to +70°C Ports: Must have an Ethernet, RS485 and USB (user defined) Remote terminal unit (RTU): 4G/ 3G/ 2G SIM cards for 5 years subscription. Data services must be from at least two reliable service providers and system should support automatic switching to 2nd service provider in case of low network without any intervention. System should support changing of service providers without changing SIM cards (future ready). Future ready RTU must have Modbus, IEC60870, IEC61850, MBUS, DLMS (all mandatory and selectable). Any other future open-source protocol (that uses RS485 or TCP port) must be provided free of cost for the period of at least 5 years (OEM declaration mandatory). Capable of capturing multi-function meter along with Run Hours as well as other fields from any compatible substation/ metering equipment Communication interface & Communication protocols Modbus, IEC60870, IEC61850, MBUS, DLMS (all mandatory and selectable on all adequate ports). Any open-source protocol (for RS485 and ethernet port) will be supported for five years without any cost (OEM declaration mandatory) Enclosure with Energy meter connectionMust support different make models of energy meters in same daisy chain Time payload 1 min, 5 min, 15 min configurable remotely with real-time anomaly detection Technical detailsReal-time KW, KVA, KVAR, phase-wise, consumption KWh, KWh, KVarh, KVAh, PF, phase-wise PF, Hz, I, Ig, In, VLL (phase wise), VLN (phase wise), Vn, Vg, harmonics, voltage and current unbalance User Interface The cloud-based facility management system should enable controlling substations and facilities. The system should support adding more parameters in future with minimal changes. AF should have a mechanism to proactively know when some equipment is not giving data / has errors without coming to site. |
| 23 | Contd....from item No 14User interface should be remotely accessible on internet, with secure login credentials. User interface should work on secure https. Communication between data gathering, and data storage should be over a secure encrypted channel. IIOT controller must have inbuild local control capability to operate in case of network unavailability. However, control logics must be configurable remotely. The user-interface should have minimum of following tabs (all dashboards, reports must be self-configurable without any scripting or OEM intervention): Dashboard - To evaluate captured parameters at a glance with current, hourly, daily, weekly, monthly, & yearly. End-user should be able to create Dashboards on their own, without AF involvement. End user should be able to define number of rows / columns in dashboard, merge cells of dashboard to make some areas small / large, configure row heights to provide flexibility in how data is displayed (ex. multiple numerical KPIs in a smaller row, and graphs in a larger row to utilize displayed area of dashboard optimally) Dashboards should allow display of both graphical data, as well as numerical KPIs (max, min, aggregated Sum, averaged values over day, week, month) For Graphs & KPIs displayed on Dashboard, user should be able to choose different time durations directly from Graph/KPI’s options to update the Graph/KPI dynamically End user should be able to create multiple dashboards User should be able to select and zoom-in / zoom-out on specific area within graphs User should be able to save graphs as an image in various formats (.png, .jpeg etc) For multiple Dashboards, user should be able to define display order of Dashboard in navigation (for ex: which is more important and should come first) AF should be able to turn off/on options in graphs to maximize utilization of available display area for each graph (ex. axis, legends, menu options, title etc.) Graphs should support at least following visualizations: line graph, pie graph, donut graph, area graph, bar graph, heatmap graphs User should be able to plot data from different sites on same graph Layout - Diagram of the system with SLD viewing options. |
| 24 | Contd....from item No 14.01Electrical SLD with all IEC symbols is must Chart - graphs based on data from multiple sources such as inverter and local weather databases.Histograms/Pie charts/Bar graphs/line graphs/ donut graph, area graph, heatmap graph shall be available. System should support Time vs Time comparison of captured parameters by showing data of interested days/months adjacent to each other (example: 9th day of this month, and last month displayed adjacent to each other)System should support Spend Analysis (money equivalent of energy, and not just units of energy) System should support creating user-defined KPIs (max, min, aggregated Sum, averaged values over day, week, month) system should support creating user-defined benchmarks, and displaying data in charts / dashboard comparing against these benchmarks System should support saving frequently used analytics charts for later users. All saved charts should be available to choose with a single-click. System should support showing analytics data in graphical and tabular form. Facility to export data over a custom time interval to Excel shall be available. Reports should be user-defined and not fixed (hardcoded into the system). System should support sending daily, weekly and monthly reports. Daily reports should be sent next day morning over email incorporating all data from previous day. There should be a mechanism to turn reporting sending of scheduled reports ON/OFF There should be a mechanism to send a pre-created report on-demand (and not just as scheduled daily / weekly / monthly report) Settings - To view the metadata related to the system, such as the site name and installation date, details of equipment at site etc. Alarms and event logs – Alarm should Issue a system update that the system has detected. Passwords should be stored in encrypted format.Website should be accessible on all platforms and be compatible with popular browsers such as IE, Chrome, Firefox, Safari etc. Online Administration: All administration is handled online via a current web browser Audit Trail: Administrators can access logs in the backend on need-basis where they can view changes that have been made to the database for critical information. |
| 25 | Contd....from item No 14.02Data Backup should support PITR (Point-in-time-recovery). Scheduler for auto archival and backup of application and database to a different machine which should be capable of coming online by simply firing a script button in event of downtime of primary server. The database should use encryption at rest to persist the data in database.Secure password protected login for administrative actions in the system. All updates to data gathering hardware should be through OTA (over the air). No static IPs shall be made available at sites. The complete equipment must be programmedwith protection CT inside the existingLow Tension switchgear /breaker / Switching Contactors along withmultifunction microprocessor digitalprogrammer having Main measurements and functions include: Voltage: phase, line and system values Current: phase values (neutral current calculated) Power: apparent, active and reactive phase and total values Power Factor per phase and total Frequency of measured voltage value HIGH LOW AVERAGE - - value functions for all measurements Maximum demand of power and current values Voltage and current asymmetryTotal harmonic distortion ( ): voltage and current THD Energy meters for active, reactive, apparent partial and total values, per phase and system values Hour counter for programmable total and partial hours Phase active power unbalancemust saturate sufficiently high to allow a relatively accurate measurement of the fault current by the protection whose operating threshold can be very high.with built in high Accuracy Limit Factor (ALF)ratio between the nominal overcurrentand the rated current. so that existing switchgear relay must be able to withstand high overcurrent’s also featured withReal accuracy factorratio between the overcurrent , nominal error and the rated current .with following specifications insulation level voltage .433 KV ratio 100/5A - to 500/5A Core 3 class PS, KPV >= 150 Volts Imag at vk/2<= 30 ma , RCT at 75C<= 2 Ohms short time rating 15 KA for 1 second , SIEMENS/SCHNIDER/ ABB. approved by GE minimum ISO 9001:2015 Certified . Note :- The Entire work at siteis to be executed onlyby OEM approved by GE.Original OEM is entitled for work . Contractor has to ensure it.Necessary test certificates to be approved by Engg-in-Charge first before execution at site. |
| 26 | Dismantling of old damaged u/s lights & replacement with new S/I/T/C of Degree of protection IP65 LED Integral LEDs 12 V, 24 V, 30 V, 48 V, 60...63.5 V, 110 V, 220...230 V AC/DC Colour White, Green, Red, Amber, Blue, Yellow of Ø 22/0.866 in. plastic control and signalling units Make as directed by Engg-in -charge |
| 27 | S/I/T/Cof 11kVCurrent Transformer (CT)with three-core CT cores required for metering, protection, and REF protection in an existing11kV system Typical CT Core Requirements for 11kV System Function CT Core Required CT Core Class Burden (VA) Metering 1 core Class 0.2 / 0.5 5–15 VA Protection 1 core Class 5P10 or 10P10 15–30 VA (typically) REF Protection 1 core Class 5P20 or PS (special) Depends on scheme (15–45 VA or more) Metering: Needs high accuracy (Class 0.2 or 0.5). Low burden. Protection: Requires higher accuracy at higher currents (Class 5P10 or 10P10). Should operate correctly under fault conditions. ŌC/EF used for overcurrent and earth fault protection REFprotection Very sensitive to current mismatch. Requires matched CTs with wide dynamic range (Class PS or 5P20). Used on both sides of a transformer. For an 11kV feeder, typically 3 CT cores per phase are required: • Core 1 – Metering • Core 2 – Protection (OC/EF) • Core 3 – REF The OEM of CT must take the data like lead resistance, relay burden, and system fault level from the MES before designing PS class CT. Core 1 & 2: Protection Cores These cores are designed to operate accurately during fault conditions and saturate quickly above the fault level to protect connected relays. Accuracy Class: Typically 5P or 10P (e.g., 5P10, meaning 5% error at the accuracy limit factor of 10).Burden: Typically 10 VA, 15 VA, or higher, depending on the connected relay\"s requirements and cable length.Accuracy Limit Factor (ALF): e.g., 10 or 15. Special Purpose (PS) Class: For high-impedance or differential protection, a PS class is used, specified by: Knee Point Voltage Not less than 700 V (depends on ratio and burden).Excitation Current Specified at a certain percentage of the knee point voltage. Secondary Winding Resistance Measured and considered for relay settings. Saturation Factor: Minimum of 10 for standard protection cores.Core 3: Metering Core This core is designed for high accuracy under normal operating conditions. It has a low Instrument Security Factor (ISF) to protect the connected meters from damage during high fault currents. Accuracy Class: Typically 0.2S, 0.5, or 0.5S.Burden: Typically 5 VA or 10 VA.Instrument Security Factor (ISF): Less than 5 at the lowest ratio to protect meters. |
| 28 | S/I/T/C flush mounted installation ofREFIR-protection relaycomply with the IEC/DIN regulations required for the specific protection application. Plug-in technology& easy operation, quick fault-analysis and optimal communication capabilities are based on the microprocessor technology with following characteristics:Integration of multiple protective functions into one compact housing,User-friendly setting procedure by means of DIP-switches,Compact construction type by SMD~technology & also Complete suitable for earth fault directional detection with Rated data: Nominal current IN : 1A/5A Nominal frequency fN : 50/60 Hz Power consumption : 97% Returning time : 30 ms Minimum operating time : 30 msOutput relay characteristics: Maximum breaking capacity : 250 V AC / 1500 VA / continuous current 6 A Design standard : VDE 0435, part 303, IEC 255.4, BS 142 Specified ambient service Temperature range: for storage : - 40°C to + 85°C for operating : - 20°C to + 70°C Environmental protection class F as per DIN 40040 and per DIN IEC 68 2-3 : relative humidity 95 % at 40°C for 56 days Insulation test voltage, inputs and outputs between themselves and to the relay frame as per VDE 0435, part 303 IEC 255-5 : 5 kV; 1.2/50 Hz; 1 min. (except supply voltage inputs) Impulse test voltage, inputs and outputs between themselves and to the relay frame as per VDE 0435, part 303 IEC 255-5 : 5 kV; 1.2 / 50 μs; 0.5 J High frequency interference test voltage, inputs and outputs between themselves and to the relay frame as per DIN IEC 255-6 : 2.5 kV / 1MHz Electrostatic discharge (ESD) test as per DIN VDE 0843, part 2 IEC 801-2 : 8 kV Electrostatic discharge (ESD) test as per DIN VDE 0843, part 4 IEC 801-4 : 4 kV / 2.5 kHz, 15 ms Radio interference suppression test as per EN 55011 : limit value class B Radio interference field test as per DIN DVE 0843, part 3 IEC 801-4 : electrical field strength 10 V/m Mechanical tests: Shock : class 1 acc. to DIN IEC 255-21-2 Vibration : class 1 acc. to DIN IEC 255-21-1 Degree of protection - front of relay : IP 54 by enclosure of the relay case and front panel (relay version D) Weight : approx. 1.5 kg Degree of pollution : 2 by using housing type A 3 by using housing type D Overvoltage class : III Influence variable values: Frequency influence : 40 Hz < f < 70 Hz: |
| 29 | Dismantling of old damaged 4 CORE 2.5 sq mm wire and replacement with new necessary for metering & motor operation |
| 30 | Dismantling of old damaged 4 CORE 1.5 sq mm wire and replacement with new metering |
| 31 | Dismantling of old damaged 2 CORE 1.5 sq mm wire and replacement with new protection activation |
| 32 | Dismantling of old damaged 2 CORE 0.5 sq mm wire and replacement with new for data analysation |
| 33 | M&L Earthing complete copper plate 60×60cm ×3.15mm thick electrode buried in ground vertically not less than 2.25mtrs deep below ground level with top edge of the plate not less than 1.5mtrs below ground level with 20×3mm copper strip as earthing lead including necessary excavation and earth work (in any of strata) providing charcoal dust, salt mixed with fine sand in continuous layers, PCC (1:3:6 ) type C1 in chember ,Precast 50 mm thick in cement ( 1: 2:4) type B.1 with CI framewith cover, 20mm dia bore light grade GI watering pipe furnel etc fixing of GI Pipe 40 mm bore protection for earthing strip from earth pit to test point complete & making connection all as specified in Electrical plate No 3 and as directed by Engineer-in-Charge. |
| 34 | M&L Earthing complete with 60cm x 60cm x 6 mm thick GI plate electrode buried in ground vertically not less than 2.25mtrs deep below ground level with top edge of the plate not less than 1.5mtrs below ground level withGIstrip of size 32 x 6mm as earthing lead including necessary excavation and earth work (in any of strata) providing charcoal dust, salt mixed with fine sand in continuous layers, PCC (1:3:6 ) type C1 in chember ,Precast 50 mm thick in cement ( 1: 2:4) type B.1 with CI framewith cover, 20mm dia bore light grade GI watering pipe furnel etc fixing of GI Pipe 40 mm bore protection for earthing strip from earth pit to test point complete & making connection all as specified in Electrical plate No 3 and as directed by Engineer-in-Charge. |
| 35 | Note:-Amount of schedule of credit shown here-in-after shall be deducted from the total quoted amount to arrive at the amount of Acceptance of the tender. |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2025 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail