| 1 | Taking down carefully copper/aluminium point wiring on batten/ PVCconduit (light, fan, socket or power) complete including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fittings etc, including removal and making good disturbed surfaces of walls, ceilings etc by cement/colour/plaster to match with the existing location spot complete all as specified & directed. |
| 2 | M&L for point wiring concealed type with 1.50sqmm PVCFRLS insulated, unsheathed, single core, multistranded copper conductorcable 1100 volts grade including 1.5sqmm FRLS PVC insulated unsheathed stranded copper conductorcable as earth continuity conductor drawnin and including rigid PVC conduit of suitable size but not less than 20mm dia with its accessories, sunken type pressed steel terminal box made of 1.2mm thick MS sheet/ anodised steel box painted with one coat of red oxide primer including 3.0mm thick ISI marked plastic laminated sheet cover for fixing switches/ socket/regulators etc including cutting chases in wall as per standard engineering practice & making good the disturbed surfaces to match with existing for the one light/ fan/street/bell point controlled by 1 one wayswitch 5/6 Amps complete all as specified & directed. |
| 3 | all as per item No-2 here in before but with 2.5 sqmm PVC FRLS wire for one socket out let 3/5 pin, 5/6 Amps controlled by 1 one wayon the same board with other switches complete all as specified & directed. |
| 4 | all as above item No-2 butone socket out let with 2.5 sqmm PVC FRLS wire for 3/5 pin, 5/6 Amps controlled by one 1wayswitch on independent board but not below the switch board of light points in same vertical plane complete all as specified & directed. |
| 5 | all as per item No-2 here in before but using2.5 sqmm PVC FRLS insulated stranded copper cunductor cable andfor one socket out let 3/6 pin, 15/16 Amps controlled by one 1 way switch on independent board complete all as specified & directed.NOTE-For item No. 2 to 5-: (i)The quoted rates shall be deemed to be inclusive for cutting chases in brick walls/pillers etc for concealing the conduits to required depth & making good the disturbed surfaces in cement mortar 1:4 including finishing the surface to match with the existing surface.The portion of point wiring at RCC Coloumns/Beams/Ceilings etc shall be in surface conduit of suitable size fixed on surface with using PVC rawl plug and provision of covering terminal boxes/junction boxes of any shape and size with 3 mm thick bakelight laminated sheet fixed with suitable GI screws and cup washers. (ii) Fittings like switches,sockets,regulators,lamp holders,light foittings shall be measured and paid for separately under appropriate item of schedule A.(iii)The size of conduits shall be determined on permissible no of runs of wires as specified in SSR part-I clause 19.125 (B) However minimum size of conduit shall be 20 mm dia (medium grade) |
| 6 | Supply & fix commissioning and testing of complete power cum starter unit compressing of ON/OFF switches socket 3 pin socket outlet with plug top modular type made out of white polycarbonate, fire retardant, UV stabilized power unit internally pre-wired with suitable size copper conductor cable with overload protective device (MCB) complete unit fixed in single polycarbonate housing with inlet & outlet cable port suitable for AC & geyser operated at single phase, 240 volts, 50 Hz AC supply of capacity 25 Amps load bearing capacity complete all as specified and directed. |
| 7 | Supply & fix in replacement, single pole and neutral sheet metal enclosure (AC box) with a two pin & earth plug and socket with one No. MCB SP of capacity 25 Amps 240 volts complete all as specified & directed. |
| 8 | Supply and fix in replacement switch piano, flush type, single pole, 5/6 Amps one way, 230 volts complete all as specified and directed. |
| 9 | Supply and fix in replacement socket outlet, 5/6 Amps, flush type, 5 pin 230 volts complete all as specified and directed. |
| 10 | Supply and fix in replacement switch piano, flush type, single pole, 15/16 Amps one way, 230 volts complete all as specified and directed. |
| 11 | Supply and fix in replacement socket outlet, multi-purpose 3 pin 5/6 Amps and 3 pin 15/16 Amps complete all as specified and directed. |
| 12 | S&F switch, bell push button, single pole,5/6 Amps, one way, 230 Volts complete all as specified and directed. |
| 13 | S&F for ceiling rose surface bakelite 62.5 x 25 mm size 3 terminals complete all as specified and directed. |
| 14 | Supply and fix in replacement lamp holder insulated body with back plate for batten fitting complete all as specified and directed. |
| 15 | Supply & fix in replacement rotory stepped type electronic fan regulator mini flush type 100 watt 230 Volts complete all as specified & directed.Make: Anchor Cat No.38284/38660 or equivalent as approved by GE. |
| 16 | Supply and fix electrical bell model city ding dong (Ding dong type) AC, 230 Volts complete all as specified & directed. |
| 17 | M&L for point wiring concealed type with 1.50sqmm PVCFRLS insulated, unsheathed, single core, multistranded copper conductorcable 1100 volts grade including 1.5 sqmm FRLS PVC insulated unsheathed stranded copper conductorcable as earth continuity conductor drawnin and including rigid PVC conduit of suitable size but not less than 20mm dia with its accessories, to be terminated in and excluding modular metal GI flush box for fixing modular type switches/ socket/regulators etc including cutting chases in wall as per standard engineering practice & making good the disturbed surfaces to match with existing for the one light/ fan/street/bell point controlled by 1 one wayswitch 5/6 Amps complete all as specified & directed. |
| 18 | all as per item No-17 here in before but point wiring for one modular socket out let 3/5 pin, 5/6 Amps controlled by one 1 waymodular switch on the same board with other switches complete all as specified & directed. |
| 19 | all as per item No-17 here in before but point wiring for one modular socket out let 3/5 pin, 5/6 Amps controlled by one 1 waymodular switch on the same board with other switches complete all as specified & directed. |
| 20 | all as per item No-17 here in before but point wiring for one six pin socket outlet 15 & 5 amps (independent) controlled by one modular switch using PVC FRLS cable of size 2.5 sqmm complete all as specified & directed. NOTE for item No. 17 to 20-: (i) the new metal flush mounting sunken boxes and its covering plates etc shall be measured and paid for separately under respective item of this schedule. (ii)The quoted rates shall be deemed to be inclusive for cutting chases in brick walls/pillers etc for concealing the conduits to required depth & making good the disturbed surfaces in cement mortar 1:4 including finishing the surface to match with the existing surface.The portion of point wiring at RCC Coloumns/Beams/Ceilings etc shall be in surface conduit of suitable size fixed on surface with using PVC rawl plug and provision of covering terminal boxes/junction boxes of any shape and size with 3 mm thick bakelight laminated sheet fixed with suitable GI screws and cup washers. (iii) Fittings like switches,sockets,regulators,lamp holders,light foittings shall be measured and paid for separately under appropriate item of schedule A.(iv)The size of conduits shall be determined on permissible no of runs of wires as specified in SSR part-I clause 19.125 (B).However minimum size of conduit shall be 20 mm dia (medium grade) |
| 21 | Supply and fixing modular cover plate with metal frame (inner and outer) 2 module for mounting switch and sockets all as specified and as directed. |
| 22 | Supply and fixing modular cover plate with metal frame (inner and outer) 3 module for mounting switch and sockets all as specified and as directed. |
| 23 | Supply and fixing modular cover plate with metal frame (inner and outer) 4/5 module for mounting switch and sockets all as specified and as directed. |
| 24 | Supply and fixing modular cover plate with metal frame (inner and outer) 6 module for mounting switch and sockets all as specified and as directed. |
| 25 | Supply and fixing modular cover plate with metal frame (inner and outer) 6 x 2 module for mounting switch and sockets all as specified and as directed. |
| 26 | Supply and fix bell push modular type, single pole, 6 Amps one module,one way, 230 volts complete all as specified and directed. |
| 27 | Supply and fix in replacement switch modular type, single pole, 6 Amps one module,one way, 230 volts complete all as specified and directed. |
| 28 | Supply and fix in replacement socket outlet, 6 Amps, modular type, 2 module 230 volts complete all as specified and directed. |
| 29 | Supply and fixin replacement switch modular type, single pole, 16 Amps one module,one way 230 volts complete all as specified and directed. |
| 30 | Supply and fix in replacement socket outlet, 6/16 Amps, modular type, 2 module 230 volts complete all as specified and directed. |
| 31 | Supply & fixin replacement rotory stepped type electronic fan regulator modular type,Single module120 watt230 Volts complete all as specified & directed. |
| 32 | Supply and fixing LED Bulb 12 watt suitable for lamp holdercomplete all as specified and directed. |
| 33 | Supply and fix LED Bulb 12 W inverter/rechargeable type for lamp holder complete all as specified and directed. |
| 34 | Supply and fix LED Bulb 15 W suitable for lamp holder complete all as specified and directed. |
| 35 | Supply and fix LED Bulb 9 W suitable for lamp holder complete all as specified and directed. |
| 36 | Supply and fix LED Bulb 9 W inverter/rechargeable type suitable for lamp holder complete all as specified and directed. |
| 37 | Supply and fix LED Bulb 18 W suitable for lamp holder complete all as specified and directed. |
| 38 | Taking down existing old/ U/S sub main wiring along with fitting/fixtures existing of any type and description, removal of teak wood batten/ PVC pipe/ PVC casing & caping and making good disturbed surfaces of walls, ceilings etc by cement/colour/plaster to match with the existing location spot complete all as specified and directed. |
| 39 | M&L for in replacement of sub main wiring with two runs of single core FRLS PVC insulated, unsheathed, mutistranded copper conductor cable of size 2.5 sqmm drawn in and including rigid PVC rigid conduit medium grade of suitable size but not less than 20mm dia with its accessories, concealed type, including one run of single core FRLS PVC insulated, unsheathed, stranded copper conductor cable of size 2.5 sqmm as earth continuity and cutting chases to wall as per standard engineering practice & making good the disturbed surfaces as per existing complete all as specified & directed.Notes:-Finished sub main wiring with two runs of 2.5 sqmm cable & one run of 2.5 sqmm cable alongwith PVC conduit including its accessories shall be measured and paid one unit length. |
| 40 | M&L for in replacement of sub main wiring with two runs of single core FRLS PVC insulated, unsheathed, mutistranded copper conductor cable of size 4.0 sqmm drawn in and including rigid PVC rigid conduit medium grade of suitable size but not less than 20mm dia with its accessories, concealed type, including one run of single core FRLS PVC insulated, unsheathed, stranded copper conductor cable of size 4.0 sqmm as earth continuity and cutting chases to wall as per standard engineering practice & making good the disturbed surfaces as per existing complete all as specified & directed.Notes:-Finished sub main wiring with two runs of 4.0 sqmm cable & one run of 4.0 sqmm cable alongwith PVC conduit including its accessories shall be measured and paid one unit length. |
| 41 | M&L for in replacement of sub main wiring with two runs of single core FRLS PVC insulated, unsheathed, mutistranded copper conductor cable of size 6.0 sqmm drawn in and including rigid PVC rigid conduit medium grade of suitable size but not less than 20mm dia with its accessories, concealed type, including one run of single core FRLS PVC insulated, unsheathed, stranded copper conductor cable of size 6.0 sqmm as earth continuity and cutting chases to wall as per standard engineering practice & making good the disturbed surfaces as per existing complete all as specified & directed.Notes:-Finished sub main wiring with two runs of 6.0 sqmm cable & one run of 6.0 sqmm cable alongwith PVC conduit including its accessories shall be measured and paid one unit length. |
| 42 | Supply & fix surface/wall mounting LED batten 20 watt luminaire having extruded aluminium housing provided for efficient heatdissipation with polycarbonate diffuser and integrated electronic driver with mounting accessoriescomplete withlamp holders fixed to wall/ ceiling with fixing accessories and connecting up with & including twin twisted copper flexible wire of size 0.75 sqmm from ceiling rose to fittings complete all as specified & directed. |
| 43 | Supply & fix surface/wall mounting LED batten 22 watt luminaire having extruded aluminium housing provided for efficient heatdissipation with polycarbonate diffuser and integrated electronic driver with mounting accessoriescomplete withlamp holders fixed to wall/ ceiling with fixing accessories and connecting up with & including twin twisted copper flexible wire of size 0.75 sqmm from ceiling rose to fittings complete all as specified & directed. |
| 44 | Supply and fixing 20W Inverter LED batten with square profile and polycarbonate channel. Lithium Ion battery with charging time 8hours-10 hours and back up time upto 4 hours including connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and directed. |
| 45 | Supply& fixing LED Batten 20W3- in -1 light LED Batten (color – cool day light, natural white and warm light) surface/wall mounted with specially designed powder coated aluminium housing complete all as specified and directed. |
| 46 | Supply & fix in replacement, outdoor street light LED 36/40 watt luminaire IP 65/66 protection polyster powder coated with pressure die cast aluminium housing and robust construction with reflector coverpre anodised and flat white high transmission acrylic cover or toughened glass, natural white type with electronic driver, connector block etc with internally prewired fixed to building with and including 1.20M long bracket made out of 40mm dia light grade GI pipe bent to shape & providing clamps 2 Nos made out of 50 x 6 mm Flat iron/MS clamps & 12mm dia bolts, nuts & washers etc and connecting up with & including twin twisted copper flexible wire from ceiling rose to fittings complete all as specified & directed. |
| 47 | Supply & fix in replacement, surface mounting type bulkhead 10 watt LED luminaire with reflector coverelectronic driver, connector block etc with internally prewired fixed to wall with fixing accessories and connecting up with & including twin twisted copper flexible wire from ceiling rose to fittings complete all as specified & directed. |
| 48 | Supply & fix, surface/ ceiling mounting type 36 watt LED luminairePLUTO NEO PENAL 2ftX2ft (600mm x 600mm) environmental friendly new generation aesthetically ultra modern recess mounting with high brightness SMD LEDs as light source with reflector cover electronic driver, connector block etc with internally prewired fixed to ceiling with fixing accessories and connecting up with & including twin twisted copper flexiblewire of size 0.75 sqmm from ceiling rose to fittings complete all as specified & directed. |
| 49 | Supply and fixingLED light fitting mirror type with high out put diffuser 2 feet, 10 watt 220 V AC decorative type with driver holder and LED lamp including connecting up with three core flexible copper conductor cable of suitable size complete all as specified and directed. |
| 50 | Supply & fix in replacement, surface round mounting type 12/15 watt LED luminaire with reflector coverelectronic driver, connector block etc with internally prewired fixed to ceiling with fixing accessories and connecting up with & including twin twisted copper flexible wire from ceiling rose to fittings complete all as specified & directed. |
| 51 | Supply & fix in replacement, surface square mounting type 12 watt LED luminaire with reflector coverelectronic driver, connector block etc with internally prewired fixed to ceiling with fixing accessories and connecting up with & including twin twisted copper flexible wire from ceiling rose to fittings complete all as specified & directed. |
| 52 | Supply & fix NEW GENERATIONPOST TOP energy saving envirmental friendly long life 35 watt LED luminaire light fitting, IP 65 protection with reflector coverelectronic driver, connector block etc with internally prewired fixed to brcketon gate with fixing accessories and connecting up with & including twin twisted copper flexible wire from ceiling rose to fittings complete all as specified & directed. |
| 53 | Supply and fixing of bollard light fitting suitable for 09 to 12 Watts LED Bulb/ light fully cast aluminum body finished with polyurethane paint (with prior treatments) bollard of length 755 mm (29.75 Inches) & circular base diameter of 177 mm (7 Inches) and max diameter of leg of bollard 76 mm (3 Inches) surmounted with aluminium sheet spray painted canpoy & transparent improted acrylic cover with 5 Louvers duly stacked duly pipe mounted on cast aluminium spigot as per IS 10322, B-22 ABS holder alongwith lamp lock device. Total Length of fiting 349 mm (13.75 Inches) and Max Breadth of fitting 304 mm (12.0 Inches) total length of bollard fitting 1104 mm (43.5 Inches). |
| 54 | Supply and fix in replacement MCB DB vertical type 4 way VTPN sheet metal enclosure 415 volts with 100 Amp fully insulated standard copper bus bar for each face & surrounded with neutral bars and two common neutral bar, two earth bar including cable tiesfor cable manegement suitable for housing MCCB TPN 415 Volts as incommer, IP-43, IK-09 as per IEC 61439-3 with metal doors all enclosed on standard steel sheet flush mouting type double door factory fabricated completewithout MCB & MCCB but with enclosue blank plate complete all as specified and directed . |
| 55 | Supply and fix in replacementMCB DB 4 way sheet metal enclosure triple pole and neutral 415 volts with 200 standard bus bar of suitable size and common neutral link and earth bar all enclosed on standard steel sheet flush mouting type double door factory fabricated complete without MCB but with enclosue blank plate complete all as specified and directed . |
| 56 | Supply and fix in replacement MCB DB sheet metal enclosure factory fabricated double door SPN 8 way with 200 amps rated bus bar 240 volts complete all as specified and directed. |
| 57 | Supply and fix in replacement MCB DB sheet metal enclosure factory fabricated double door SPN 4 way with 200 amps rated bus bar 240 volts complete all as specified and directed. |
| 58 | Supply and fix in replacement MCCB 4 pole 100 to 250 Amp Icu 16 Kilo Amp and Ics 100% of Icu with adjustable 70% to 100% and thermal magnetic release suitable for fixing in VTPN DB. |
| 59 | Supply and fixing in replacement miniature circuit breaker (MCB) TPN 40 to 63 Amp, 4 poles, 415V 10KA \"C\" curve current carrying capacity in the DBIP-20 as per IEC 60947-3 ISI marked complete with connection testing and commissioning., complete all as specified & directed. |
| 60 | Supply & fix in replacement MCB SPN, 40 Amps,\"C\" series, 240 volts, 50Hz, 10kA complete all as specified & directed. |
| 61 | Supply & fix in replacement MCB SP, 40 Amps, \"C\" Curve, 240 volts, 50Hz, 10kA IP-20 as per IS/IEC 60898-1 2002 ISI marked complete all as specified & directed. |
| 62 | Supply & fix in replacement MCB SP, 6 to 32 Amps, \"C\" series, 240 volts, 50Hz, 10kA complete all as specified & directed. |
| 63 | M&L for earthing in replacement complete with galvanized steel earth plate electrode 600 x 600 x 6.0mm thick directly burried in the ground (Earth pit not less than 2.25 m deep below ground level) with top edge of earth plate not less than 1.50M below the normal ground level, GI wire 4.0mm dia from earth plate/ electrode to test point (upto max distance of 7.50M is included in unit rate) and connected to earth plate & earth test point by means of bolts, nuts, check nuts andwashers of galvanised iron or steel, 15mm bore GI pipe light grade including necessary fittings for protection of earthing wire, watering pipe 20mm bore GI medium grade, concrete chamber in PCC (1:4:8) type D-2 using 40 mm grade aggregate, coping shall be in PCC (1:3:6) type C-1 using 20 mm grade aggregate and internal surfaces of concrete chamber shall be renderd 12mm thick plaster in CM (1:4), funnel with wire mesh of 22 gauge (0.63 mm) 8 mesh per linear incl 50mm thick cover of RCC (1:2:4) type B-1 using 20mm grade stone aggregate reinforced with 8mm MS deformed bar @ 75 mm C/C both ways, char coal dust and common salt all as shown in electrical plate No. 3 of SSR Part-I (2009) includingall necessary excavation & earth work and removal of surplus soil to a distance n. exc 50M andconnection from DB to earth electrode with same GI wire alongwith protection pipe and testing on completion complete all as specified and directed. |
| 64 | Supplying and fixing in repair/replacement 1100 volts grade heavy duty cable PVC insulated stranded aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections uspended by insulating hangers not more than 1 metre apart including 4mm suspension wire, one twin core of size 4.0 Sqmm cable flat or circular compele all as specified and as directed by Engr-in-Charge. |
| 65 | Supplying and fixing in repair/replacement 1100 volts grade heavy duty cable PVC insulated stranded aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections uspended by insulating hangers not more than 1 metre apart including 4mm suspension wire, one twin core of size 6.0 Sqmm cable flat or circular compele all as specified and as directed by Engr-in-Charge. |
| 66 | S & Laying,jointing,commissioning and testing in repair/replacement XLPE insulated steel armoured heavy duty elect power cable 1100 volt grade, stranded aluminium conductor 4 core 25 sqmm laid in trenches or fixed to wall with saddles or layed in duct or passing through pipe for making electrical connection between LT panel/ feeder pillar box and DBs compele all as specified and as directed by Engr-in-Charge. |
| 67 | S & Laying,jointing,commissioning and testing XLPE in repair/replacement insulated steel armoured heavy duty elect power cable 1100 volt grade, stranded aluminium conductor 4 core 16 sqmm laid in trenches or fixed to wall with saddles or layed in duct or passing through pipe for making electrical connection between LT panel/ feeder pillar box and DBs compele all as specified and as directed by Engr-in-Charge. |
| 68 | Excavation in trenches n.exc 1.5 mtr wide and n.exc 1.5 mtr deep in soft/loose/ soil for taking out/laying CI/GI pipe line and getting out soft/loose soilcomplete all as specified and as directed by Engineer-in-Charge. |
| 69 | Returning, filling in including spreading, leveling, watering and well ramming in layers n.exc 25 cm thick layers complete all as specified and as directed by Engineer-in-Charge. |
| 70 | Removal of excavated material n.exc 50 mtr away and depositing where directed at a level n.exc 1.5 mtr above from starting point complete all as specified and as directed by Engineer-in-Charge. |
| 71 | Supplying and laying un-rainforced precast concrete cable cover LV type-I flat size 250 mm x 150 mm x 40 mm in trenches for protection of cable. |
| 72 | M&L for sand cushioning dry fine for cable cushioningbelow and abovethe cable complete all as directed at site by Engr- in-Charge. |
| 73 | Supply and fixing GI Pipe 40mmLight grade , for cable protection laid in trench under road or pathor fixed on pole or wall with clamps with all fittings complete all as specified and as directed at site,. |