| 1 | S&F IN REPAIR new generation energy saving and environmental friendly long life LED street light made up of innovative die cast aluminium housing high power LED as lighting source with IP - 65 power consumption 45watt complete input voltage of 150-240 Volt (nominal rated voltage 240 Volt) including pvc coated twisted copper cable 1.5 sqmm x 3 core through copper connectors from junction box to security lights, complete all as specified and directed. Make Havells model no- ENDURASUNDOWNSL 45WLED765PASYBOTG or Equivalent make as specified here-in-after. |
| 2 | Excavation in trenches not exceeding 1.5m wide and not exceeding 10 Sq.m on plan area and not exceeding 1.5m deep in any type of soil, for laying of cable/pipes etc., including taking out old bricks and separating serviceable & unserviceable bricks, cleaning & stacking serviceable bricks for re-use, complete all as specified. |
| 3 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick of excavated soil, as in any type of soil, complete all as specified. Note: A deduction of 10% shall be made from total computed volume of filling to cater in bulk irrespective of machinery used for ramming. |
| 4 | Removal of excavated material [Soil] to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point, complete all as specified. |
| 5 | M&L for PCC 1:3:6 type C-2 (using 40mm graded stone aggregates) as in foundation filling and mass concrete including form work for poles all as specified and directed by Engr-in-Charge. |
| 6 | M&L for PCC 1:2:4 type B-1 (using 20mm graded stone aggregates) as in coping etc including form work for poles all as specified and directed by Engr-in-Charge. |
| 7 | Supply, laying, testing and commissioning of LT XLPE insulated, screened with extruded PVC inner sheathed, PVC bedded, galvanised steel strip armoured electric power cable [heavy duty] of size 4.0core x 16.0Sqmm, with stranded aluminium conductor, 1100 volts grade, suitable for earthed system with and including cable glands, ferrules and connected accessories, laid in trenches or ducts or through the pipe etc., including taking down old u/s cable, complete all as specified. Note: Necessary excavation & earth work, brick protection & sand cushioning shall be measured and paid separately under respective items. |
| 8 | All as per Serial Item No. 07 here-in-before but for cable of size 4.0core x 10.0Sqmm. |
| 9 | S&F IN REPAIR Corrugated HDPE pipe of 40mm bore dia for cable protection, confirming IS-14930 1 & 2, laid in trenches or fixed to the pole with necessary accessories, complete all as specified. |
| 10 | Taking down existing complete PA system with wire from existing Poles and refixing the same to new Poles with and including new fixing GI clamps and all other necessary accessories required at site for fixing, complete all as specified. |
| 11 | M&L for IN REPAIR Earthing complete with galvanised steel earth plate electrode 60cm X 60cm X 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised earth lead 4mm GI wire by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No.3 of SSR Part-I, including excavation / earth work in any strata, adequate quantity of charcoal and common salt, PCC chamber with RCC 1:2:4 type B1 40mm thick cover slab with 8mm dia TMT bars @150mm c/c in bothways, suitable handle and angle iron frame of suitable size to fix the cover, with 20mm bore GI pipe light grade for watering with funnel, wire mesh and 15mm bore GI pipe medium grade for GI wire protection and 4mm GI earth wire, including testing after completion, complete all as specified and directed. Note : Earth wire will be measured after 7.5mtr from the earth strip or earth testing terminal block whichever is lesser under relevant item. |
| 12 | S&F IN REPAIR LT Panel as per IEC 61439, Outdoor type, floor mounted free standing dust and vermin proof panel / DB with IP-55 protection, CPRI approved OEM, frame fabricated out of 40mmx40mm x 4mm MS angle iron, made with 3.15mm thick CRCA sheet for entire outer panel and 1.6mm thick CRCA sheet 40mmx4mm MS flat Iron for inner compartments with separate cubicle chamber with cable alley with minimum 300mm width for installation/connecting switchgears with the main bus bar using aluminium bus link or copper conductor flexible wires suitable for switch rating and connecting outgoing terminals of the switchgear with terminal blocks of appropriate current rating using flexible copper wires duly terminated by cable lugs and thimbles, MS surfaces epoxy based powder coated, shade as approved over 2 coats of red oxide primer, surfaces pre-treated in seven tank process for de-greasing, de-rusting & Phosphated, panel having front and rear opening and provision for installation of separate cable alleys, all MCCBs must be have thermal magnetic relrase, busbar chamber and switchgear compartments, provision in cable alleys for bottom cable entry for incoming & outgoing cables,fixing danger notice plate, with and including erection, testing and commissioning, complete all as specified and directed including the following fixtures and fitments:- (a) Aluminiumbus bar four strips1000 Amp, 415 volts, fixed on epoxy insulated with panel fixed horizontally, duly insulated with heat shrinkable sleeves in colour code - 01 Set. |
| 13 | Incoming:-(b) ACB 04 Pole, 800 Amp with ultimate breaking capacity Icu- 50 KA at 415 volts, adjustable type with thermal & magnetic settings (Ics=Icu=100%)- 01No Outgoing:-(c) MCCB 04 Pole, 400 Amp with ultimate breaking capacity Icu- 50 KA at 415 volts, adjustable type with thermal and magnetic settings (Ics=Icu=100%) - 02Nos (d) MCCB 04 Pole, 250 Amp with ultimate breaking capacity Icu- 25KA at 415 volts, adjustable type with thermal and magnetic settings (Ics=Icu=100%)-02Nos (e) MCCB 04 Pole, 200Amp with ultimate breaking capacity Icu- 25KA at 415 volts, adjustable type with thermal and magnetic settings (Ics=Icu=100%)- 01Nos (f) MCCB 04 Pole, 160Amp with ultimate breaking capacity Icu- 25KA at 415 volts, adjustable type with thermal and magnetic settings (Ics=Icu=100%)-03Nos and Spare way for MCCB , 4Pole, 63Amp-02Nos(g) Analoge type volt meter 0-500V - 1Set., Analoge type Ammeter 0-400Amp - 1Set with selector switch & MCB, Indication lamps R,Y,B LED type with 3 Nos –1 set, Internal wiring with suitable size of PVC insulated stranded copper conductor cable duly crimped with copper lugs & ferruled and aluminum strips for MCCB\"s. Note :- Panel drawings & make of MCCB/SDFU will be submitted by contractor for approval of GE before ordering the panel. |
| 14 | S&F IN REPAIR Electric astronomical timer control panel, cubical type, for out door use, dust & vermin proof wall mounted type, made out of CRCA steel sheet with timer switches type 63Amp, 3 pole, 230 Volt, Analog time switch with complete accessories, fixedon pole for switch on/off and control the street light timings including testing, complete all as specified and as directed. |
| 15 | S&F IN REPAIR Electric astronomical timer control panel, cubical type, for out door use, dust & vermin proof wall mounted type, made out of CRCA steel sheet with timer switches type 40Amp, 3 pole, 230 Volt, Analog time switch with complete accessories, fixedon pole for switch on/off and control the street light timings including testing, complete all as specified and as directed. |
| 16 | S&F GFRP street light pole of 6meter height, with top outer dia 100mm, bottom outer dia 240mm, made with translucent conical pole Glass Fibre Reinforced Polymer matrix fibre (GFRP) combination of Fibre Glass & Resign winding by CNC method,designed & made to sustain a minimum wind speed of 180Km/Hr, GFRP anchor plate & base plate of size suitable size, with LOGO and including fixing fittings fixed & civil foundation as per manufacturers design, including dismantling existing u/s street light pole of any type after disconnecting electrical connections and making good the disturbed surface, complete all as specified and directed. Note: The work shall be carried out directly by the authorised Rep of OEM of Poles and a certificate to this effect and foundation drawing shall be submitted to GE before starting the work. |
| 17 | S&F Single arm of 01m length suitable for 6metre GFRP street light pole, complete all as specified and as directed. |
| 18 | S&F IN REPAIR AC LED of colour Amber, Red, Green, Blue & White COLOR STRIPflexi strip with optimum brightness and uniformity of light for perfect cover lightening and having IP65 protection, including all connector and plug required for proper functioning, complete all as specified and as directed. |
| 19 | S&F Octagonal hot dip galvanized street light pole of 6.0meter height, with and including single arm CANOPY Type (1m length canopy) with top dia minimum 70mm, bottom dia minimum 135mm, made with 3mm thick GI sheet, anchor plate & base plate of size 225mm X 225mm X 16mm fixed with 04 Nos of M20 size foundation bolt of minimum length 750mm, internal & external fabrication of the pole shall be in accordance with IS-2629/BSEN ISO 1461, with and including all necessary civil works i.e earthwork, RCC/PCC foundation as per manufacturers design, including dismantling existing u/s street light pole of any type after disconnecting electrical connections and making good the disturbed surface, complete all as specified and directed. Note: The work shall be carried out directly by the authorised Rep of OEM of Poles and a certificate to this effect and foundation drawing shall be submitted to GE before starting the work. |
| 20 | M&L for Dry & clean river sand cushioning in two layers, first layers of 80mm thick before laying of cable and second layer of 150mm thick after laying of cable, levelled and punned down to a depth of 100mm above the top of the upper-most cable, for cable protection in trenches, complete all as specified and as directed. Note: The punned down thickness shall be measured for payment. |
| 21 | Supply and laying Precast un-reinforced concrete cable cover, Class LV, Type I, flat, size 250mm x 150mm x 40mm, complete all as specified and as directed. |
| 22 | M&L for Earth continuity conductor or main earthing lead of 4mm dia GI or steel wire, fixed to wall on batten on recess or chases or buried in ground or dawn in conduit / pipe or fixed to poles or any other indicated situation for loop earthing etc. as required, completion all as specified and as directed. |