| 1 | Supply and lay cable XLPE Insulated screenedPVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of following sizes:- |
| 2 | (a) 10 Sqmm 2 core |
| 3 | (e) 25 Sqmm 4 core |
| 4 | (f) 35 Sqmm 3.5 core |
| 5 | (g) 50 Sqmm 3.5 core |
| 6 | (h) 70 Sqmm 3.5 core |
| 7 | (i) 95 Sqmm 3.5 core |
| 8 | (j) 120 Sqmm 3.5 core |
| 9 | (k) 150 Sqmm 3.5 core |
| 10 | (l) 240 Sqmm 3.5 core |
| 11 | Supply and fix, test , commissioning of LT weather proof panel board powder coated outdoor type double door shutter, made out of CRCA 3.15 mm thickouter and 1.6 mm thick for inner door confirming to IS 8623 with angle iron 50x50x6 mm outoor, floor mounting type with closed bus bar, chamber and with Aluminiumbus barwith necessary insulator suitable for 3 phase, 4 wire 50 Hz AC supplyas per CPRI approved including provn of digital ammeter 0-500A,digital voltmeter 0-500 Volts, CT\"s of suitable ratio, indicator lamps R-Y-B, selector switches and internal wiring including making PCC block type 0.6 Mtr above ground level grouting etc complete all as specified and directed with the following Work alsoincludes provision of suitable size of cable glands, cable lugs, nut, bolts, washers etc. The bottom portion of enclosure shall be minimum 60 cm above ground level of legs of angle iron)(Main Panel from 160 KVA TFRa) Aluminium bus bar capacity 600 Amps for Phase-R-Y-B-3 Nos & one for neutral -1 No b)MCCB FP 400 Amps 36 kA -01 No (I/C)c) MCCB FP 250 Amps 36 kA - 01 Nos (O/G to FP 3)d) MCCB FP 200 Amps 25 kA - 01 Nos (O/G to FP 1) e) MCCB FP 125 Amps 16 kA - 01 Nos (O/G to FP 2)f) MCB SPN 16 Amps 10 kA - 01 Nog) Timer with synchronous timer 0-24 Hrs suitable for street light controlandwith suitablecontactor single phase 20 Amps capacity - 01 Set |
| 12 | Ditto as per item No 2 above but comprising of following items(Feeder Panel - No 01from MP a) Aluminium bus bar capacity 300 Amps for Phase-R-Y-B-3 Nos & one for neutral -1 No b) MCCB FP200 Amps 25 kA - 01 No (I/C)c) MCCB FP40 Amps 16 kA - 08 Nos d) MCCB FP63 Amps 16 kA - 01 No |
| 13 | Ditto as per item No 2 above but comprising of following itemsFeeder Panel - No 03 from MPa) Aluminium bus bar capacity 400 Amps for Phase-R-Y-B-3 Nos & one for neutral -1 No b) MCCB FP250 Amp 25 kA -01 No (I/C)c) MCCB FP100 Amps 25 kA - 01 Nos (O/G )d) MCCB FP 40 Amps 10 kA -09 Nos (O/G) |
| 14 | Ditto as per item No 2 above but comprising of following itemsFeederPanel - No 02 from MP a) Aluminium bus bar capacity 200 Amps for Phase-R-Y-B-3 Nos & one for neutral -1 No b) MCCB FP125 Amps 25 kA - 01 Nos (I/C) c) MCCB FP40 Amps 16 kA - 07 No |
| 15 | Ditto as per item No 2 above but comprising of following itemsFeederPanel - No 04 from FP 3) a) Aluminium bus bar capacity 150 Amps for Phase-R-Y-B-3 Nos & one for neutral -1 No b) MCCB FP100 Amps 25 kA - 01 Nos (I/C)c) MCCB FP 40 Amps 16 kA - 04 No |
| 16 | Cable route indicator of size 100mm dia embossed as LT round shaped 10mm thick with marking of 1.1 KV, LT welded bolted on angle iron of 25x25 of 60cm length grouted in PCC (1:3:6) type C-2 using block size of 150x150x150mm embedded in ground including not exceeding earth work complete all as specified and directed. |
| 17 | Supply & fix Junction box of size 280 X 170 X 130 mmHinged (L) wiith 2 way connector mounted on epoxy insulators for looping of cablefor 1 Phase and1neutral fixed on polewith the help of MS nuts bolts and MS clamps-2 Nos of size 40 mm X4 mm thick with one No MCB SP 6 Amp capacity mounted on din rail inside box. work also includes making suitable hole in pole to take out connections to fitting if required at site and provisioning of 1.0 sqmm 3.0 core flexible PVC insulated copper cable from junction box to connector of street light complete all as specified and directed. |
| 18 | M&L for earthing complete with galvanized steel earth plate electrode 60cmX60cmX6mm thick buried directly in ground, earth pit not less than 2.25m deep below normal GL with top edge of the earth plate not less than 1.25m below GL connected with earth strip 32 x 6 by means of check nuts, bolts, nuts, washers of GI or steel all as shown in plate no. 3 of MES sch. Pt 0I, connected to main switch board all as specified and testing on completion including provision of earth strip protected by galvanized iron 15 mm dia light grade including all excavation, earth work, PCC, RCC cover, watering by funnel etc. complete including testing on completion complete all as specified directed |
| 19 | All as per item no 9 above but using 4 mm GI wire complete all as specifed directed. |
| 20 | Supply and erection of Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-31 (9.00 meters long) including painting of poles with two coats of aluminium paint over a coat of red oxide primer on all exposed surfaces and black bituminous paint on embedded portion and Zebra marking on pole with black paint up to one meter height above PCC coping including pasting of radium reflector band / strips (Make: 3M or equivalent) of 5cm wide in Green (02 Nos) & White (01 No.) colour shall be provided at a height of 1.25mtr from coping of pole and writing the pole number in black colour on yellow background at a suitable place on the pole including taking down existing unserviceable pole of any description complete all as specified and directed.(Note: Excavation and concrete shall be measured and paid separately). |
| 21 | Material and labour for cutting the existing bituminous road/ hard standing to size not exceeding 45 cm wide and depth not less than 45 cm for passing of UG cable through GI pipe and making good the disturbed surface filled with excavated material and top 200 mm depth with plain cement concreet 1:2:4 type C1 (using 20mm grade stone aggregate) complete all as specified and directed. |
| 22 | S&F GI pipe light grade of dia 50, mm laying in road and along with poles for cable protection complete with all fitting laid in tranches complete all as specified and directed. |
| 23 | S&F GI pipe light grade of dia 80, mm laying in road and along with poles for cable protection complete with all fitting laid in tranchescomplete all as specified and directed. |
| 24 | S&F GI pipe light grade of dia 100, mm laying in road and along with poles for cable protection complete with all fitting laid in tranchescomplete all as specified and directed. |
| 25 | Dismantling & taking down ACSR conductor of any size after taking necessary shut down for 11KV OH line by loosening the binding wires jumpers ect complete all as specified and as directed. |
| 26 | Dismantling cross-arms of M.S. channel or angle sections etc. complete and setting aside complete all as specified and directed. |
| 27 | Dismantling GI wire of size 4 sqmm etc. complete and setting aside complete all as specified and directed. |
| 28 | Dismantling insulators any type, any size setting aside complete all as specified and directed. |
| 29 | Dismantling & taking down Main Panel any size setting aside complete all as specified and directed. |
| 30 | Dismantling and Taking down Old cable of all sizes XLPE Insulated screenedPVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of all sizes complete all as specified and directed. |
| 31 | Dismantling concretepoles / struts, any size complete all as specified and directed. |
| 32 | Excavation in tenches not exceeding 1.5m wide and not exc 1.5m depth and getting out in soft/loose soil complete all as specified and as directed. |
| 33 | Excavation in tenches not exceeding 1.5m wide and exc 1.5m depth and getting out in soft/loose soil complete all as specified and as directed. |
| 34 | Returning, filling, including spreading, leveling, watering and well ramming in layers not exc. 25cmin soft/loose soil complete all as specified and as directed. |
| 35 | Removal of excavated soil to a distance not exc 50 m and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified and directed. |
| 36 | M&L for sand cushioning in trenches for cable protection including consolidation complete all as specified and directed. |
| 37 | Supplying and laying un reinforced precast concrete cable cover, Class LV, Type I, flat, size 250mm x 150mm x 40mm complete all as specified and directed. |
| 38 | M&L for PCC 1:4:8, type D2 (using 40mm graded stone aggregate) as in foundation filling and mass concrete complete all as specified and directed. |
| 39 | M&L for PCC 1:3:6, type C2 (using 40mm graded stone aggregate) as in foundation, filling and mass concrete complete all as specified and directed. |
| 40 | M&L for PCC 1:2:4 type B-0 (using 12.5 mm graded BT stone aggregate) as in bed block for hold fast or coping including necessary form work complete all as specified and directed. |