| 1 | Excavation in trenches not exc 1.5 metre wide and not exc 1.5 metre depth for laying of UG cable / pole etc getting out including forming bottom surfaceto required level and gradient in soft/loose soil complete all as specified and as directed. |
| 2 | Returning and filling in excavated soil including spreading leveling, watering, well ramming in layers not exc 25 Cm thick complete. |
| 3 | Removing of excavated materials not exceeding 50 metre and depositing where directed by Engrin Charge at a level not exceeding 1.5 metre above the starting point. |
| 4 | M & L forPCC (1:2:4) type B-1 (using 20 mm aggregate) as in coping of poleetc including form work & finishing the surfaces even & smooth with out using extra cement complete all as specified and as directed.(Note :- Cost of demolition of coping of pole shall deem to be included in above quoted rate. |
| 5 | M & L for laying of DWC pipe inner dia 32 mm and outer dia 40mm comfirming to IS 14930 : 2 and IS 16205 for protection of LT UG cable of size 10 sqmm to 25 sqmm .and directed bby engr-in-charge |
| 6 | M & L for laying of DWC pipe inner dia 38 mm and outer dia 50 mm comfirming to IS 14930 : 2 and IS 16205 for protection of LT UG cable of size 50 sqmm to 95 sqmm and directed bby engr-in-charge |
| 7 | M & L for laying of DWC pipe inner dia 61 mm and outer dia 75mm comfirming to IS 14930 : 2 and IS 16205 for protection of LT UG cable.and directed by engr-in-charge |
| 8 | M & L for laying of DWC pipe inner dia 93 mm and outer dia 110 mm comfirming to IS 14930 : 2 and IS 16205 for protection of LT UG cable.and directed bby engr-in-charge |
| 9 | Supply & Laying, testing & commissioning of LT UG cable XLPE sheathed PVC insulated,screened PVC bedded, galvanised steel strip of wire armoured electric power cable heavy duty with stranded aluminium conductor 1100 volts grade, laid in trenches, in GI pipe , including brass cable glands, clamps etc of size4 core x 10sq mm complete all as specified.Make :- Polycab/Havells/KEINote : Earthwork, sand cushioning, bricks, GI pipe, etc will be measured and paid under appropriate items |
| 10 | Supply & Laying, testing & commissioning of LT UG cable XLPE sheathed PVC insulated,screened PVC bedded, galvanised steel strip of wire armoured electric power cable heavy duty with stranded aluminium conductor 1100 volts grade, laid in trenches, in GI pipe , including brass cable glands, clamps etc of size 4 core x 25sq mm complete all as specified.Note : Earthwork, sand cushioning, bricks, GI pipe, etc will be measured and paid under appropriate items |
| 11 | Supply & Laying, testing & commissioning of LT UG cable XLPE sheathed PVC insulated,screened PVC bedded, galvanised steel strip of wire armoured electric power cable heavy duty with stranded aluminium conductor 1100 volts grade, laid in trenches, in GI pipe , including brass cable glands, clamps etc of size3.5 core x 50sq mm complete all as specified Note : Earthwork, sand cushioning, bricks, GI pipe, etc will be measured and paid under appropriate items |
| 12 | Supply & Laying, testing & commissioning of LT UG cable XLPE sheathed PVC insulated,screened PVC bedded, galvanised steel strip of wire armoured electric power cable heavy duty with stranded aluminium conductor 1100 volts grade, laid in trenches, in GI pipe , including brass cable glands, clamps etc of size3.5 core x 95sq mm complete all as specified.Make :- Polycab/Havells/KEINote : Earthwork, sand cushioning, bricks, GI pipe, etc will be measured and paid under appropriate items |
| 13 | Supply & Laying, testing & commissioning of LT UG cable XLPE sheathed PVC insulated,screened PVC bedded, galvanised steel strip of wire armoured electric power cable heavy duty with stranded aluminium conductor 1100 volts grade, laid in trenches, in GI pipe , including brass cable glands, clamps etc of size3.5 core x 185sq mm complete all as specified.Make :- Polycab/Havells/KEINote : Earthwork, sand cushioning, bricks, GI pipe, etc will be measured and paid under appropriate items |
| 14 | Supply & Laying, testing & commissioning of LT UG cable XLPE sheathed PVC insulated,screened PVC bedded, galvanised steel strip of wire armoured electric power cable heavy duty with stranded aluminium conductor 1100 volts grade, laid in trenches, in GI pipe , including brass cable glands, clamps etc of size3.5 core x 300sq mm complete all as specified.Make :- Polycab/Havells/KEINote : Earthwork, sand cushioning, bricks, GI pipe, etc will be measured and paid under appropriate items |
| 15 | Cable indoor / outdoor end terminals/Straight through jointing kitfor LV/LT 1100 V cable heat shrinkable type joint kit complete with jointing material and accessories, thimbles etc suitable for 25 Sqmm to 50 Sqmm 3.5 coreXLPE armoured aluminium conductor cable including testing after jointing, fixing in replacementcomplete all as specified as directed by Engineer-in-Charge. |
| 16 | Cable indoor / outdoor end terminals/Straight through jointing kitfor LV/LT 1100 V cable heat shrinkable type joint kit complete with jointing material and accessories, thimbles etc suitable for 70 Sqmm to 150 Sqmm 3.5 coreXLPE armoured aluminium conductor cable including testing after jointing, fixing in replacementcomplete all as specified as directed by Engineer-in-Charge. |
| 17 | M & L for earthing complete with GI Earth Plate Electrode 600mm x 600mm x6mm, thick burieddirectlyin ground vertically to a depth not less than 2.25 Metre below Ground Level with Top Edge of Earth Plate at depth not less than 1.50 Metre below Normal Ground Level, connectedto Galvanised ironearthstrip 32X6 mm drawn through and including Galvanised Ironprotection Pipe 40 mm bore (dia) Light grade uptoheightl of thetransformer foundation where foundation situated by means of Bolts, Nuts, Check Nuts and Washers etc Earth plate surrounded by a packed thickness of charcoal or coke dust mixed with common salt in alternate layers of not exc 150mm thick PCC Pit in cement concrete 1:3:6 (20 mm graded aggregrate ), Precast RCC1:2:4 (20mm graded aggregrate )cover slab 350 x350 x 50mm thick reinforced with and including 8mm dia TMT Bars @ 10 cmCentre to Centreboth ways GIWire Mesh , Funnel, with GI Watering Pipe 20mm bore dia Medium grade necessary excavation in soft loose soil returning filling in and removal of surplus soil upto a distance of 50 METRE and all asshown in Electrical Plate No. 3 of MES schedule Part- I and testing on completion complete all as specified and as directed. |
| 18 | M & L for earthing complete with GI Earth Plate Electrode 600mm x 600mm x6mm, thick burieddirectlyin ground vertically to a depth not less than 2.25 Metre below Ground Level with Top Edge of Earth Plate at depth not less than 1.50 Metre below Normal Ground Level, connectedto GI wire as earthlead 4 mm dia drawn through and including Galvanised Ironprotection Pipe 15 mm bore (dia) Light grade upto 1.0 Metre above the ground levelof the HT pole foundation where PCC pole issituated by means of Bolts, Nuts, Check Nuts and Washers etc Earth plate surrounded by a packed thickness of charcoal or coke dust mixed with common salt in alternate layers of not exc 150mm thick PCC Pit in cement concrete 1:3:6 (20 mm graded aggregrate ), Precast RCC1:2:4 (20mm graded aggregrate )cover slab 350 x350 x 50mm thick reinforced with and including 8mm dia TMT Bars @ 10 cmCentre to Centreboth ways GIWire Mesh , Funnel, with GI Watering Pipe 20mm bore dia Medium grade necessary excavation in soft loose soil returning filling in and removal of surplus soil upto a distance of 50 METRE and all asshown in Electrical Plate No. 3 of MES schedule Part- I and testing on completion including taking down unserviceable earting and connected Items, complete all as specified and as directed. |
| 19 | Boring holes horizontally under Road without damaging the surface of Road (minimum 1.0 METRE below the Road Surface with the help of GI Tubing not exc. 80mm bore (dia) for passing of UG Cable, complete all as specified and as directed.Note : GI Pipe laid will be measured and paid separately under appropriate Item. |
| 20 | Supply, installing, commissioning and testing factory made and tested (CPRI type test certified) LT Feeder Pillar Box cubical type (KIOSK) of size as per IS specifications, 415 Volt, 3 Phase & neutral, 4 wire, 50 Hz, AC supply system, protection class IP-53, dust & vermin proof for outdoor use, made out of CRCA sheet 3.15 mm thick, powder coated inside & outside of flint grey shade (RAL-7032), machine pressed, both side opening in two halves with provision of rubber beading and locking system, including copperbus bar of 200Amp capacity, 4 strip in colour code mounted on porcelain insulator, bus bar chamber shall be provided with inspection covers for each MCCB/cubical switch shall have the independent opening, panel shall be mounted on angle iron frame and legs made from angle of size 50x50x5 mm including internal wiring with PVC insulated stranded copper conductor FRLSH cables of appropriate size but not less than 6 sqmm with proper ferrule & cable glands, including danger notice sticker, comprising & including the following accessories complete all as specified and as directed.( P-11 to P-16 and P-1 to P-06) |
| 21 | Description of serial item No. 18.(a)MCCB 125 Amp 25 kA, 4 Pole, Icu=100% Ics with built in protection functions for overload, short circuit current adjustable tybe complete with spreader link and extendable ON/OFF rotary handle - 01 No. (Incomer). Make:ABB/Siemens/ Schneider/Legrand.(b) MCCB 63 Amp 25 kA, 4 Pole, Icu=100% Ics with built in protection functions for overload, short circuit current complete with spreader link and extendable ON/OFF rotary handle - 07 Nos (Outgoing). Make:ABB/Siemens/ Schneider/Legrand.(c) MCB 32 Amp 10 kA, 2 Pole, Icu=100% Ics- 02 Nos (Outgoing). Make: ABB/Siemens/ Schneider/Legrand.(d) Indicator Set RYB, “LED” type (set of three) -01 Set(e) Digital Amp meter (0-300) Amp with built in selector switch including necessary CTs(set of three) - 1 Set(f) Digital Volt meterwith built in selector switch (0-500) - 01 No. |
| 22 | Supply, installing, commissioning and testing factory made and tested (CPRI type test certified) LT Feeder Pillar Box cubical type (KIOSK) of size as per IS specifications, 415 Volt, 3 Phase & neutral, 4 wire, 50 Hz, AC supply system, protection class IP-53, dust & vermin proof for outdoor use, made out of CRCA sheet 3.15 mm thick, powder coated inside & outside of flint grey shade (RAL-7032), machine pressed, both side opening in two halves with provision of rubber beading and locking system, including copperbus bar of 300 Amp capacity, 4 strip in colour code mounted on porcelain insulator, bus bar chamber shall be provided with inspection covers for each MCCB/cubical switch shall have the independent opening, panel shall be mounted on angle iron frame and legs made from angle of size 50x50x5 mm including internal wiring with PVC insulated stranded copper conductor FRLSH cables of appropriate size but not less than 6 sqmm with proper ferrule & cable glands, including danger notice sticker, comprising & including the following accessories complete all as specified and as directed.( P--19,20,24,23), (P-27,25,26,28), (P64 TO 68) and (P-69 to P-71) , (P-55,60,54,69, 75,74,83,84) |
| 23 | Description of serial item No. 21.(a)MCCB 160 Amp 36 kA, 4 Pole, Icu=100% Ics with built in protection functions for overload, short circuit current adjustable tybe complete with spreader link and extendable ON/OFF rotary handle - 01 No. (Incomer). Make:ABB/Siemens/ Schneider/Legrand.(b) MCCB 63 Amp 25 kA, 4 Pole, Icu=100% Ics with built in protection functions for overload, short circuit current complete with spreader link and extendable ON/OFF rotary handle - 09 Nos (Outgoing). Make:ABB/Siemens/ Schneider/Legrand.(c) MCB 32 Amp 10 kA, 2 Pole, Icu=100% Ics- 02 Nos (Outgoing). Make: ABB/Siemens/ Schneider/Legrand.(d) Indicator Set RYB, “LED” type (set of three) -01 Set(e) Digital Amp meter (0-300) Amp with built in selector switch including necessary CTs(set of three) - 1 Set(f) Digital Volt meterwith built in selector switch (0-500) - 01 No. |
| 24 | Supply, installing, commissioning and testing factory made and tested (CPRI type test certified) LT Feeder Pillar Box cubical type (KIOSK) of size as per IS specifications, 415 Volt, 3 Phase & neutral, 4 wire, 50 Hz, AC supply system, protection class IP-53, dust & vermin proof for outdoor use, made out of CRCA sheet 3.15 mm thick, powder coated inside & outside of flint grey shade (RAL-7032), machine pressed, both side opening in two halves with provision of rubber beading and locking system, including copperbus bar of 600 Amp capacity, 4 strip in colour code mounted on porcelain insulator, bus bar chamber shall be provided with inspection covers for each MCCB/cubical switch shall have the independent opening, panel shall be mounted on angle iron frame and legs made from angle of size 50x50x5 mm including internal wiring with PVC insulated stranded copper conductor FRLSH cables of appropriate size but not less than 6 sqmm with proper ferrule & cable glands, including danger notice sticker, comprising & including the following accessories complete all as specified and as directed. Main Panel No.01 (P-7 to 10) |
| 25 | Description of serial item No. 22.(a)MCCB 400 Amp 25 kA, 4 Pole, Icu=100% Ics with built in protection functions for overload, short circuit current adjustable tybe complete with spreader link and extendable ON/OFF rotary handle - 01 No. (Incomer). Make:ABB/Siemens/ Schneider/Legrand.(b) MCCB 160 Amp 25 kA, 4 Pole, Icu=100% Ics with built in protection functions for overload, short circuit current complete with spreader link and extendable ON/OFF rotary handle - 01 Nos (Outgoing). Make:ABB/Siemens/ Schneider/Legrand.(c) MCCB 63 Amp 25 kA, 4 Pole, Icu=100% Ics with built in protection functions for overload, short circuit current complete with spreader link and extendable ON/OFF rotary handle - 09 Nos (Outgoing). Make:ABB/Siemens/ Schneider/Legrand.(d) MCB 32 Amp 10 kA, 2 Pole, Icu=100% Ics- 02 Nos (Outgoing). Make: ABB/Siemens/ Schneider/Legrand.(e) Indicator Set RYB, “LED” type (set of three) -01 Set(f) Digital Amp meter (0-300) Amp with built in selector switch including necessary CTs(set of three) - 1 Set(g) Digital Volt meterwith built in selector switch (0-500) - 01 No. |
| 26 | Supply, installing, commissioning and testing factory made and tested (CPRI type test certified) LT Feeder Pillar Box cubical type (KIOSK) of size as per IS specifications, 415 Volt, 3 Phase & neutral, 4 wire, 50 Hz, AC supply system, protection class IP-53, dust & vermin proof for outdoor use, made out of CRCA sheet 3.15 mm thick, powder coated inside & outside of flint grey shade (RAL-7032), machine pressed, both side opening in two halves with provision of rubber beading and locking system, including copperbus bar of 600 Amp capacity, 4 strip in colour code mounted on porcelain insulator, bus bar chamber shall be provided with inspection covers for each MCCB/cubical switch shall have the independent opening, panel shall be mounted on angle iron frame and legs made from angle of size 50x50x5 mm including internal wiring with PVC insulated stranded copper conductor FRLSH cables of appropriate size but not less than 6 sqmm with proper ferrule & cable glands, including danger notice sticker, comprising & including the following accessories complete all as specified and as directed. Main Panel No.02 (P-17,18,22,23) and Main Panel No. 03 (P-72, 73,66) |
| 27 | Description of serial item No. 23.(a)MCCB 320 Amp 25 kA, 4 Pole, Icu=100% Ics with built in protection functions for overload, short circuit current adjustable tybe complete with spreader link and extendable ON/OFF rotary handle - 01 No. (Incomer). Make:ABB/Siemens/ Schneider/Legrand.(b) MCCB 160 Amp 25 kA, 4 Pole, Icu=100% Ics with built in protection functions for overload, short circuit current complete with spreader link and extendable ON/OFF rotary handle - 01 Nos (Outgoing). Make:ABB/Siemens/ Schneider/Legrand.(c) MCCB 63 Amp 25 kA, 4 Pole, Icu=100% Ics with built in protection functions for overload, short circuit current complete with spreader link and extendable ON/OFF rotary handle - 09 Nos (Outgoing). Make:ABB/Siemens/ Schneider/Legrand.(d) MCB 32 Amp 10 kA, 2 Pole, Icu=100% Ics- 02 Nos (Outgoing). Make: ABB/Siemens/ Schneider/Legrand.(e) Indicator Set RYB, “LED” type (set of three) -01 Set(f) Digital Amp meter (0-300) Amp with built in selector switch including necessary CTs(set of three) - 1 Set(g) Digital Volt meterwith built in selector switch (0-500) - 01 No. |
| 28 | S & F Junction Box fof size(H X W X D) 300x200x105 mm made out of Polycarbonate material totally enclosed, dust and vermin proof, rain protected slanted roof top, door pasted with rubber gasket, water tight IP 66 with integrated membranes/metric knockouts for cable entry with cable glands,protection and suitable size of \"connectwell\" stud teriminal (provision for socket bolting)- 04 Nos suitable for 415 volts, 50 Hz, 3 phase 4 wire internal wiring system including MCB SP 06 amps- 01 No and mounted on tubular/PCC pole with suitableclamps, nuts, bolts including removal of exiting unsv all as specified and directed.Note :- CA No. shall be embossed on each box by digital printing mechanism. |
| 29 | Supply & fixing FRLS PVCinsulated Copper conductor, two single core of size 1.5sqmm complete for terminal box to street/ flood light fitting. |
| 30 | Dismantling earth wire |
| 31 | Dismantling of stay asembly |
| 32 | Dismantling cross-arms of M.S. channel or angle sections etc. |
| 33 | Dismantling insulators any type, any size |
| 34 | Dismantling ACSR conductor of any size and shape |