| 1 | Excavating post holes or similar holes, each not exceeding 0.5 Cum, getting out in hard/dense soil, returning, filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25 cm thick, watering, and removing surplus soil to a distance not exceeding 50m and making good surface complete all as specified and as directed. |
| 2 | M&L for PCC 1:3:6, type C2 (using 40mm graded crushed stone aggregate) as in foundation, filling and mass concrete etc. complete all as specified and as directed. |
| 3 | Material & Labour for providing and fixing stainless steel (Grade 304) railing made of hollow tubes,channels, plates etc., including welding, grinding, buffing, polishing and making curvature (where ever required) and fitting the same with necessary stainless steel nuts and bolts complete, including fixing the railing with necessary accessories & stainless steel dash fasteners, stainless steel bolts etc., of required size, on the top of floor orthe side of waist slab with suitable arrangement complete all as specified and as directed.Make:Jindal/Tata/Sail |
| 4 | S & F 50W LEDflood lightfitting with luminare made uppressure die cast aluminium housing with toughned glass and individual LED lenses complete making connection with 1.5sqmm, 3core, copper wireand suitable size of mounting bracket withclamps and nuts bolts etc, complete all as specified and as directed. Notes: (i)Light fitting shall be of PF>0.95(ii)The driver should be potted anti vibration type, IP66 should be sustain 440 volts for 2-4 hours.(iii)LM-79 and LM-80 test report for LED from NABL lab shall be submitted to AGE(I).(iv) CRI (Colour rendering index) of fixture shall be not less than 70.(v) CCT (Colour correlated temperature) of fixture shall be5700 K or more.(vi) System lumens efficiency not less than 110 LumensMake: Havells/Philips/Bajaj/CG |
| 5 | S & F single pole & neutral, DBs, 2 Ways, double door, without bus bar fixed on existing wall/ pole with necessary fixing arrangement, complete all as specified and as directed. |
| 6 | S&F MCBs, SP 6 to 32 Amps, 10 KA, \"C\" curve IS/IEC 60898-1 2002 marked fixing in DBs complete all as specified and as directed. |
| 7 | S&F 1.5Sqmm, 3 core PVC insulated& sheathed copper flexible cable black including conduit pipe complete all as specified and as directed. |
| 8 | M&L for plate earthing completewith galvanizedmild steel plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground vertically (in earth pit not less than2.25 m deep below normal ground level) with the top edge of the earth plate at a depth not less than 1.5 m below normal ground level,the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides and incl GI earth lead wire 4 mm dia or 8 SWG bolted (with GI nuts, bolts & check nuts) and earth plate electrodeat one end and connected to main switch board/ DBs etc. at the other, earth strip encased(protected) in and including 15 mm boreGIpipe medium gradewith all fittings from top of electrode to main switch board/ DBs etc fixed with and including 25 x 6mm flat iron clamps, bolts, nuts and washer and also including providing watering pipe 20mm bore GI pipe medium grade from bottom of earth pit to top of electrode complete with earth pit in PCC 1:2:4 type B-2 using 12 mm graded crushed stone aggregate, RCC cover, funnel, wire mesh including necessary excavation and earth work complete all as specified and shown in electrical plate No 3 of SSR Pt-I, complete all as specified and directed. |