| 1 | M&L for 80 mm GI pipe medium grade of length 5.0 mtr (4.5 mtr above ground & 0.5 mtr inside ground) duly grouted with PCC 1:4:8 in excavated base(exc depth will be 0.65 mtr) ,PCC 1:3:6 in foundation & PCC 1:2:4 as coping above ground (0.45 mtr) for errection of GI pole with necessary arrangement to covering top of pole with GI lid duly welded. Making holes on GI pole for provn of passing 1.5 sq mm x 3 core copper wire, fixing GI brackets by welding on pole for street light fittingmade outof 32 mm dia G.I. Pipe light grade in shape and angle as directed not exceeding 1.5 mtrs in length. Finally painting pole and bracket with onecoat of oil based aluminium paint, durable and long lasting, resistant to UV radiation and chemicals,including necessary preparation of surfaces with iron oxide primer before painting & numbering with black enamelled paint and writing TSL No on pole with white enamelled paint complete all as specified and directed . |
| 2 | Excavationin trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth and getting out in soft/ loose soil, for laying of under ground electric cable etc complete all as specified |
| 3 | Supply and lay, jointing and testing of LT cable of size 16 Sqmm 4 core XLPE insulated, armoured, heavy duty with multi stranded aluminum conductors, 1100V grade, laid in trenches / ducts / through GI pipe fixed to polecomplete all as specified and directedNote:Excavation earthwork, cable covers, sand cushioning and GI protection pipe shall be measured and paid separately. |
| 4 | Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick eachcomplete all as specified and directed |
| 5 | Removing excavated surplus soil to a distance not exceeding 50 meter and depositing where directed at a level not exceeding 1.50 meter above the starting point complete all as specified |
| 6 | M & L for river bed sand in trenches/ ducts 15 cm under cable and 8 cm above the cable for cushioning/protection to cable including spreading, leveling and get thick 18cm after hand punning complete all as specified and directed |
| 7 | Supply & laying un-reinforced precast concrete cable cover, class LV, Type 1, flat, size 250 mm x 150 mm x 40 mm abetting each other with gap between adjacent slab not exceeding10mm over for cable protection complete all as specified and directed |
| 8 | Supply and laying galvanised steel water tubing, light grade, IS-1239 marked with all fittings IS marked and laid in trenches under roads in drains, fixed to poles/walls with required size flat iron clamp bolts, nuts and washers, pipesof50 mm bore ,fixed in repair complete all as specified and as directed. |
| 9 | S&F service wire 1100 volts grade PVC insulated PVC unsheathed cable multi strandedcopper conductor of size 3 core 1.0 sqmm complete all as specified |
| 10 | M&L for Cutting under road/PCC path and passing GI pipe for cable protection and making good as existing complete all as specified and as directed. |
| 11 | Supply and fixing LED street light fitting 60/70 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver,bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified and directed |
| 12 | S&F kiosk box for luminaries, weather proof made out of PVC/HDPE /FRP housing fire retardant, non fusing, shock & rust proof, single piece molded andcover with hinged door, pole mounting type comprising of aluminum TPNbus bar of 60 Amps of minimum size 200x 140 x 95mm, fixed on pole with MS, clamps 30x5mm with necessary nuts, washer including 16 Amp MCB SP for out goining complete all as directed. Note. Rate of TPN bus bar and MS clamp inclusive in item rate |
| 13 | S&F installation alongwith complete accessories for polycarbonate dual solar traffic light polycarbonate with switching alternate and on-off provision, supply : 12Ah (12.8V DC supply lead phosphate) with 50WP solar panel alongwith MS sheet fabrication colour - Green and Red each of dia 300mm, LED 180 Number, LED 5mm ultra power LED wavelength : 600+-5nm, Lux > 300 cd, IP -65 protectioncomplying MORTH standards alongwith 4 Mtr blinker pole of 75mm outer dia MS 1.6 mm thickess with yellow powder coatingall etc complete including excavation and PCC foundation all as specified and directed |
| 14 | S&F installation alongwith complete accessories forpolycarbonate solar traffic light polycarbonate with switch on-off provision supply : 6Ah (12.8V DC supply lead phosphate) with 30WP solar panel alongwith MS sheet fabrication colour - amber of dia 300mm, LED 180 Number, LED 5mm ultra power LED wavelength : 600+-5nm, Lux > 300 cd, IP -65 protection complying MORTH standards alongwith 4 Mtr blinker pole of 75mm outer dia MS 1.6 mm thickess with yellow powder coating all etc complete including necessary excavation, PCC foundation all as specified and directed |
| 15 | Supply and laying of 3 Core 2.5 Sqmm PVC insulated round sheathed copper annealed conductor of voltage grade 1100 volts etc complete drawn through PVC conduit of size 20mm dia on ceiling/walls including saddle. |
| 16 | Taking down copper/aluminum point wiring (light, fan, socket or power) complete and including (fitting and fixture such as switches, socket ,ceiling rose ,pendent ,regulators,light fittings, etc to be measured separetaly) NOTE:- Job including for taking out old gutties,screw,nails,casing caping/conduit etcand making good to disturbed surface of wall ,floor etc including to match with the existing surface. |
| 17 | M&L for point wiring for one light/Fan/socket 5Amps point on indep boardcontrolled by one, one way switch complete with 1.5 Sqmm multi-stranded copper conductor PVC insulated, unsheathed, FRLSH cable 1100 volts grade ISI marked drawn through and including heavy duty ERW conduit not less than 20 mm dia concealed type , including all accessories like bend, tees, junction boxes etc.including 1.5 Sqmm multi-stranded copper conductor PVC insulated, unsheathed, fire retardant low smoke cable as a earth wire connected to common earth dolly complete all as specified and directed by Engr-in-charge. Note : Point wiring will be done from Main DB. Length of point wiring may be beyond 5 mtrs and no extra amount for long point wiring will be considered. |
| 18 | S&F in replacement switch flame proof rotary type with termination box in LM6, 16A, single pole 250V complete all as specified and directed |
| 19 | S& Fin repair/replacement of LED flame proof well glass in die cast aluminum housing with heat resistant toughened glass, 70watt , IP65 protected and including all accessories, connecting up with flexible copper conductor 1.5 Sqmm 3core covered with flexible metal conduit of suitable size complete all as specified and directed. |
| 20 | Taking down Exhaust fan and depositing to MES store yard all etc complete as specified and directed. |
| 21 | Supply and fix flame proof/ weather proof exhaust fan,single phase,230 volt oscillating 400mm sweep, 0.25HP motor suitable for wall mounting with louvers complete all as specified and directed. |
| 22 | S&F sub main wiring drawing through rigid PVC conduit not less than 40 mm concealed in wall/roof with four single core 6 sq mm and one run of 6 sq mm as earth wire of FRLSH stranded copper conductor PVC insulated and unsheathed cable of 1100 volts gradeall as directed |
| 23 | S&F sub main wiring drawing through rigid PVC conduit not less than 20 mm concealed in wall/roof with two single core 2.5 sq mm and one run of 2.5 sq mm as earth wire of FRLSH stranded copper conductor PVC insulated and unsheathed cable of 1100 volts gradeall as directed. |
| 24 | S&F moduler white cover plate with frame. 3 modulecomplete all as specified. |
| 25 | S&Fmoduler metal flush box 3 module.complete all as specified. |
| 26 | S&F moduler socket 6A 2/3 pin combined,2 module |
| 27 | S&F moduler switch 1 way 6A 1 modulecomplete all as specified. |
| 28 | S&F MCB DB SPN 08 ways double door with 240 Volt, 200 amps rated bus bar with all accessories flush in the wall including taking down old Unsv DBs by dissconnecting of electrical coonection any type including connection in new DBs by using flexible pipe suitable size and making good and match with theexisting surface of wall etc all as specified and directed |
| 29 | S&F triple pole and earth metallic encolsure with a three pin and earth plug with socket complete with one triple pole MCB 32 amps, 415 volt completeall as specified and directed |
| 30 | S&FMCB4 pole 40 amp 415 volts 10 KA, C curve , complete all as specified and directed. |
| 31 | S&FMCB 16 amps single pole 240 Volts 10 KA, B curve, complete all as specified and directed. |
| 32 | S&F MCCB4 pole 63 amp 415 volts 36 KA, to be fixed on existing LT panel with all accessories complete all as specified and directed. |
| 33 | M & L for earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground vertically (earth pit not less than 2.25m deep below ground level) with top edge of the plate not less than 1.50 mtr deep below normal ground level, connecting to GI strip of size 32 x 6 mmby means of bolts, nuts, check nuts, and washers of galvanized iron or steel including 40 mm dia light grade protection pipe for earth strip complete with charcoal and common salt including watering arrangement with galvanized iron pipe light grade 20 mm dia, PCC Chamber, CI frame and cover, MS funnel with wire mesh all as shown in electrical plate no 3 of SSR part I including excavation and earthwork in any type ofsoil/strata and testing on completion. Note:- GI strip of size 32 x 6 mmand 40 mm dia GI light grade protection pipe upto 7.5 mtr from earth plate is deemed to be included in rate quoted. |
| 34 | M&L for chemical earthing of copper earth plate of size 90 x 60cm x 5mm ,as earth electrode burried directly in ground earth pit not less than 2.25 mtr deep below ground level using 32 x 6 mm copper strip as as earth lead up to 7.5 mtr long fixed by means of bolts, nuts, check nuts and washers or brazing etc. of galvanised iron or steelincluding provn of GI protectionpipe light grade of 40mm bore and connected to earth strip earthing test point all as shown in electrical plate No.5 of SSR Part-I 2009 and as specified or indicatedand testing on completion including necessary excavation & earthwork in any type of soil, PCC (1:3:6) type C1 chamber, precast slab 50mm thick in cement concrete (1:2:4)type B1 (reinforced with welded steel wire fabric (XPM) of weight not less than 4kg/sqm) with frame, funnel with watering pipe of 15mm bore medium grade, wire mesh and lugs, test point including salt (150KG), Coal dust(100KG) & Magnesium sulphate (150KG) including refilling of earth pit with cultivated soil and removal of surplus soil upto 50mtrs apart etc. complete all as directed by EIC. Note: Copper strip exceeding 7.5m long shall be measured & paid separately.The earth resistance value less than 1 ohm.Failing to achieve the value the contractor shall be re do the earthing without any extra cost. |
| 35 | Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required copper strip 20 mm x 3 mm complete all as specified and directed |
| 36 | Excavation in trenches not exc 1.5 mtr wide and not exc 1.5 mtr in depth for foundation and getting out in soft disintegrated rock complete all as specified and directed |
| 37 | M&L for plain cement concrete (1:4:8) type D2 (using 40mm graded stone aggregate as in foundation,filling and mass concrete all as specified and directed. |
| 38 | M&L sand filling incl spreading levelling, well ramming in layers n exc 25 mm thick incl consolidation by machenical vibrator. |
| 39 | Supplying and laying 400 micron thick HDPE sheet (Virgin Quality) water proof, wrinkle free without puncture having minimum weight 390 gm/Sqm over tack coat/sand cushion as specified in the design with overlap between adjacent strips and at transverse joints as minimum 300mm. |
| 40 | S&F of lnsulated PVC Wall Lining consisting of PVC Insulated Panels having expanded polystyrene (EPS) of 40mm thick stuck to 2mm thick plain colour PVC sheet duly fitted into the wall as per specifications and drawing all as specified and as directed by engr-in-charge. |
| 41 | M&L for RCC (Nominalmix)TypeB1 1:2:4(20mm graded aggregate) for Foundations, including rafts, footings, foundation beams; plinth beams; bases for columns, etc.; basement slabs, under-reamed piles and mass concrete all as specified and directed. |
| 42 | M&L for TMT mild steel bars 10mm dia and over cut to length,bent to shape required and binding with mild steel wire(annealed) not less than 0.9mm dia complete all as specified and as directed. |
| 43 | M&L for Cement concrete(Type B1 1:2:4) 20mm graded aggregate in foundations, filling and mass concrete complete all as specified and directed |
| 44 | M&L forForm workfor fair finished surfaces of concrete measured flat for walls complete all as specified and directed |
| 45 | M & L for cement concrete type B0 1:2:4 (12.5 mm graded agg) 25mm thick as in sub floors complete all as specified and directed |
| 46 | M&L for non skid ceramic coloured tiles 7to 8mm thick (square/rectangular) area of each tile exceeding 0.11sqm and n exc 0.18sqm in floors etc set and jointed in neat cement slurry and pointed in white or coloured cement to match and over and including 15 mm thick screed bed in cm 1:6 for complete all as specified. |
| 47 | Surface excavation n.exc (not exceeding) 30 cm deep and averaging 15cm deep and getting out in soft / loose soil complete all as specified. |
| 48 | M L for Hardcore of Broken stone/boulders gauge n exc. 63mm, deposited, spread & levelled in layers n exc. 15 cm thick, watered & rammed to a true surface complete all as specified and directed |
| 49 | M&L for 100 mm thick cement concrete type C- 2, 1:4:8 (40mm graded aggregate) in sub-floors, sub-bases, floors and pavings etc complete all as specified and directed |
| 50 | M&L sand filling incl spreading levelling, well ramming in layers n exc 25 mm thick incl consolidation by machenical vibrator complete all as specified and directed |
| 51 | M&L for machine pressed precast concrete interlocking paver block of approved shape and size of 60mm thickness, with minimum compressive strength of 35N/sqm (M-35 ), withoutcorrection factor for chamfering, made in rubber moulds with 0.50mm thick scratch proof lacquer coating on top surface, with white cement and pigment laid over sand screed bed complete. |
| 52 | M&L Cement Concrete Type B1 1:2:4(12.5mm grade aggregate ) in Copings,,kneelers,apex stons,Kerbs etc including weathering,slightly rounded or chamfered angles and throating,as directed.. |
| 53 | Removing excavated soil /disintegrated rock to a distance exc. 1000 mtr but n. Exc. 1.5 Km and deposited where directed at a level not exc. 1.5 m above the starting point complete all as specified and directed. |
| 54 | S&F for Anodised aluminium powder coated frame for doors, windows, partition, ventilators with one or more rebatescluding joining cleat for fixing Powder Coating to (minimum thickness of powder coating 50 micron) etc. complete all as specified |
| 55 | 529S&F for anodised aluminium powder coated (minimum 50 micron thickness) double leafdoor shutterglazed with 5.0mm thick tinted glass grade including rubber bead, joining cleat for fixing, aluminium door handle 150mm size and tower bolt 200mm size, mortice lock vertical type of mild steel 4 levers of size 100mm etc as mentioned here in below complete all as specified and as directed:-(a) Vertical members of shutter Section-85.00 x 44.45 x 2.00 mm (Section No 19560)(b) Top Members of shutter Section - 83.50 x 44.45 x 2.00mm (Section No 19581)(c) Lock rail (middle member) of shutter Section - 150.00 x 44.45 x 3.00 mm (Section No. 19596)(d) Bottom Members of shutter Section - 150.00 x 44.45 x 3.10mm(Section No. 19584)(e) Glazing clip for securing glass - 0.80 mm thick (Section No. 19370).Note:- Section No. given above are of make Jindal, Contractor may use similar section of other make mention in Appx A. Make:- Make of aluminium section : Jindal/ INDAL/ Hindalco as approved by GE. |
| 56 | S&F for 5.0 mm thick tinted glassof selected qualityfixed to aluminumframing incudingrubber beadingall as specified |
| 57 | S&F for 18/19mm thick pre-laminated particle board, inerior grade, prelaminaed both sides with decorative choice laminations one side wih decorative choice laminaion & other side balancing white lamination lamination & other side balancing white lamination, fixed with screws to timber frame complete all as specified and directed |
| 58 | S&Faluminium (Die cast) body, door closer hydraulically regulated designation No-1, universal type, suitable for door shutters of weight not more than 35 kg complete all as specified and directed. |