| 1 | Rewinding of the armature for 125 KVA Alternator armature (Stator) completely, as per the original gauge of super enamelled winding wire (\"Class F\" insulation), after removing the burnt out winding from EA set ( including buying back the burnt wire), replacing the AVR, transportation to work shop at Sri Vijaya Puram and back to site i/c heat varnishing and baking, loading & unloading after rewinding, degreasing, replacement of other necessary items etc, alignment with the engine, recoupling after rewinding,testing on load complete as reqd. (Winding wire shall be of BIC/Khaitan make, paper insulation of Krempel/womex/Phillips, varnish of Dr.Beck.) |
| 2 | Shifting of 125 KVA DG set from the front portion of Telephone Bhawan to BSNL bhawan, i/c loading and unloading by mechanical mode, transportation and handling charge, and placing at the designated location as per the direction of EIC, complete as reqd. |
| 3 | Jointing copper / G.I. tape (with another copper/ G I tape, base of the finial or any other metallic object) by riveting / nut bolting/ sweating and soldering etc as required. |
| 4 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from existing electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 5 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required |
| 6 | Supplying of PVC insulated and sheathed armoured 2 core 1.5 sq.mm copper conductor 1.1 KV grade cable and laying the same on surface or in recess as reqd.(BSNL approved make). |
| 7 | Supplying and making end termination with brass compression gland for PVC insulated and sheathed copper conductor cable of 1.1 KV grade of size 2 core 1.5 sq.mm as reqd. |
| 8 | Supplying and making end termination with brass compression gland for PVC insulated and sheathed Alluminium conductor cable of 1.1 KV grade of size 3½ x 95 sq.mm Al as reqd. |
| 9 | Supply and delivery of PVC insulated and sheathed armoured 3½ x 95 sq.mm Al. armouredconductor, 1.1 KV grade cable as reqd.(ISI marked). |
| 10 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL/PVC pipe as required. (i) 50 sq.mm) |
| 11 | Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching by breaking the concrete and re-filling/making goodetc as required(40 mm) |
| 12 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required ( 50 sq. mm (clamped with 35x5mm MS flat clamp) |
| 13 | Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete ( In excess of dismantled shed) |
| 14 | Providing and fixing precoated galvanised iron profile sheets (size, shape and pitch of corrugation as approved by Engineer-in-charge)0.50 mm + 0.05 %, total coated thickness with zinc coating 120 gsm as per IS: 277 in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns. Sheet should have protective guard film of 25 microns minimum to avoid scratches while transportation and should be supplied in single length upto 12metre or as desired by Engineer-in-charge. The sheet shall be fixed using self drilling /self tapping screws of size (5.5x 55mm) with EPDM seal, complete upto any pitch in horizontal/ vertical or curved surfaces excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required. ( In excess of dismantled shed) |
| 15 | Excavation for foundation in soft soil including dressing of sides and ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 metres. |
| 16 | Providing and laying in position cement concrete 1:3:6 (1 cement: 2 coarse sand : 6 graded stone aggregate 40 mm nominal size) in foundation of pump, DG set etc including form work etc as required. |
| 17 | Providing and laying in position cement concrete 1:2:4 (1 cement: 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc including form work etc as required. |
| 18 | Providing 15 mm thick cement plaster of mix 1:4 (1 cement : 4 fine sand) at all levels. |
| 19 | Supplying and fixingof 12V, 150AH, lead acid battery, heavy duty with connector and clip, complete as reqd. |
| 20 | Servicing of 125 KVA DEA set( Kirloskar make engine ,6R1080TA Type)thoroughly by replacing B-Check Kits such as spinon lub oil filter ( 06.436.01.0.00)-2nos, Fuel filter elemen primary ( 3H.131.01.0.00)-1No. , Fuel filter element secondary ( 3H.132.02.0.00-1No., Primary air filter element ( +611.411.02.0.00)-1No., V belt cogged Bx-48 ( 47.305.01.0.00)-2Nos,V belt XPA 1250 cogged ( 4H.069.01.0.00)-1No., Line voltage relay ( 38.148.25.6.00)-1 No. after flushing the sump after dismantling, checking of alignment and adjustment of different components like valve, tappet, replacing the head gasket, and assembling the engine parts i/c S/F of nuts & bolts, washers, spring washers, etc if required , testing, checking and commissioning, complete as reqd. |
| 21 | Supplying and pouring mobil oil of 15-W -40 grade in the E/A set complete as reqd. (Castrol/Indian Oil or SS) |
| 22 | Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade: Two or more coats on over an under coat of paint of approved brand and manufacture, suitableshade withordinarypaint of approved brand and manufacture. |
| 23 | Supplying and fixing of following module, PVC enclosure along with modular base & cover plate for modular switch in recessetc as required (a) 3 module |
| 24 | Supplying and fixing following accessories in the existing Modular enclosure including connections etc as required a) 6/10 A 1 way modular switch |
| 25 | b) 10 A modular Socket Outlet |