| 1 | Supply, installation, testing and commissioningdust & vermin proof LT electrical panel board, 3 phase and neutral, 415 volts, 50 Hz, AC supply, Outdoor type (protection class IP-54) fully compartmentalised for cable chamber and busbar chambers with adequate space made out of 3 mm thick CRCA sheet for load bearing like all over body, front and back cover with hinges and aldrops with DC locks CRCA poweder coated and 2.0 mm thick MS Sheet for non load bearing and portions, complete with one coat of powder coating including suitable angle iron/ flat iron frame work/ supports bottom 50x50x6 mm MS channel as base and chamber for metering equipment complete suitable for mounting following switch gear items internally connected with suitable capacity aluminium strip/ rods insulated and connection wirings with FRLSH copper conductor includingPCC pillars foundation of suitable size as directed by Engn-In-Charge, arrangements for bus bar trunking system, cable connectionusing new lugs complete with danger notice all as specified and comprising of the followings:-Note: (i) Existing cables which removed from old panel board will be fixed with new lugs during fixing in new panel board (as if required) (ii) Getting of approval for Panel board drawing from Engr-in-charge is necessary before fabrication. (iii) All switch gears should be fixed with 06 mm thick Fibre sheet.Incoming:-(a) MCCB 4 Pole, 415 V,adjustable type, 160 A with breaking capacity 36 KA - 1 Nos(b) LED/Neon indicator bulb in RYB Colour - 1 Set. (c) 4 No Aluminium Bus bar 350 Ampswith chamber. (d) Digital Multi function meter for showing Amps (upto 500 Amps) and Voltage (upto 500 voltage) with suitable CT and PT. (e) Electronic energy meters temper proof3 phase , 415 volt ,LCD display with polycarbonate coverenergy meters conforming to IS 13779/ as per latest policy, IP-54, with parameters to show data, time, current reading, load, PF, voltage and KWH. |
| 2 | Outgoing:-(a) MCCB 4 Pole, 415 V, adjustable type, 100 A with breaking capacity 25 KA - 01 Nos.(b) MCCB 4 Pole, 415 V, adjustable type, 63 A with breaking capacity 25 KA - 03 Nos(c) suitable cable gland for incoming and outgoing cable |
| 3 | All as per herein above item but forIncoming:-(a)MCCB 63 Amps 4 Pole, 415 V, 25KA- 01 Nos.(b) LED/Neon indicator bulb in RYB Colour - 1 Set.(c) 4 No copper Bus bar 200 amps with chamber.(d) Digital Multi function meter for showing Amps (upto 500 Amps) and Voltage (upto 500 voltage) with suitable CT and PT.Outgoing:-(a) MCCB 63 Amps TPN , 415 V,25KA- 01 Nos.(b) suitable cable gland for incoming and outgoing cable. |
| 4 | All as per herein above item but forIncoming:-(a) MCCB 4 Pole, 415 V, adjustable type, 320 A with breaking capacity 36 KA - 1 Nos(b) LED/Neon indicator bulb in RYB Colour - 1 Set.(c) 4 No copper Bus bar 700 Amps with chamber(d) Digital Multi function meter for showing Amps (upto 500 Amps) and Voltage (upto 500 voltage) with suitable CT and PT.e) Electronic energy meters temper proof3 phase, 415 volt, LCD display with polycarbonate coverenergy meters conforming to IS 13779/ as per latest policy, IP-54, with parameters to show data, time, current reading, load, PF, voltage and KWH.Outgoing:-(a) MCCB 4 Pole, 415 V, adjustable type, 125 A with breaking capacity 36 KA - 02 Nos.(b) MCCB 4 Pole, 415 V, adjustable type, 63 A with breaking capacity 25 KA - 02 Nos.(c) MCCB 4 Pole, 415 V, adjustable type, 200 A with breaking capacity 36 KA - 01 Nos.(d) Suitable cable gland for incoming and outgoing cable. |
| 5 | All as per herein above item but forIncoming:-a) MCCB 400 Amps 4 Pole, 415 V,36KA -01 No.b) LED/Neon indicator bulb in RYB Colour - 1 Set.c) 4 No copper Bus bar 800 amps with chamber.d) Digital Multi function meter for showing Amps (upto 500 Amps) and Voltage (upto 500 voltage) with suitable CT and PT.Outgoing:-(a) MCCB 320 Amps 4 Pole, 415 V, 35KA -01 No.(b) suitable cable gland for incoming and outgoing cable. |
| 6 | All as per herein above item but forIncoming:-(a) ACB 4 Pole, 415 V, with Thermal Magnetic Release (Manual Fixed type) of capacity 630 Amps - 1 Nos(b) LED/Neon indicator bulb in RYB Colour - 1 Set.(c) 4 No Aluminium Bus bar 1300Amps with chamber.(d) Digital Multi function meter for showing Amps (upto 500 Amps) and Voltage (upto 500 voltage) with suitable CT and PT.(e) Electronic energy meters temper proof 3 phase, 415 volt, LCD display with polycarbonate coverenergy meters conforming to IS 13779/ as per latest policy, IP-54, with parameters to show data, time, current reading, load, PF, voltage and KWH.Outgoing:-(a) MCCB 4 Pole, 415 V, adjustable type, 400 A with breaking capacity 36 KA - 01 Nos(b) MCCB 4 Pole, 415 V, adjustable type, 250 A with breaking capacity 36 KA - 02 Nos(c) MCCB 4 Pole, 415 V, adjustable type, 63 A with breaking capacity 25 KA with electric meter 3 phase - 06 Nos.(d) Suitable cable gland for incoming and outgoing cable |
| 7 | All as per herein above item but forIncoming:-(a) MCCB 100 Amps 4 Pole, 415 V,25KA- 01 Nos (I/C)(b) LED/Neon indicator bulb in RYB Colour - 1 Set.(c) 4 No Aluminium Bus bar 200 amps with chamber.(d) Digital Multi function meter for showing Amps (upto 500 Amps) and Voltage (upto 500 voltage) with suitable CT and PT.Outgoing:-(e) MCB 40 Amps TPN, 415 V,10KA- 02 Nos (O/G).(f) MCB 32 Amps SPN, 415 V,10KA- 02 Nos (O/G)(g) suitable cable gland for incoming and outgoing cable |
| 8 | All as per herein above item but forIncoming:-(a) MCCB 400 Amps 4 Pole, 415 V,36KA- 01 Nos (I/C).(b) LED/Neon indicator bulb in RYB Colour - 1 Set.(c) 4 No Aluminium Bus bar 800 amps with chamber.(d) Digital Multi function meter for showing Amps (upto 500 Amps) and Voltage (upto 500 voltage) with suitable CT and PT.Outgoing:-(e) MCCB320 Amps 4P, 415 V,36KA- 01 Nos (O/G)(f) MCB 40 Amps TPN, 415 V,16KA- 02 Nos (O/G).(g) suitable cable gland for incoming and outgoing cable |
| 9 | All as per herein above item but forIncoming:-(a) ACB 4 Pole, 415 V, with Thermal Magnetic Release (Manual Fixed type) of capacity 630 Amps - 1 Nos.(b) LED/Neon indicator bulb in RYB Colour - 1 Set.(c) 4 No Aluminium Bus bar 1300amps with chamberd) Digital Multi function meter for showing Amps (upto 500 Amps) and Voltage (upto 500 voltage) with suitable CT and PT.e) Electronic energy meters temper proof3 phase, 415 volt, LCD display with polycarbonate coverenergy meters conforming to IS 13779/ as per latest policy, IP-54, with parameters to show data, time, current reading, load, PF, voltage and KWH.Outgoing:-(a) MCCB TPN, 415 V, adjustable type, 320 A with breaking capacity 36 KA - 02 Nos.(b) MCCB TPN, 415 V, adjustable type, 160 A with breaking capacity 36 KA - 02 Nos.(c) MCCB TPN, 415 V, adjustable type, 100 A with breaking capacity 36 KA - 10 Nos.(d) MCCB 4 Pole, 415 V, adjustable type, 63 A with breaking capacity 25 KA - 02 Nos.(e) Suitable cable gland for incoming and outgoing cable |
| 10 | All as per herein above item but forIncoming:-(a) MCCB 400 Amps 4 Pole, 415 V, 36KA- 01 Nos (I/C).(b) LED/Neon indicator bulb in RYB Colour - 1 Set.(c) 4 No Aluminium Bus bar 800 amps with chamber.(d) Digital Multi function meter for showing Amps (upto 500 Amps) and Voltage (upto 500 voltage) with suitable CT and PT.(e) Electronic energy meters temper proof3 phase, 415 volt, LCD display with polycarbonate coverenergy meters conforming to IS 13779/ as per latest policy, IP-54, with parameters to show data, time, current reading, load, PF, voltage and KWH.Outgoing:-(a) MCCB250 Amps TPN, 415 V,36KA- 01 Nos (O/G).(b) MCCB 160 Amps TPN, 415 V,25KA- 02 Nos (O/G).(c) MCCB 200 Amps TPN, 415 V,25KA- 02 Nos (O/G).(d) suitable cable gland for incoming and outgoing cable |
| 11 | All as per herein above item but forIncoming:-(a) MCCB 250 Amps 4 Pole, 415 V, 36KA- 01 Nos (I/C).(b) LED/Neon indicator bulb in RYB Colour - 1 Set.(c) 4 No Aluminium Bus bar 500 amps with chamber.(d) Digital Multi function meter for showing Amps (upto 500 Amps) and Voltage (upto 500 voltage) with suitable CT and PT.Outgoing:-(a) MCCB 200 Amps TPN, 415 V, 36KA- (O/G).(b) MCCB 63 Amps TPN, 415 V, 25KA- 02 Nos (O/G)(c) suitable cable gland for incoming and outgoing cable |
| 12 | All as per herein above item but forIncoming:-(a) MCCB 200 Amps 4 Pole, 415 V, 36KA- 01 Nos (Incomer)(b) LED/Neon indicator bulb in RYB Colour - 1 Set.(c) 4 No Aluminium Bus bar 400 amps with chamber.(d) Digital Multi function meter for showing Amps (upto 500 Amps) and Voltage (upto 500 voltage) with suitable CT and PT.Outgoing:-(a) MCCB 100 Amps TPN, 415 V, 25KA- 03 Nos.(b) MCB 32 Amps FP, 415 V, 25KA- 02 Nos.(c) MCCB 63 Amps TPN, 415 V, 25KA- 02 Nos.(d) suitable cable gland for incoming and outgoing cable |
| 13 | All as per herein above item but forIncoming:-(a) MCCB 4 pole, 415 V, adjustable type, 320 A with breaking capacity 36 KA - 01 Nos.(b) LED/Neon indicator bulb in RYB Colour - 1 Set.(c) 4 No Aluminium Bus bar 700 amps with chamber.(d) Digital Multi function meter for showing Amps (upto 500 Amps) and Voltage (upto 500 voltage) with suitable CT and PT.(e) Electronic energy meters temper proof3 phase, 415 volt, LCD display with polycarbonate coverenergy meters conforming to IS 13779/ as per latest policy, IP-54, with parameters to show data, time, current reading, load, PF, voltage and KWH.Outgoing:-(a) MCCB TPN, 415 V, adjustable type, 160 A with breaking capacity 25 KA - 01 Nos.(b) MCCB TPN, 415 V, adjustable type, 125 A with breaking capacity 25 KA - 02 Nos.(c) suitable cable gland for incoming and outgoing cable. |
| 14 | All as per herein above item but forIncoming:-(a) MCCB 4 pole, 415 V, adjustable type, 100 A with breaking capacity 25 KA - 01 Nos.(b) LED/Neon indicator bulb in RYB Colour - 1 Set.(c) 4 No Aluminium Bus bar 200 amps with chamber.(d) Digital Multi function meter for showing Amps (upto 500Amps) and Voltage (upto 500 voltage) with suitable CT and PT.(e) Electronic energy meters temper proof3 phase, 415 volt, LCD display with polycarbonate coverenergy meters conforming to IS 13779/ as per latest policy, IP-54, with parameters to show data, time, current reading, load, PF, voltage and KWH.Outgoing:-(a) MCCB TPN, 415 V,adjustable type, 63 A with breaking capacity 25 KA - 02 Nos.(b) MCB, 415 V, adjustable type, 40 A with breaking capacity 25 KA - 03 Nos(c) suitable cable gland for incoming and outgoing cable |
| 15 | All as per herein above item but forIncoming:-(a) MCCB 4 pole, 415 V,adjustable type, 125 A with breaking capacity 25 KA - 01 Nos.(b) LED/Neon indicator bulb in RYB Colour - 1 Set.(c) 4 No Aluminium Bus bar 250 amps with chamber.(d) Digital Multi function meter for showing Amps (upto 500 Amps) and Voltage (upto 500 voltage) with suitable CT and PT.(e) Electronic energy meters temper proof3 phase, 415 volt, LCD display with polycarbonate coverenergy meters conforming to IS 13779/ as per latest policy, IP-54, with parameters to show data, time, current reading, load, PF, voltage and KWH.Outgoing:-(a) MCCB TPN, 415 V,adjustable type, 63 A with breaking capacity 25 KA - 01 Nos.(b) suitable cable gland for incoming and outgoing cable |
| 16 | All as per herein above item but forIncoming:-(a) MCCB 4 pole, 415 V,adjustable type, 160 A with breaking capacity 25 KA - 01 Nos.(b) LED/Neon indicator bulb in RYB Colour - 1 Set.(c) 4 No Aluminium Bus bar 350 amps with chamber(d) Digital Multi function meter for showing Amps (upto 500 Amps) and Voltage (upto 500 voltage) with suitable CT and PT.(e) Electronic energy meters temper proof3 phase, 415 volt, LCD display with polycarbonate coverenergy meters conforming to IS 13779/ as per latest policy, IP-54, with parameters to show data, time, current reading, load, PF, voltage and KWH.Outgoing:-(a) MCCB TPN, 415 V,adjustable type, 125 A with breaking capacity 25 KA - 01 Nos.(b) MCCB TPN, 415 V,adjustable type, 63 A with breaking capacity 25 KA - 01 Nos.(c) MCCB TPN, 415 V,adjustable type, 40 A with breaking capacity 25 KA - 02 Nos.(d) MCB DP 40 Amps -12Nos.(e) MCB DP 25 Amps- 4Nos.(f) suitable cable gland for incoming and outgoing cable |
| 17 | All as per herein above item but forIncoming:-(a) MCCB 4 pole, 415 V, adjustable type, 125 A with breaking capacity 25 KA - 01 Nos.(b) LED/Neon indicator bulb in RYB Colour - 1 Set.(c) 4 No Aluminium Bus bar 250 amps with chamber.(d) Digital Multi function meter for showing Amps (upto 500 Amps) and Voltage (upto 500 voltage) with suitable CT and PT.(e) Electronic energy meters temper proof3 phase, 415 volt, LCD display with polycarbonate coverenergy meters conforming to IS 13779/ as per latest policy, IP-54, with parameters to show data, time, current reading, load, PF, voltage and KWH.Outgoing:-a) MCCB TPN, 415 V, adjustable type, 63 A with breaking capacity 25 KA - 01 Nos.b) MCCB 4 pole, 415 V, adjustable type, 100 A with breaking capacity 25 KA - 01 Nos |
| 18 | All as per herein above item but forIncoming:-(a) ACB 4 Pole, 415 V, with Thermal Magnetic Release (Manual Fixed type) of capacity 800 Amps - 1 Nos.(b) LED/Neon indicator bulb in RYB Colour - 1 Set.(c) 4 No Aluminium Bus bar 1600amps with chamber.(d) Digital Multi function meter for showing Amps (upto 500Amps) and Voltage (upto 500 voltage) with suitable CT and PT.(e) Electronic energy meters temper proof3 phase , 415 volt ,LCD display with polycarbonate coverenergy meters conforming to IS 13779/ as per latest policy, IP-54, with parameters to show data, time, current reading, load, PF, voltage and KWH.Outgoing:-(a) ACB 4 Pole, 415 V, with Thermal Magnetic Release (Manual Fixed type) of capacity 630 Amps - 1 Nos.(b) MCCB 4 Pole, 415 V, adjustable type, 100 A with breaking capacity 25 KA - 01 Nos.(c) MCCB 4 Pole, 415 V, adjustable type, 125 A with breaking capacity 25 KA - 01 Nos(d) suitable cable gland for incoming and outgoing cable. |
| 19 | All as per herein above item but forIncoming:-(a) MCCB 4 pole, 415 V,adjustable type, 320 A with breaking capacity 36 KA - 01 Nos.(b) LED/Neon indicator bulb in RYB Colour - 1 Set.(c) 4 No Aluminium Bus bar 650amps with chamber.(d) Digital Multi function meter for showing Amps (upto 500Amps) and Voltage (upto 500 voltage) with suitable CT and PT.(e) Electronic energy meters temper proof3 phase, 415 volt, LCD display with polycarbonate coverenergy meters conforming to IS 13779/ as per latest policy, IP-54, with parameters to show data, time, current reading, load, PF, voltage and KWH.Outgoing:-(a) ACB 4 Pole, 415 V, with Thermal Magnetic Release (Manual Fixed type) of capacity 630 Amps - 1 Nos.(b) MCCB 4 Pole, 415 V,adjustable type, 100 A with breaking capacity 25 KA - 01 Nos.(c) MCCB 4 Pole, 415 V,adjustable type, 125 A with breaking capacity 25 KA - 01 Nos.(d) suitable cable gland for incoming and outgoing cable |
| 20 | All as per herein above item but forIncoming:-(a) ACB 4 Pole, 415 V, Manual Drawout type with microprocessor release of capacity 630 Amps - 01 Nos.(b) LED/Neon indicator bulb in RYB Colour - 1 Set.(c) 4 No aluminium Bus bar 1400 amps with chamber.(d) Digital Multi function meter for showing Amps (upto 500 Amps) and Voltage (upto 500 voltage) with suitable CT and PT.(e) Electronic energy meters temper proof3 phase, 415 volt, LCD display with polycarbonate coverenergy meters conforming to IS 13779/ as per latest policy, IP-54, with parameters to show data, time, current reading, load, PF, voltage and KWH.Outgoing:-(a) MCCB 4 pole, 415 V,adjustable type, 320 A with breaking capacity 36 KA - 01 Nos(b) MCCB TPN, 415 V, , 200 Amps- 06 Nos.(c) suitable cable gland for incoming and outgoing cable |
| 21 | All as per herein above item but forIncoming:-(a) MCCB 4P 415 V 50Hz 160 Amps 36KA- 01 Nos.(b) LED/Neon indicator bulb in RYB Colour - 1 Set.(c) 4 No aluminium Bus bar 350 amps with chamber.(d) Digital Multi function meter for showing Amps (upto 500 Amps) and Voltage (upto 500 voltage) with suitable CT and PT.(e) Electronic energy meters temper proof3 phase , 415 volt ,LCD display with polycarbonate coverenergy meters conforming to IS 13779/ as per latest policy, IP-54, with parameters to show data, time, current reading, load, PF, voltage and KWH.Outgoing:-(a) MCCB 4 Pole, 415 V, , 63 Amps 25 KA - 07 Nos.(b) suitable cable gland for incoming and outgoing cable |
| 22 | All as per herein above item but forIncoming:-(a) ACB 4 Pole, 415 V, Manual Drawout type with microprocessor release of capacity 630 Amps - 01 Nos.(b) LED/Neon indicator bulb in RYB Colour - 1 Set.(c) 4 No aluminium Bus bar 1300 amps with chamber.(d) Digital Multi function meter for showing Amps (upto 500 Amps) and Voltage (upto 500 voltage) with suitable CT and PT.(e) Electronic energy meters temper proof3 phase, 415 volt, LCD display with polycarbonate coverenergy meters conforming to IS 13779/ as per latest policy, IP-54, with parameters to show data, time, current reading, load, PF, voltage and KWH.Outgoing:-(a) MCCB TP, 415 V, 200 Amps- 07 Nos.(b) MCCB TP, 415 V, 250 Amps- 06 Nos.(c) suitable cable gland for incoming and outgoing cable. |
| 23 | All as per herein above item but forIncoming:-(a) MCCB 4 pole, 415 V,adjustable type, 320 A with breaking capacity 36 KA - 01 Nos(b) LED/Neon indicator bulb in RYB Colour - 1 Set.(c) 4 No aluminium Bus bar 650 amps with chamber.(d) Digital Multi function meter for showing Amps (upto 500 Amps) and Voltage (upto 500 voltage) with suitable CT and PT.(e) Electronic energy meters temper proof3 phase, 415 volt, LCD display with polycarbonate cover energy meters conforming to IS 13779/ as per latest policy, IP-54, with parameters to show data, time, current reading, load, PF, voltage and KWH.Outgoing:-(a) MCCB TPN, 415 V, 200 Amps 25KA -01 No(b) MCCB TPN, 415 V, 160 Amps25KA- 02Nos(c) MCCB TPN, 415 V, 100 Amps25KA- 02Nos(d) MCCB TPN, 415 V, 63 Amps25KA - 02Nos(e) suitable cable gland for incoming and outgoing cable |
| 24 | All as per herein above item but forIncoming:-(a) MCCB 4 pole, 415 V, adjustable type, 320 A with breaking capacity 36 KA - 01 Nos.(b) LED/Neon indicator bulb in RYB Colour - 1 Set.(c) 4 No aluminium Bus bar 500 amps with chamber.(d) Digital Multi function meter for showing Amps (upto 500 Amps) and Voltage (upto 500 voltage) with suitable CT and PT.(e) Electronic energy meters temper proof 3 phase, 415 volt, LCD display with polycarbonate coverenergy meters conforming to IS 13779/ as per latest policy, IP-54, with parameters to show data, time, current reading, load, PF, voltage and KWH.Outgoing:-(a) MCCB TPN, 415 V, 200 Amps- 01 No(b) MCCB TPN, 415 V, 250 Amps- 01 Nos.(c) MCCB TPN, 415 V, 100 Amps25KA- 02 Nos.(d) MCCB TPN, 415 V, 63 Amps25KA - 02 Nos.(e) suitable cable gland for incoming and outgoing cable |
| 25 | All as per herein above item but forIncoming:-(a) MCCB 4 pole, 415 V,adjustable type, 250 A with breaking capacity 36 KA - 01 Nos.(b) LED/Neon indicator bulb in RYB Colour - 1 Set.(c) 4 No aluminium Bus bar 400 amps with chamber.(d) Digital Multi function meter for showing Amps (upto 500 Amps) and Voltage (upto 500 voltage) with suitable CT and PT.(e) Electronic energy meters temper proof3 phase , 415 volt ,LCD display with polycarbonate coverenergy meters conforming to IS 13779/ as per latest policy, IP-54, with parameters to show data, time, current reading, load, PF, voltage and KWH.Outgoing:-(a) MCCB TPN, 415 V, 100 Amps25KA -04 No.(b) MCCB TPN, 415 V, 63 Amps25KA - 01 No.(c) suitable cable gland for incoming and outgoing cable |
| 26 | Material and Labour for Earthing complete with with600 mm x 60 mm x 6.15 mm thick, galvanized steel earth plate electrode buried vertically in ground (not less than 2.25 meters deep below normal ground level),with top edge of earth plate not less than 1.5 meter below ground level connected to and including G.I strip of size 32mm x 6 mm by means of bolts/nuts/check nuts and washers of galvanized steel, GI Strip encased in and including 40 mm bore GI light grade protection pipe starting from top edge of the earth platelaid in ground/floors fixed on wall. GI strip to be connected with HT/LT electrical equipments with provision of charcoal dust & common salt all around the earth plate 15 cm layersincludingnecessary excavation and earth work in any type of soil/strata, provision of concrete earth pit using PCC 1:3:6 type C-2 including RCC cover using PCC 1:2:4 type B1 20 mm dia GI light grade with wire mesh and tunel for watering arrangement, complete all as shown on electrical plate No. 3 of SSR Part I includig testing after completion of earth complete all as specified and directed. |