| 1 | Dismantling unserviceable broken electric poles/ struts, any size and type with disconnecting all connections, demolition of concrete foundation including excavation, earth work, as required and removing the same from site complete all as specified and directed. |
| 2 | Material and labour for supply, erection of Prestressed concrete pole, 9.0 metres long,102mm x 172mm at top and 102mm x 279mm at bottom, class 10 complete including painting two coats of white bituminous paint throughout internally and externally up to the planting depth and the remaining portion of the exteriors shall be painted with two coats of exterior weather proof paint after necessary preparation of surfaces complete all as specified and directed by Engr-in charge. |
| 3 | M&L for Pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 100mm height, 65mm dia for 1100 volts grade, including taking down old unserviceable insulator complete all as specified and directed. |
| 4 | M&L for preparation old painted surface of cement concrete poles of any size from pole coping to top of pole including struts, cross arms, clamps, etc painting with two coats of approved colour of aluminium paint on cross arms over one coat of red oxide zinc chrome primer and two coats of exterior weather proof paint and numbering of poles with black synthetic enamel paint complete all as specified and directed. |
| 5 | M&L for preparation old painted panels surfaces of any size, top to bottom and left to right, internal and external surface complete spray painting with Siemens powder coated grey colour complete all as specified and directed. |
| 6 | Material and labour for laying XLPE insulated, PVC innersheathed, extruded PVC outer sheathed, LT underground cable, armoured with glavanised steel strip, heavy duty electric cable with stranded aluminium conductor of cross-sectional area 3.5 core 150Sqmm, 1100 volts grade, as per IS 7098 (Part 1) 1988, laid in trench, fixed on wall/pole drawn through pipe etc includingof provision of lugs & testing, including taking down old unserviceable LT UG cable complete all as specified and directed. |
| 7 | All as per item Ser No. 6.00 here in before, but cable of cross-sectional area 3.5 core 70 sqmm, including taking down old unserviceable LT UG cable complete all as specified and directed. |
| 8 | All as per item Ser No. 6.00 here in before, but cable of cross-sectional area 3.5 core 50 sqmm, including taking down old unserviceable LT UG cable complete all as specified and directed. |
| 9 | All as per item Ser No. 6.00 here in before, but cable of cross-sectional area 3.5 core 35 sqmm, including taking down old unserviceable LT UG cable complete all as specified and directed. |
| 10 | All as per item Ser No. 6.00 here in before, but cable of cross-sectional area 3.5 core 25 sqmm, including taking down old unserviceable LT UG cable complete all as specified and directed. |
| 11 | All as per item Ser No. 6.00 here in before, but cable of cross-sectional area 4 core 16 sqmm, including taking down old unserviceable LT UG cable complete all as specified and directed. |
| 12 | All as per item Ser No. 6.00 here in before, but cable of cross-sectional area 2 core 16 sqmm, including taking down old unserviceable LT UG cable complete all as specified and directed. |
| 13 | Material and labour for laying XLPE insulated, PVC innersheathed, extruded PVC outer sheathed, LT underground cable, armoured with glavanised wire, heavy duty electric cable with stranded aluminium conductor of cross-sectional area 2 core 10 sqmm, 1100 volts grade, as per IS 7098 (Part 1) 1988, laid in trench, fixed on wall/pole drawn through pipe etc includingof provision of lugs & testing, including taking down old unserviceable LT UG cable complete all as specified and directed. |
| 14 | S&F in repairs 1 run 10 Sqmm single core PVC insulated, FRLS, stranded copper conductor 1100 volts grade through in existing surface/ recessed steel/ PVC conduct complete all as specified and directed. |
| 15 | S&F in repairs 1100 volts grade heavy duty cable PVC insulated aluminium conductor as service connections served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 01 metre apart including 4 mm dia GI suspension wire one twin core cable flat or circular stranded conductor of size 4 sqmm 2 core complete allasspecifiedanddirected. |
| 16 | S&F in repairs 1100 volts grade heavy duty cable PVC insulated aluminium conductor as service connections served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 01 metre apart including 4 mm dia GI suspension wire one twin core cable flat or circular stranded conductor of size 6 sqmm 2 core complete allasspecifiedanddirected. |
| 17 | S&F in repairs 1100 volts grade heavy duty cable PVC insulated aluminium conductor as service connections served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 01 metre apart including 4 mm dia GI suspension wire one twin core cable flat or circular stranded conductor of size 10 sqmm 2 core complete allasspecifiedanddirected. |
| 18 | S&F cable route indicator for LT cable, cast iron material, 100 mm dia, round with 5-6 mm thick also paint whole plate with arrow for direction and two holes for mounting (3 mm embossed letter as appropriate) with angle including PCC 15x15x20 cm foundation complete allasspecifiedanddirected. |
| 19 | S&F MCCB 4 Pole, 415 V, adjustable type, 400 Amps with breaking capacity 36 KA, including taking out old unserviceable MCCB complete all as specified and directed. |
| 20 | S&F MCCB 4 Pole, 415 V, adjustable type, 250 Amps with breaking capacity 36 KA, including taking out old unserviceable MCCB complete all as specified and directed. |
| 21 | S&F MCCB 4 Pole, 415 V, adjustable type, 200 Amps with breaking capacity 25 KA, including taking out old unserviceable MCCB complete all as specified and directed. |
| 22 | S&F MCCB 4 Pole, 415 V, adjustable type, 160 Amps with breaking capacity 16 KA, including taking out old unserviceable MCCB complete all as specified and directed. |
| 23 | S&F MCCB 4 Pole, 415 V, adjustable type, 100 Amps with breaking capacity 16 KA, including taking out old unserviceable MCCB complete all as specified and directed. |
| 24 | M&L for danger notice plate of 1.6mm thick mild steel sheet, vitreous enameled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for LT, 25x15cm size complete all as specified and directed. |
| 25 | Supplying and laying synthetic Rubber insulated mats 2.50 mm thick for voltage upto 11 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable forelectrical shock safety of sizes 2m x 1m complete all as specified and directed. |
| 26 | Supply and laying 90 mm bore high density polyethylene pipes (HDPE) of pressure rating 6 kgf/cm2 laid in trenches including taking out old unserviceable pipes complete all as specified and directed. |
| 27 | Supply and laying 63 mm bore high density polyethylene pipes (HDPE) of pressure rating 6 kgf/cm2 laid in trenches including taking out old unserviceable pipes complete all as specified and directed. |
| 28 | Supply and laying 40 mm bore high density polyethylene pipes (HDPE) of pressure rating 6 kgf/cm2 laid in trenches including taking out old unserviceable pipes complete all as specified and directed. |
| 29 | Supply and laying 25 mm bore high density polyethylene pipes (HDPE) of pressure rating 6 kgf/cm2 laid in trenches including taking out old unserviceable pipes complete all as specified and directed. |
| 30 | S&F LT panel installing, testing and commissioning factory made and tested (CPRI type test certified), LT feeder pillar box (KIOSK), outdoor type, platform mounted, suitable for 415 V, 3 phase, 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated aluminium bus bars 400 Amps. The panel shall be dust, weather and vermin proof, IP 65 class protection and made of CRCA MS sheet 3.15 mm thick and 40x40x6 mm thick angle iron frame work, powder coated finish, front opening type, with aprons for cable entry, with double door shutters and locking arrangements (including provision of 65 mm Godrej (Freedom) lock with 2 keys, internal wiring with PVC insulated, copper conductor, FRLS cables, IS-694 marked of adequate size but not less than 4 Sqmm. Panel should be above ground level, including taking down old unserviceable panel complete all as specified and directed. Location- P-230 Harshan Enclave. The scope of work includes the following:- |
| 31 | (a) INCOMING(a) MCCB 4 Pole 250 Amps 415 Volts AC grade and 36 kA rupturing capacity - 01 No.(b) Digital voltmeter 0-500 volts square type flush pattern with 3 way selector rotary switch - 01 No.(c) Digital ammeter with CT ratio 400:5 square type with 3 way selector rotary switch - 01 no.(d) Indicators LED type RYB set - 01 set (Three Nos in each set) |
| 32 | (b) OUTGOING(a) MCCB 4 Pole 160 Amps 415 Volts AC grade and 25 kA rupturing capacity - 02 Nos(b) MCCB 4 Pole 100 Amps 415 Volts AC grade and 16 kA rupturing capacity - 01 No.(c) MCCB 4 Pole 63 Amps 415 Volts AC grade and 16 kA rupturing capacity - 03 Nos(d) MCB SPN 63 Amps 240 V with breaking capacity 10 kA - 03 Nos(e) Street light timer - 01 No. |
| 33 | (c) Platform for the panel with PCC 1:4:8 type D2 with 40 mm graded stone aggregate, 15 cm thick foundation, brick work in CM 1:6 with sub class \"B\" old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6 type C1 using 20 mm graded stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45 cm above the nearest road level.Note: All out going feeders shall be connected by cable through suitable size gland plate/ glands. |
| 34 | S&F LT panel installing, testing and commissioning factory made and tested (CPRI type test certified), LT feeder pillar box (KIOSK), outdoor type, platform mounted, suitable for 415 V, 3 phase, 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated aluminium bus bars 400 Amps. The panel shall be dust, weather and vermin proof, IP 65 class protection and made of CRCA MS sheet 3.15 mm thick and 40x40x6 mm thick angle iron frame work, powder coated finish, front opening type, with aprons for cable entry, with double door shutters and locking arrangements (including provision of 65 mm Godrej (Freedom) lock with 2 keys, internal wiring with PVC insulated, copper conductor, FRLS cables, IS-694 marked of adequate size but not less than 4 Sqmm. Panel should be above ground level, including taking down old unserviceable panel complete all as specified and directed. Location- Cariappa pump house & Poojapura Pump house. The scope of work includes the following:- |
| 35 | (a) INCOMING(a) MCCB 4 Pole 100 Amps 415 Volts AC grade and 25 kA rupturing capacity - 01 No.(b) Digital voltmeter 0-500 volts square type flush pattern with 3 way selector rotary switch - 01 No.(c) Digital ammeter with CT ratio 400:5 square type with 3 way selector rotary switch - 01 No.(d) Indicators LED type RYB set - 01 set (Three Nos in each set) |
| 36 | (b) OUTGOING(a) MCCB 3 Pole 63 Amps 415 Volts AC grade and 16 kA rupturing capacity - 02 Nos(b) Star delta starter suitable for up to 20 HP monoblock pump set - 02 Nos |
| 37 | (c) Platform for the panel with PCC 1:4:8 type D2 with 40 mm graded stone aggregate, 15 cm thick foundation, brick work in CM 1:6 with sub class \"B\" old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6 type C1 using 20 mm graded stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45 cm above the nearest road level.Note: All out going feeders shall be connected by cable through suitable size gland plate/ glands. |
| 38 | M&L for Earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6.0mm thick buried directly in ground vertically to a depth not less than 2.25 metre below ground level with top edge of earth plate at a depth of not less than 1.5 metre below normal ground level, connected to galvanised earth lead of GI strip of size 32x6mm by means of GI Bolts, Nuts, check nuts and washers of the earth and thimbles and other end of the earth strip connected to earthing test point and protected by galvanised iron pipe light grade 50mm bore from earth plate to Panel/ DBs and water pipe 20mm bore GI medium grade raised up to a level of 50cm above ground level with plug at top, earthing pit in PCC (1:3:6) type C-1 RCC pre-cast (1:2:4 typeB-1) cover slab of 50 mm thick using 8.00mm dia CTD bars reinforcement both ways at 150 mm centre to centre with handle, 10 mm dia MS bars, wire mesh, funnel and providingcharcoal or coke and salt in alternative layers of 15 cm includingnecessary earth work in soft/ loose soil, returning, refilling and removing of surplus soil to a distance not exceeding 50 mtr testing complete all as shown in electrical plate No-3 of MES Schedule Part-I of SSR-2009, including taking out old unserviceable earthingcomplete all as specified and directed.Note : If the desired resistance is not found, the earthing shall be done by the contractor at no cost to Govt. |
| 39 | Removing grass, vegetation and bushes growing at all around electric substations area, premises and keep all the substation yards neat and clean complete all as per the direction of Engr-in-Charge.Note: Unit rate quoted deemed to include to keep the installation neat and clean throughout the period of contract. |
| 40 | Excavating in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth for laying ofUG cable, pipe, pole, stay etc and getting out soft/ loose soil including bottom surface to required level complete all as specified and directed. |
| 41 | Excavating in trenches not exceeding 1.5m wide and exceeding 1.5m but not exceeding 3.00m in depth for laying of UG cable, pipe, pole, stay etc and getting out soft/ loose soil including bottom surface to required level complete all as specified and directed. |
| 42 | Returning, filling in using soil obtained from excavation including spreading, leveling, watering and well ramming in layers not exceeding 25 Cm complete all as specified and directed. |
| 43 | Removing excavated surplus soil to a distance not exceeding 50 Mtr and depositing where directed at a level not exceeding 1.5 Mtr above the starting point complete all as specified and directed. |
| 44 | M&L for PCC 1:4:8 type D-2 using 40 mm graded stone aggregate including use and waste of form work of concrete for pole and stay foundation complete all as specifiedand directed. |
| 45 | M&L for PCC 1:3:6 type C-2 using 40 mm graded stone aggregate including use and waste of form work of concrete for pole and stay foundation complete all as specifiedand directed. |
| 46 | M&L for PCC 1:2:4 type B1 using 20mm graded stone aggregate including use and waste of form work for pole coping/ any description complete all as specifiedand directed. |
| 47 | S&F RYB indicator LED type lamps as required in various panel including taking down old unserviceable lamps complete all as specified and directed. |
| 48 | S&F Ammeter and Voltmeter as required in various panel including taking down old unserviceable Volt and Ammeter complete all as specified and directed. |
| 49 | S&F sintex terminal box for street light connection with MCB 6 Amps, lugs including taking out old unserviceable box complete all as specified and directed. |