| 1 | Excavating in trenches, not exceeding 1.5m wide and not exceeding 1.5m in depth, for foundations etc or manholes, cesspits, pipes and cables etc. not exc 10 Sqm on plan and getting out in any type of soil all as specified and directed by Engineer - in - Charge. |
| 2 | Returning, filling in, including spreading, levelling, watering and well ramming in layersof soft / loose soil not exceeding 25cm thick all as specified and directed by Engineer - in - Charge. |
| 3 | Removingexcavated material n exc. 50 m and depositing where directedat a level not exceeding 1.5m above the starting point all as specified and directed by Engineer - in - Charge. |
| 4 | M&L 25 mm thick Cement Conrete 1:2:4 type B–0 using 12.5mm graded stone aggregates flooring finished even and rough to receive topping layer all as specified and directed by Engineer - in – Charge . |
| 5 | M&L for chequered cement concrete tiles 20cm x 20cm x 25mm thick with grey cement and pigments set, jointed and pointed in neat cement slurry and pigments as in floors over and including 20mm thick screed bed of cement mortar 1:4 complete all as specified and directed by Engineer - in – Charge. |
| 6 | M&L for glass mosaic coloured tiles of size 300 x 300 x 8mm thick of premium quality fixed on wall by applying deformable cementitious adhesive with no vertical slip high performance after completing water proofing treatment complete all as specified and directed. |
| 7 | M&L providing and applying 10 mm thick plaster with Sika Monotop-122F mixing with 4.5 - 4.8 ltr water per 30 kg of Sika Monotop. Material should have Compressive strength ≥ 55 MPa after 28 days, Tensile strength in flexure ≥ 9.0 MPa after 28 days, Tensile adhesion strength ≥ 12.0 MPa after 28 days.Product : Sika Monotop -122F of M/s SIKA or equivalent product of makes M/s Fosroc or M/s Pidlite. |
| 8 | M&L providing and applying high performance flexible acryliccementitious waterproofing coating having Tensile strength ≥ 2.0 MPa, Tensile adhesion strength ≥ 2.0 MPa. Material shall be applied with base coat @ 1.0 Kg/Sqm with fibre reinforcement mesh of Top coat @ 1.2 kg/Sqm above over a coat ofprimer @ 0.20 Kg/Sqm after proper surface preparation . Material shall be prepared by mixing Acrylic polymer with portland cement with selected aggregate and additives in ratio 1:1.5 by weight.Product :SikaTop - 109 Seal IN of M/s SIKA or equivalent product of makes M/s Fosroc or M/s Pidlite. |
| 9 | M&L for Surface excavation of soft / loose soil n.exc (not exceeding) 30cm deep and averaging 15cm deep and getting out complete all as specified. |
| 10 | S&F waterproof light fitting, IP-68, RGB colour, Stainless Steel body, LED 10 W complete all as specified and as directed. |
| 11 | M&L RGB controller for the required capacity (12 V 20 ampof LED Light complete in all respect to be fitted in control panel with required wiring and switches complete all as specified and as directed. |
| 12 | S&F stainless steel pipe, 54 mm dia, grade 304 and circular in shape Straight Pipe and having provision of fixing nozzles 15 mm with threads as directed for fountain including welding work and including connecting work required as per site complete all as specified and directed. |
| 13 | S&F of brass nozzle adjustable type of 15 mm dia medium grade, interior thread, ball joint complete all as directed. |
| 14 | S&F 25mm bore medium grade steel tubes galvanised with all fittings and fixed complete to walls & ceiling or laid in floor all as specified and directed by Engineer - in – Charge . |
| 15 | S&F 50mm bore medium grade steel tubes galvanised with all fittings and fixed complete to walls & ceiling or laid in floor all as specified and directed by Engineer - in – Charge . |
| 16 | Supply, laying and testing PVC cable with copper conductor, unarmoured heavy duty LT power cables, 1100 volts grade cross sectional area2.5 sqmm4 Core including lux of cable complete all as specified and directed. |
| 17 | Supply, laying and testing PVC cable with copper conductor, unarmoured heavy duty LT power cables, 1100 volts grade cross sectional area4 sqmm3 Core including lux of cable complete all as specified and directed. |
| 18 | Supply, installation, testing and commissioning of LT panel of suitable size in replacement of outdoor type dust proof & vermin proof cubical panel board compartmentalized with seperate bus and cable alley chambers suitable for 3 phase, 4 wire, 415 Volts, 50 Hz, AC supply system as per latest IS / IEC standards & regulations, factory fabricated in an approved factory (Manufacturer possessing CPRI test report for equivalent ratings)having modern fabrication facilities, made out of CRCA sheet steel of 3mm thick for outer shell and 2mm thick for inner shell with front and rear openable double leaf doors with two point locking arrangement i.e. locking system with handle up & down arrangement & pad-locking facility , including PCC foundation with PCC 1:2:4, type B1 using 20mm graded stone aggregate with following:- |
| 19 | (a) Bus bar: TPN Aluminium bus bar of suitable rating provided with heat shrinkable coloured PVC sleeve insulation mounted on insulators for main bus bar and from main bus bar to outgoing MCCBs and outgoing MCCBs up to cable termination etc complete.(b) MCCB, 63 A, 4 Pole, 30 KA (Ics=100%Icu), 415 V, 50 Hz, with adjustable thermal & magnetic release - 01 No(c) Digital Voltmeter with selector switch - 01 Set.(d) Digital Ammeter with selector switch & suitable ratio of CT\"s - 01 set of 03(e) LED Pilot light indication lamps for R,Y,B phases - 01 Set of 03(iii) Outgoing:- (a) MCB, TPN ,32 A, \"C\" curve - 03 Nos |
| 20 | NOTE :-(i) All existing and new connections of incoming/ outgoing cables shall be done through appropriate size of copper thimbles. (ii) The Contractor shall submit set of all drawings of the L.T. Pillar Boxes and its components in duplicate and get the same approved from GE before commencement of production. The contractor shall furnish all details and clarifications required if any for scrutiny and evaluation. Manufacture of material to be supplied shall be done strictly as per approved drawing. However, approval of drawing shall not absolve the contractor/supplier of his liability for ensuring correctness according to applicable standards & regulations. |
| 21 | S&Fmonoblock Pump motor set for 440 V , 3 Phase 50 Hz, 7.5kw/10HP, 2900 rpm Head - 40 M, Discharge not less than 500 LPM with CIimpeller & shaft mounted on heavy duty bearing complete all as specified and directed by Eingr-in-Charge. |
| 22 | S&F automatic star delta starter suitable for 10 HP capacity motor, relay 10-16, confirming to IS/IEC 60947-4-1, IP54, sheet steel enclosure complete all as specified and directed. |
| 23 | S&F openwell submersible pump set for clear water pumping, 440 V , 3 Phase 50 Hz, 5HP, 2900 rpm with CIimpeller complete all as specified and directed by Eingr-in-Charge. |
| 24 | S&F DOL starter for induction motor capacity of 5 HP three phase ,415 V, 50 Hz as per specified and directed by Engr-in-charge. |
| 25 | S&F gunmetal globe or gate valve with iron wheel head, screwed both ends for iron pipes 50mm bore complete all as specified and directed by Engineer – in – Charge. |
| 26 | Supply, laying and testingPVC cable with copper conductor,unarmoured heavy duty LT power cables, 1100 volts grade cross sectional area10 sqmm3 Core including lux of cable complete all as specified and directed. |
| 27 | M&L Cement concrete 1:2:4 type B-2 using 40mm graded crushed stone aggregate for foundations, fillings and mass concrete all as specified and directed by Engineer – in - Charge. |