| 1 | Dismantling ACSR or AAC Conductors from the disturbed span including line spacer, etc., complete all as specified and as directed by Engineer-in-charge. |
| 2 | Dismantling Cross-Arms of Mild Steel Channel or Angle Sections, etc, including Mild Steel Bolts, Nuts, Washers, etc., complete all as specified and as directed by Engineer-in-charge. |
| 3 | Dismantling Insulators like Pin type, Shackle type from existing Street/ Security Light Pole of any description and any size, seggregating Seviceable Insulators and keep in safe custody for re-use, complete all as specified and as directed by Engineer-in-charge. |
| 4 | Dismantling stay assembly of any description and any size including MS clamps with nut-bolt-washers, demolition of Cement Concrete (as/if required) and made good disturbed Ground, complete all as specified and as directed by Engineer-in-charge. NOTE: Unserviceable stay assembly will be dismantled at Ground Level and disturbed ground will made good as directed for which Earthwork, demolition of Cement Concrete, etc. will not be measured and paid separately. |
| 5 | Excavation in trenches n.exc 1.5m wide and n.exc 1.5 m in depth for foundation etc or for shafts, wells, cesspits, manholes, pier holes etc. and getting out in soft/loose soil complete all as per specified and as directed by Engineer-in-charge. |
| 6 | Returning,filling in, including spreading, leveling, watering and well ramming in layers n exc 25cm complete all as per specified and as directed by Engineer-in-charge. |
| 7 | Removing excavated material not exc. 50 m & depositing where directed at a level not exc. 1.5 m above starting point complete all as per specified and as directed by Engineer-in-charge. |
| 8 | M&L for Sand Cushioning (dry) in trenches/ducts for protection of UG Cables (below, above and around the UG Cable laid in Trenches) of 230mm Spread thickness (8 Cm in depth before laying the Cable and 15 Cm in depth after laying the Cable) and consolidated (punned) upto 180mm thickness, complete all as per specified and as directed by Engineer-in-charge.NOTE : For the purpose of Payment, Punned thickness of Sand Cushioning only will be measured and paid for. |
| 9 | Supply & Laying Fly ash Bricks, well burnt, laid breadth wise along the length of cable laid in trenches over sand cushion laid for UG cable protection, complete all as specified and as directed by Engineer-in-charge. |
| 10 | S&F of Galvanised Iron Pipe 50mm bore (dia) ‘light grade’ for protection of UG Cable, laid under Floors or Road Crossing, fixing to Pole with and including Mild Steel Clamps, Nuts, Bolts, etc., complete all as specified and as directed by Engineer-in-charge. |
| 11 | All as per Item No. 10 here-in-above, but for 80mm bore (dia) pipe, complete all as specified and as directed by Engineer-in-charge. |
| 12 | M&L for cutting existing bituminous road/hard standing not exc 60x90cm in wide & depth getting out excavated material for laying cable/GI tube, returning filling, sand filling of 45cm & well rammaing watering, finishing suraface of depth not less than 25 cm from top using PCC 1:2:4, type B-1 (using 20mm graded aggregate); including removal of surplus soil complete all as specified and as directed by engineer-in-charge. |
| 13 | Supply & laying of LT XLPE insulated cable, sheathed, screened, PVC bedded, Galvanised Steel Strip or Wire armoured, Electic Power Cable (heavy duty) with Aluminium Conductor, 1100 Volts grade, cross-sectional area 400 Sqmm 3½ Core, laid in Pipe/ Ducts/Trenches/ under Floor/ under Road/ fixing on pole/ above floor including Testing, complete all as specified and as directed by Engineer-in-charge. NOTE : Earthworks, Sand Cushioning, Bricks, GI Pipe, etc. will be measured and paid under appropriate Items. |
| 14 | All as per Item No. 13 here-in-above, but for cross-sectional area 240 Sqmm 3½ Core, complete all as specified and as directed by Engineer-in-charge. |
| 15 | All as per Item No. 13 here-in-above, but for cross-sectional area 185 Sqmm 3½ Core, complete all as specified and as directed by Engineer-in-charge. |
| 16 | All as per Item No. 13 here-in-above, but for cross-sectional area 150 Sqmm 3½ Core, complete all as specified and as directed by Engineer-in-charge. |
| 17 | All as per Item No. 13 here-in-above, but for cross-sectional area 120 Sqmm 3½ Core, complete all as specified and as directed by Engineer-in-charge. |
| 18 | All as per Item No. 13 here-in-above, but for cross-sectional area 95 Sqmm 3½ Core, complete all as specified and as directed by Engineer-in-charge. |
| 19 | All as per Item No. 13 here-in-above, but for cross-sectional area 70 Sqmm 3½ Core, complete all as specified and as directed by Engineer-in-charge. |
| 20 | All as per Item No. 13 here-in-above, but for cross-sectional area 50 Sqmm 3½ Core, complete all as specified and as directed by Engineer-in-charge. |
| 21 | All as per Item No. 13 here-in-above, but for cross-sectional area 35 Sqmm 3½ Core, complete all as specified and as directed by Engineer-in-charge. |
| 22 | All as per Item No. 13 here-in-above, but for cross-sectional area 10 Sqmm 4 Core, complete all as specified and as directed by Engineer-in-charge. |
| 23 | All as per Item No. 13 here-in-above, but for cross-sectional area 10 Sqmm 2 Core, complete all as specified and as directed by Engineer-in-charge. |
| 24 | M&L for PVC insulated Multistranded Copper Conductor flexible cable of3 Core 4 Sq mmsize drawn through steel tubular poles for interconnection of cable looping box to street light Fitting, Post Top Lantern &etc., complete all as specified and as directed by Engineer-in-charge. |
| 25 | S&F of Pole Box/Junction Box of size 130 X 180 X 77mm (LxBxH) made out of Polycarbonate material totally enclosed, dust and vermin proof, door pasted with rubber gasket, water tight IP 66/67 protection single leaf shutter in front having proper locking arrangements, mounted on security light pole with suitable clamps (GI Flat iron of 25x3mm), nuts, bolts, complete all as specified and directed by Engineer-in-charge. |
| 26 | S&F of Pole Box/Junction Box of size 130 X 130 X 77mm (LxBxH) made out of Polycarbonate material totally enclosed, dust and vermin proof, door pasted with rubber gasket, water tight IP 66/67 protection single leaf shutter in front having proper locking arrangements, mounted on security light pole with suitable clamps (GI Flat iron of 25x3mm), nuts, bolts, complete all as specified and directed by Engineer-in-charge. |
| 27 | Supply, installation, testing and commissioning of Factory made (CPRI Approved) floor mounted Outdoor cubical type LT Feeder pillar box with raised projected sloped canopy of size 1000 X 700 X 450 MM fabricated out of 3.15 mm thick CRCA Sheet and angle iron 50 X 50 X 6 mm frame totally enclosed dust and vermin proof both side hinge opening arrangement on front and back, centre openable double door with locking arrangements, cable entry andexit from bottom with cable glands and gaskets, earth strip connections, Digital VAF Meter- 01 Set (Make- L&T/ Schneider/ Legrand/ Siemens), including LED indicating lamps- 03 Nos (Make- L&T/ Schneider/ Legrand/ Siemens), internal wiring of suitable size to be used for incoming and outgoing connection of all switches/MCCB\"s & Bus-bar. The TPN aluminium bus bars of capacity 200 Amps shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on DMC/epoxy insulator, connected with Aluminium lugs, including powder coat painting (RAL-7032) on the surfaces externally & internallyincluding necessary preparation of surfaces and providing PCC (1 : 3 : 6) type C-2 as in foundation all as specified and as directed, comprising of the following :-(a) Internal wiring with single core copper conductor cable/ PVC Insulated Copper Strip of suitable size incoming to bus bar and bus bar to outgoing MCCB/MCB-1Job.(b) Fine wiring with single core copper conductor cable for instruments/indicating lamps-1 Job. (c) Bus bar chamber comprising 04 Nos aluminium strip bus bar mounted on DMC ( Dough Moulding Compound) insulator and PVC sheathed of capacity 200 Amps with colour coding for RYB & N - 01 SetINCOMING(d)MCCB125 Amp, 4 Pole , 415 Volts rating with, overload, short circuitfault protection 3 phase with neutral link specially fixed incoming supply (Breaking capacity 36KA)Ics=100% of Icu, with Spreader terminal of both side-01 No.OUT GOING(e) MCCB63 Amp, 4 Pole , 415 Volts rating with, overload, short circuitfault protection 3 phase with neutral link specially fixed out going supply (Breaking capacity 25KA)Ics=100% of Icu, with Spreader terminal of both side-01 No.(f)MCCB40 Amp, 4 Pole , 415 Volts rating with, overload, short circuitfault protection 3 phase with neutral link specially fixed out going supply (Breaking capacity 25KA)Ics=100% of Icu, with Spreader terminal of both side-02 Nos.(g)MCB Four Pole (FP) 32 Amp, 415 Volts rating specially fixed out going supply (Breaking capacity 10KA)-02 Nos.(h) Analog time switch of type 3 module- 01 No. (Note-Fixing arrangement diagram and line diagram of the panel shall be got approved by accepting officer before panel fabrication). |
| 28 | Supply, installation, testing and commissioning of Factory made (CPRI Approved) floor mounted Outdoor cubical type LT Feeder pillar box with raised projected sloped canopy of size 1200 X 800 X 450 MM fabricated out of 3.15 mm thick CRCA Sheet and angle iron 50 X 50 X 6 mm frame totally enclosed dust and vermin proof both side hinge opening arrangement on front and back, centre openable double door with locking arrangements, cable entry andexit from bottom with cable glands and gaskets, earth strip connections, Digital VAF Meter- 01 Set (Make- L&T/ Schneider/ Legrand/ Siemens), including LED indicating lamps- 03 Nos (Make- L&T/ Schneider/ Legrand/ Siemens), internal wiring of suitable size to be used for incoming and outgoing connection of all switches/MCCB\"s & Bus-bar. The TPN aluminium bus bars of capacity 400 Amps shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on DMC/epoxy insulator, connected with Aluminium lugs, including powder coat painting (RAL-7032) on the surfaces externally & internallyincluding necessary preparation of surfaces and providing PCC (1 : 3 : 6) type C-2 as in foundation all as specified and as directed, comprising of the following :-(a) Internal wiring with single core copper conductor cable/ PVC Insulated Copper Strip of suitable size incoming to bus bar and bus bar to outgoing MCCB/MCB-1Job.(b) Fine wiring with single core copper conductor cable for instruments/indicating lamps-1 Job. (c) Bus bar chamber comprising 04 Nos aluminium strip bus bar mounted on DMC ( Dough Moulding Compound) insulator and PVC sheathed of capacity 400 Amps with colour coding for RYB & N - 01 SetINCOMING(d)MCCB250 Amp, 4 Pole , 415 Volts rating with, overload, short circuitfault protection 3 phase with neutral link specially fixed incoming supply (Breaking capacity 36KA)Ics=100% of Icu, with Spreader terminal of both side-01 No.OUT GOING(e) MCCB125 Amp, 4 Pole , 415 Volts rating with, overload, short circuitfault protection 3 phase with neutral link specially fixed out going supply (Breaking capacity 25KA)Ics=100% of Icu, with Spreader terminal of both side-01 No.(f)MCCB100 Amp, 4 Pole , 415 Volts rating with, overload, short circuitfault protection 3 phase with neutral link specially fixed out going supply (Breaking capacity 25KA)Ics=100% of Icu, with Spreader terminal of both side-01 No.(g) MCCB63 Amp, 4 Pole , 415 Volts rating with, overload, short circuitfault protection 3 phase with neutral link specially fixed out going supply (Breaking capacity 25KA)Ics=100% of Icu, with Spreader terminal of both side-02 Nos.(h)MCCB40 Amp, 4 Pole , 415 Volts rating with, overload, short circuitfault protection 3 phase with neutral link specially fixed out going supply (Breaking capacity 25KA)Ics=100% of Icu, with Spreader terminal of both side-02 Nos. (j)MCB Four Pole (FP) 32 Amp, 415 Volts rating specially fixed out going supply (Breaking capacity 10KA)-01 No. (Note-Fixing arrangement diagram and line diagram of the panel shall be got approved by accepting officer before panel fabrication). |
| 29 | Supply, installation, commission and testing of Factory made Out door cubical type LT Bus-bar chamber of 800x500x1000mm with 4 nos 40x8mm aluminium strip bus-bar, suitable for 3 Phase, padestal mounted (height of padestal 1500mm above floor level) totally enclosed weather, dust and vermin proof (Protection Class IP-54) made out of not less than 45 X 45 X 6 mm angle iron frame with cable entry exit through bottom with double compression copper stainless steel cable glands and gaskets and 3.15 mm thick MS CRCA sheet front and back openable door with proper hinge and locking arrangements, painted externally and internally with powder coat painting (RAL-7032) of gray colour after necessary preparation of surfaces incl. necessary PCC (1:3:6) type C-2 as in foundation all as specified and as directed, comprising of the following :-(a) Internal wiring with copper conductor cable of suitable size-1Job.(b) Bus-bar shall be insulated with colour codes/ Sleeves/ Taps. |
| 30 | M&L for earthing completewith galvanisedsteelearth plateelectrode of size 600 mm x 600 mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of the plate not less than 1.5 mtr below ground level, connected to galvanized earth lead of 32x6 mm by means of bolts nuts check nuts & washers of galvanized iron or steel , procteded by GI pipe 40 mm bore( light grade)and watering pipe 20 mm bore GI pipe(med grade) andchamber and coping shall be in PCC 1:3:6 type C1 using 20mm graded stone agg.50 mm thick cover of RCC 1:2:4 type B1 using 20 mm graded stone agg. reinforced with 8 mm dia MS tor bar @ 80 mm c/c both ways including excvation and earth work and removal of surplus soil complete all as shown in electrical plate no 3 of SSR PT 1, 1991 with charcoal dust and saltcomplete and earth leadconnected to earthing test point (up to main switches, DBs), complete all as specified & testing on completion. NOTE:-(i)item includes the cost of 1.5 mtr length GI pipe for protection for GI earth lead.(ii) item rates includes the cost of 7.5 mtr GI earth lead. |
| 31 | All as per Item No 30 here-in-above, but for 4mm dia GI wire earth strip procteded by GI pipe 15 mm bore( light grade), complete all as specified and as directed by engineer-in-charge. |