| 1 | SCHEDULE \"A\" |
| 2 | Supply , laying and testing cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured , electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 10 sqmm 4 Core including taking down complete all as specified anddirected. |
| 3 | Supply , laying and testing cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured , electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16 sqmm 4 Core including takingdown complete all as specified anddirected. |
| 4 | M & L forexcavating in trenches, not exc 1.5m wide and not exc 1.5m in depth; for laying cable and getting out in any type of soil, complete all as specified and directed. |
| 5 | M & L forreturning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm in any type of soil, complete all as specified and directed |
| 6 | M & L for removing excavated soils to a distance n exc. 50m and depositing where directed at a level n exc. 1.5m above the starting point complete all as specified anddirected. |
| 7 | Labour charges for spreading of riddled earth obtained from trenchesfor cable cushioning on top and bottom of cable as specified.for cable protection complete all as specified and directed. Note: Only punned thickness of riddled earth shall be measured |
| 8 | Supply and laybricks in trenches , common burnt clay building bricks, subclass `B’ designation 75, old size ,with width equal to thelength of the brick; laid dry on edge vertically complete all as specified and directed. |
| 9 | Supply & Fix in repairs energy saving LED street light fittings,35 Wattsor nearest higher wattage, with in-built electronic driver, IP 65 class of protection with versatile pressure die-cast aluminium housing parts, pure polyester powder coated dark gray housing, toughened glass cover with silicon gaskets and energy efficient LEDincluding all accessories and dismantling of old unserviceable fittingfor taking into credit complete all as specified and as directed. |
| 10 | Supply & Fix in repairs LED street light fitting 70 watt 230 V AC outdoor type with high pressure die cast aluminum housing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65 protection including dismantling of old unserviceable fittingfor taking into credit all as specified and as directed. |
| 11 | Supply & Fix in repairs LED flood light 150 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp. and dismantling of old unserviceable fittingfor taking into creditall as specified and as directed. |
| 12 | Supply & Fix in repairs150 W LED search light long range type, 230 Vsuitable for fixing in watch tower cabin, weather,verminand dust proof swiveling type with stainless steel body , tripod and glass reflectors, suitable driverand othercontrolling accessories and dismantling of old search light all as specified and directed |
| 13 | Supply and fix in repairs 12 W LED luminaire suitable for a solar street light, including taking down the existing luminaire of any type, complete as specified and directed. |
| 14 | Supply and fix in repairs 75W solar panel suitable for 1 × 12 W LED solar light fitting, after taking down the unserviceable solar panel, complete as specified and directed. |
| 15 | Supply and fix in repairs pole mounting type FRP cable looping box with connector having internal dimension 250 mm × 250 mm × 150 mm, with 40 × 6 mm flat iron, including suitable brass glands, lugs etc. The terminal box shall be fixed on the pole with a suitable fixing arrangement, complete as specified and directed. |
| 16 | M & L in replacement of GI bracket made out of 32 mm dia GI pipe length 1.50m,bent to an angle of 30 degree andfixed with 40mm x 6mm flat iron, including suitable 02 setofclamps withnut , bolts ,and washers for fixingof light to pole complete all as specified and as directed. |
| 17 | Supply & Fix in repairs 240V, 10 KA \"B\" curve miniature circuit breaker (MCB) of single pole and current carrying capacity 6 to 15 AMP, in the MCB DB Complete with connection testing and commissioning all as specified and directed |
| 18 | M & L for 40mm bore `light grade` galvanised tubes with all fitting, laid in trenches complete all as specified and as directed. |
| 19 | Supply & Fix in repairs analog time switch of capacity 16 Amp single outlet with 3 position over ride switch ON-AUTO-OFF on front panel for switching on/off street/security lights/flood light circuitcomplete all as specified anddirected. |
| 20 | Supply and lay LT underground cable of 1100-volt grade, Cross-linked Polyethylene (XLPE) insulated, PVC-sheathed, 4-core, 25 sqmm, armoured, multistranded heavy-duty aluminium conductor cable, laid in trenches/ducts/walls, including cable glands at both terminations where required, laying and connecting to various switches in the panel board, testing and commissioning, and taking out existing unserviceable cables, complete all as specified and directed. |
| 21 | Supply , installation, testing and commissioning of outdoor LT feeder pillar box in replacement, CPRI Approved ,factory fabricated in afactory having modern fabrication and testing process which includes seven tank pre-treatment process comprising of degreasing, rinsing, de-rusting , rinsing, phosphatising, rinsing and passivation followed by powder coat painting having thickness not less than 100 microns . The doors shall be provided with suitable gasket and latchincluding PCC foundation for erecting the panel board.Feeder piller shall be suitable to accommodate the following as specied and as directed:-OUTER SHELL : The outer shall be made out of 3.15 mm thick CRCA sheet &MS angle section 50x50x6 mm frame, factory fabricated with front & back openable, double door system lockable/openable by keys from both sides having chromium platedlocks. ‘U’ type gasket shall be used to make the outer shell completely vermin proof. The bottom of the outer shell contains a detachable plate of thickness 3.15 mm powder coated having provision for entry of armoured cable of adequate size with glands. The outer shell shall be powder coated Siemens grey structural RAL 7032 shade. |
| 22 | Serial item NO 21 contd.../ INNER SHELL : Inner shell shall be made out of 2.0 mm thick CRCA sheet duly compartmentalized for each control gear, front & back openable single door system lockable / openable by keys from both sides having chromium platedlocks (2 Nos in each compartment),having louvers & air vent gasket for natural flow of air.The TPN bus bar shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size ‘F’ class insulator made on non hygroscopic, non combustible , track resistant, high strength FRP/SMC/DMC material at an interval not more than 500mm throughout the length of the TPN bus bar for the following panel:-(a) The bus bar chamber comprising of high conductivity aluminium bus bar of capacity 270 Amps three phase and half the capacity for neutral.INCOMING(a) MCCB 415 V,160 A, 4 pole breaking capacity 25 KA- 01 No. (b) Manual Change over switch 160 A - 01 No. (c) Digital Panel Meter Multifunctional type for Amps, Volts, KWH, Power Factor and other parameters flush mounting with LED indication lamp complete and all as per standard practice ---1 Job OUT GOING(a) MCCB 100 A, 415V , 4 pole , breaking capacity 16 KA - 01 Nos (b) MCCB 63 A, 415V ,4 pole , 16kAC Curve- 02 Nos (c)MCCB40 A, 415V , TPN , 16kAC Curve- 04Nos |
| 23 | M&L for taking down old unserviceable GI pipe and supplying and fixing new GI pipe, light grade, 50 mm dia, for protection of underground cables on walls, under floors, at road crossings, or in trenches, including taking down the old unserviceable earthing GI pipe for taking into credit, complete as specified and as directed. |
| 24 | Schedule of credit amount brought back from Ser Page No.32- Rs. 38,800.00 will be deducted from the above quoted amount to derive the contract sum. SIGNATURE OF CONTRACTOR |