| 1 | Supply, installation, testing and commissioning of 100W new-generation, energy-saving and environmentally-friendly long-life LED street light, made of pressure die-cast aluminium housing with high-efficiency LEDs as lighting source, having an efficacy of >110 lm/W, CRI >80, CCT ~5000 K, average life L70 ≥ 50,000 hours, no harmful UV and IR radiations. The luminaire shall operate at a temperature range of -10 °C to +45 °C, shall have surge voltage protection, IP66 protection, and impact resistance of IK07, to be installed on the existing bracket present on poles. LM79 & LM80 test reports shall be submitted from a government-approved NABL laboratory. The OEM must have its own in-house NABL testing facility for LED fixtures. Complete job including testing, commissioning and handing over to the department. The job includes replacement warranty of the fixture if damaged or burnt out for any reason for a period of two years from the date of successful commissioning / handing over to the concerned department. (Havells / Philips / Crompton / Jaguar / Wipro/ eq. make to be approved by EIC) |
| 2 | Supply, Laying, Connecting and Commissioning of 16 sq mm 4 core XLPE/ PVCInsulated and steel armored 1.1 KV grade Aluminum LT cable for Service line, incl. cost of required al. thimbles duly crimped. (Over head/ under ground) (Havells/Polycab/KEI/ eq. make to be approved by EIC) |
| 3 | Supply, laying, connecting and commissioning of 10 sq mm 4 core XLPE/ PVCInsulated and steel armored 1.1 KV grade Aluminum LT cable for Service line, incl. cost of required al. thimbles duly crimped. (Over head/ under ground) (Havells/Polycab/KEI/ eq. make to be approved by EIC) |
| 4 | Supply, installation, testing and commissloning of 5-32A single pole rating 240/415V,10 KA \"C\" curve MCB of Legrand/ Havells/ L&T/ABB/ eq. make to be approved by EIC suitable for inductive load in the MCBdistribution board complete with necessary connections. |
| 5 | Supply, installation, testing and commissloning of 100A 4P Connector of Legrand/ Havells/ L&T inside existing junction box complete with necessary connections. |
| 6 | Supplying, installation, testing and commissioning of pole mounted junction box of standard make ISI marked suitable to accommodate SPMCB and 4P Connector. incl all reqd. connections, Complete job. |
| 7 | Wiring for Circuit along with earth wire in FRLS PVC insulated 660/1100 volt grade flexible stranded copper conductor wires in recessed or surface conduiting system, excluding cost of conduits. (Havells/ Polycab/ Finolex/ Anchor/KEI/RR or equivalent). |
| 8 | 2x 2.5 sq mm |
| 9 | Supply, installation, testing and commissloning of 63A TPN MCB including spreader links inside existing Panel (Legrand/ Havells/ L&T/ABB/ eq. make to be approved by EIC) |
| 10 | Supply, installation, testing and commissloning of Astronomical timer with 4 pole contactor of suitable capicity. (Legrand/ Havells/ L&T/ABB eqv. Make) |
| 11 | Supply, installation, testing and commissloning of 100 amp TPN MCCB 35 KA including spreader links inside existing Panel (Adjustable thermal and Adjustable magnetic release ) Legrand/ Havells/ L&T/ABB/ eq. make to be approved by EIC |
| 12 | Supply, laying, and fixing of 32mm dia PVC Conduit (FRLS type), medium class, confirming to IS: 9537 standards, including all necessary accessories such as bends, couplers, tees, saddles, and junction boxes, complete as per site requirements and specifications. |
| 13 | Repairing, fixing and commissioning of 15 kVA three-phase Servo Stabilizer, including replacement/repair of servo motor,phase auto system, Voltmeters, Ammeters, 60A DP relay,20-32A dimmer, and all other damaged components. All spare parts used shall be of standard make and ISI marked. The work shall be carried out as per direction of the Engineer-in-Charge and shall include testing and commissioning at site. The stabilizer shall be handed over in fully operational condition and shall carry a minimum one-year warranty after commissioning. All dismantled unserviceable materials shall be handed over to the intending department.The cost of repair/replacement of components is provisional and may vary depending upon the actual condition of equipment and parts found during execution. Please Enable Macros to View BoQ information |