| 1 | M & L for Routine servicing of DG set including Engine, alternator, electric panel board connection to DG set as per OEM check list & maintaining proper records of the same and submit to Engineer-in-charge after every maintainance. Repair and labour cost of item is included in quoted rates and replacement of new items/parts will be measured and paid seperatly under relevant items for DG set of following capacities and located at various loactions :-(a) 63 KVA |
| 2 | (b) 125 KVA |
| 3 | (c) 200 KVA |
| 4 | (d) 250KVA |
| 5 | (e) 380 KVA |
| 6 | (f) 500 KVA |
| 7 | (g) 625 KVAServicing of the DG set should be followed as per the instructions given under:Checking and rectifyng of (i)Battery charging system , level up Electrolite and specific gravity. (ii) Leakage in fuel lines & connections of fuel pump.(iii) Leakage of Lub. Oil and cooling system, hose pipe & connection, belts tension, fan hub drive pully and water pump and cleaning of water separation and cooling system. (iv) condensate trap. Repair of leakage/ maintenance of water cooling system. Cleaning of radiator by draining out of Coolent, checking of all hose pipes, nut & bolts and tightening properly including checking of leakages all as directed by Engr – in – Charge.(v) Reset the complete switches in automatic lighting connection. (vi) Cleaning of complete D G Set, check and tightening of all nut & bolts including replacement of U/S parts , oiling/ greasing of all movable parts and unusual vibration.(vii) Leakage in exhaust system and exhaust restriction, drain out condensate trap. Repair of leakage/ maintenance of water cooling system. checking of all hose pipes, nut & bolts and tightening properly including checking of leakages all as directed by Engr – in – Charge. (viii) Check all electrical connection of alternator and control wiring(ix) Check all earthing connection of DG Set, repair the same if required (x) Drain out old used engine oil from the DG Set cleaning the sump Properly including opening of “B” check kit.Filling of Engine Oil 20W40 oras recommended by the manufacturer, Qty of Engine Oil is specified sepeartly.(xi) Opening of all filters such as diesel filters, oil filters, Air filter and other required items. proper cleaing of the items and reinstalling or replace the same if required. ( xii) Testing the D G Sets after completion of work. (xiii)Contractor shall employ skilled labour (FGM) for the above repairs. All the complaints arised should be attendedand solved on the same day within one hour by one company engineer/ technician for over all repairs.Note:- Replacement of required spare parts will be measured and paid separately |
| 8 | M & L for the following spare partsfor DG Sets of capacity 380 to 625 KVA (a) Fuel flow filter with ring including screen filter. |
| 9 | (b) Oilfilter. |
| 10 | M & L for the following spare parts of D G Sets of capacity 200 to 250 kVA(a)Fuel flow filter with ring including screen filter. |
| 11 | (b) Oilfilter. |
| 12 | M & L for the following spare parts of D G Sets of capacity 63 to 125 kVA (a)Fuel flow filter with ring including screen filter |
| 13 | (b) Oilfilter. |
| 14 | Supply and filling of superior grade engine oil 20W40 for DG set topping .Make:BPCL/HP/Indian oil |
| 15 | S&F (in repairs) solenoid coil suitable for DG set of capacity 63 to 250 KVA self starter all as per directions of engineer-in-charge |
| 16 | S&F (in repairs) solenoid coil suitable for DG set of capacity 380 to 630 KVA self starter all as per directions of engineer-in-charge |
| 17 | Supply & filling only coolent \"K\" Cool Super plus 50-50 Premix for radiator of water cooled engines of any make/capacity and as per manufacturers recommendation, all as specified and directed. |
| 18 | Supply and topup / replace distilled water for battery or radiator of engine used with coolent \"K\" Cool Super plus 50-50 Premix all as specified and directed. |
| 19 | Dismantling unserviceable battery charging dynamo from DG set of rating 1 x 12 / 2 x 12 Volts complete repairs and servicing including replacement of bushes, bearings, Carbon brushes, rectifires, rewinding of field magnet coil / rotor armeture coils and any other minor parts required all as directed and fixing on engine testing/commissioning complete for DG set having any capacity.Note :Replacement of rotor armeture coil if reqd shall be measured and paid seperately. |
| 20 | Dismantling self starter 12V/24 V of DG set for repairing the starter by replacing carbon brushes, brush holder, bearings, solenoid coil, replacement of burnt aremeture, rewinding of Fd coils, replace of pinion gears etc, completer servicing and refixing after repair, testing/commissioning complete for DG Set any capacity |
| 21 | S&F (in repairs) armature coil complete with shaft suitable for DG set self starter all as per directions of engineer-in-charge |
| 22 | S&F (in repairs) pinion gear suitable for DG set self starter. all as per directions of engineer-in-charge |
| 23 | Dismantling old unserviceable battery charging dynamo of rating 12/24 volts and supply and fixing new battery charging dynomo same as per existing model suitable for fixing on DG set, 1500 rpmincluding testing after complete installation all as directed and specified. Make-LUCAS TVS or as exiting make to suit DG set all as specified and directed by engineer-in charge |
| 24 | Dismantling old unserviceable Self starter of Disel engine and supply and fixing new self starter of working voltage 12 volt/24 Volt DC and same as per existing model suitable for fixing on engine set including testing after complete installation all as directed and specified. |
| 25 | S&F and replace \"V\" belt ribbed of (a) radiator fan belt, (b) battery charging dynomo belt, and (c) water pump belt all suitable for any type of DG Sets.63 KVA to 200 KVA |
| 26 | Removing existing defective wring of DG set control panel, rewiring with mulitstrated single core PVC insulated copper conductor wire suitable and existing size for AC/DC supply connections to all control system, ECM and devices including replacement of all existing sensors such as oil pressure sensor, coolant temperature sensor, engine speed sensor, fuel level sensor intake air temperature and pressure sensor and replace ment of AMF contoller with LCD display to monitor multiple parameters, universal compatibility, button lay out with labelled terminals and self start function and installation kit with silicone gasket for sealing and detailed installation manual for settings all as including all control wiring all as specified and directed. |
| 27 | Removing existing defective wring of DG set AMF panel, rewiring with mulitstrated single core PVC insulated copper conductor wire, 1.5 sqmm for AC/DC supply connections to all control system and devices and testing of AMFpanel after complete repair all as specified and directed. (Note : Unserviceable spare like power contactor, auxilary contactor, Digital meters, relays, indication lamps, KWH meters, rotary selector switches etc shall be measured and paid separately under relavant items. |
| 28 | S&F in repairs EC2 AMF logic relays, suitable for DG set of any capacity AMF panel board. all as per directions of engineer-in-charge |
| 29 | Supply & fix in repairs AVR Chipset Suitable for DG set alternator of any capacity make and model all asper exiting sample |
| 30 | S&F in repairs Indicating lamps, 230 volt, AC, LED type suitable for DG set AMF/LT panel board. |
| 31 | S&F in repairs overload relay 10Amp to 80 Amp suitable for AMF/LT panel board. As per existing sample and as per directions of engineer-in-charge |
| 32 | S&F in repairs rotary switch suitable for selection between auto and manual modes 3 pole, 3 way suitable for DG set AMF panel board all as per directions of engineer-in-charge |
| 33 | Supply and fixing 240V, 10 KA \"B\" curve miniature circuit breaker (MCB) of single poles and current carrying capacity 5 to 32 AMP Complete with connection all as specified. |
| 34 | S&F in repairs ON/OFF switch, single pole suitable for DG set AMF panel board all as per existing sample and as per directions of engineer-in-charge |
| 35 | Supply& fix in repairs SMPS automatic battery charger 12/24voltsuitable for DG set AMF panel board all as per existing sample and as per directions of engineer-in-charge |
| 36 | Supply & fix in repairsVMR protection device 3 phase, 415V suitable for DG set AMF panel board all as per existing sample and as per directions of engineer-in-charge |
| 37 | S&F in repairs multifunction AMF panel control meter as per existing make provided in AMF panel board all as per existing sample and as per directions of engineer-in-charge |
| 38 | S&F in repair water body suitable for genset of capacity63 -200 KVA all as per existing make as per OEM specisifictaions . Dismantling of unserv water body & fixing new water body along with filling of coolant as required all as per directions of Engineer - in-charge. Note: coolant shall be measured & paid sepeartly. |
| 39 | S&F and replace \"V\" belt ribbed of (a) radiator fan belt, (b) battery charging dynomo belt, and (c) water pump belt all suitable for any type of DG Sets.250 KVA to 625 KVA |
| 40 | S&F in repair water body suitable for genset of capacity200 - 625 KVA all as per existing make as per OEM specisifictaions . Dismantling of unserv water body & fixing new water body along with filling of coolant as required all as per directions of Engineer - in-charge. Note: coolant shall be measured & paid sepeartly. |
| 41 | M&L for draining out coolent water from radiator, dismantling radiator, repair of radiator for leakage if any, cleaning the radiator set with dilute HCL, kerosin, fresh water and refixing the same with new rubber hose with clamps filling with coolent with distilled water and checking for its proper function on DG set all as directed and specified. Note : Coolent and distilled water shall be measured and paid separately under relavant items. |
| 42 | Supply and fix in replacement battery lead length not less than 1.25 Mtr long and not more than 2.5 mtr as per connection requiremnt of each DG set, PVC insulated multistranded copper conductor 70 sqmm single core, duly fixed brass clamps, copper lugs for connections from DG battery to self starter on DG Sets of any capacity . |
| 43 | Labour only for attending breakdowns of DG sets/AMF panels through skilled technician from reputed service centre of DG sets with necessary tool kits, checking Engine and alternator for defects, carryout necessary repairs works to rectify the defects without major overhauling/opening of Engine or Alternators, replace of external spare to repair/rectify the defects and testing DG set for its smooth functioning on full load all as specified and directed by Engr-in-charge. Note :1.Necessary spares required to rectify the defects shall be measured and paid separately under relavant items.2.The complaint shall be attended and rectifed within 24 hrs form time of reporting by Engr-in-Charge or his auth representative.3. Any Major defects shall be reported on Priority to Engr-in-charge to avoid undue delay in fuctioning of installation. |
| 44 | Replacement of control card of AMF panel with defective controllermodel and type as per existing to DG set of any capacity all as per existing sample and as per directions of engineer-in-charge |
| 45 | Dismantling of ACB of various capacity from the panel and opening the same and servicing the ACB and refixing of the ACB includingreplacemnet of ACB closing/opening coils all as per directions of engineer-in-charge. |
| 46 | Dismantling of mannual fuel pump of DG set any capacity and taking the same to reputed workshop and reparing the same for any defects and refixing the same onto dgset all as directed by engineer-in-charge |
| 47 | S & F Replacement of electronics/manual speed governer of the dgset of any capacity existing type and size and model all as specified and direction of engineer-in-charge |
| 48 | S&F in replacement of moving contact & fixing contact set of contactor capacity 250 to 400 Amp |
| 49 | S&F in replacement of moving contact & fixing contact set of contactor capacity 100 to 200 Amp |
| 50 | S&F in replacement of moving contact & fixing contact set of contactor capacity 50 to 100 Amp |
| 51 | Replacement of terminal block of suitable size with four terminal including nuts ,bolts ,washers with all acessries and materials. |
| 52 | S & F in replacement of power contactor 4P equivalent of MCX 22 make and model as per existing inthe AMF panel all as specified and directed. |
| 53 | S & F in replacement of power contactor 4P equivalentof MCX 32 make and model as per existing in the AMF panel all as specifided and directed. |
| 54 | S & F in replacement of power contactor 4P equivalent of MCX 34make and model as per existing in the AMF panel all as specified and directed. |
| 55 | S & F in replacement of power contactor 4P equivalent of MCX 41/MCX 44 make and model as per existing in the AMF panelt all as specified and directed. |
| 56 | S & F in replacement of power contactor 4P equivalent of MCX 45 make and model as per existing in the AMF panel all as specified and directed. |
| 57 | S&F in replacement flexible fuel pipe complete set with banjo bolt and washer etc. all as per existing sample and as per directions of engineer-in-charge. Note: length of the fuel pipe should be supplied as per requiremnt at site. |
| 58 | M&L for laying, jointing, testing cable XLPE insulated, armoured and PVC sheathed LT 1100 volts grade and aluminum conductor confirming to IS 7098 laid in trenches/through pipe/floor/fixed wall etc complete all as specified and directed for size of cables 50 Sqmm 3.5 core stranded conductor |
| 59 | All as per item No 49 here-in-above but size of cable 70 Sqmm 3.5 core stranded conductor. |
| 60 | All as per item No 49 here-in-above but size of cable 120 Sqmm 3.5 core stranded conductor. |
| 61 | All as per item No 49 here-in-above but size of cable 240 Sqmm 3.5 core stranded conductor. |
| 62 | All as per item No 49 here-in-above but size of cable 300 Sqmm 3.5 core stranded conductor. |
| 63 | M&L for replace of MCCB four pole, 415 Volts, 400 Amps capacity 25 KA rating with thermal relay and as per model & make provided in existing panel board including taking out old unserviceable MCCB Make - L&T, ABB,C&S,Havells,Legrand. |
| 64 | M&L for replace of MCCB four pole, 415 Volts, 250 Amps capacity 25 KA rating with thermal relay and as per model & make provided in existing panel board including taking out old unserviceable MCCB Make - L&T, ABB,C&S,Havells,Legrand. |
| 65 | M&L for replace of MCCB four pole, 415 volt 125 Amps capacity 25 KA rating with thermal relay and as per model & make provided in existing panel board including taking out old unserviceable MCCB Make - L&T, ABB,C&S,Havells,Legrand. |
| 66 | M&L for replace of MCCB four pole, 415 volt 100 Amps capacity 25 KA rating with thermal relay and as per model & make provided in existing panel board including taking out old unserviceable MCCB Make - L&T, ABB,C&S,Havells,Legrand.. |
| 67 | M&L for replace of MCCB four pole, 415 Volts, 315 Amps capacity 25 KA rating with thermal relay and as per model & make provided in existing panel board including taking out old unserviceable MCCB Make -ABB/L&K/Havells/Schneider/Legrand/Elmeasure/C&S/Siemens |
| 68 | M&L for replace of MCCB four pole, 415 Volts, 630 Amps capacity 25 KA rating with thermal relay and as per model & make provided in existing panel board including taking out old unserviceable MCCB Make - ABB/L&K/Havells/Schneider/Legrand/Elmeasure/C&S/Siemens |
| 69 | M&L for replace of ON LOAD change over switch, 4 pole, 415 Volts,& repair assembly according to existing panel 315 Amps capacity and as per model & make provided in existing panel board including taking out old unserviceable changeover. |
| 70 | M&L for replace of ON LOAD change over switch, 4 pole, 415 Volts,& repair assembly according to existing panel 630 Amps capacity and as per model & make provided in existing panel board including taking out old unserviceable changeover. |
| 71 | M&L for replace of ON LOAD change over switch, 4 pole, 415 Volts according to existing panel 100 Amps capacity and as per model & make provided in existing panel board including taking out old unserviceable changeover |
| 72 | M&L for replace of ON LOAD change over switch, 4 pole, 415 Voltsaccording to existing panel 250 Amps capacity and as per model & make provided in existing panel board including taking out old unserviceable changeover |
| 73 | M&L for replace of ON LOAD change over switch, 4 pole, 415 Volts, 200 Amps capacity and as per model & make provided in existing panel board including taking out old unserviceable changeover |
| 74 | M&L for replace of ON LOAD change over switch, 4 pole, 415 Volts, 200 Amps capacity with sheet steel enclosure box and external operating handle all as specified and directed. |
| 75 | M&L for replace of ON LOAD change over switch, 4 pole, 415 Volts, 400 Amps capacity and as per model & make provided in existing panel board including taking out old unserviceable changeover |
| 76 | Supply and fix HRC Fuse link and with basse plate 100 amp as per existing panel board including taking out unserviceable HRC fuse in panel with fuse puller |
| 77 | Removing existing unserviceble battery and supplied and fixed lead acid battery maintenance free 12 volts 180AH |
| 78 | Removing existing unserviceble battery and supplied and fixed lead acid battery maintenance free 12 volts 150 AH |
| 79 | Removing existing unserviceble battery and supplied and fixed lead acid battery maintenance free 12 volts 100 AH |
| 80 | Supply, installation, Testing& Commissioningof out door AMF Panel board (CPRI Certified) with canopy and bypass arrangement suitable for DG set of capacity 500 KVA suitable for 415 V 3Phase, 4wire, 50 HZ AC supply system having bus bar chamber with copper bus bars (60X10mm) of coloured sleeves . The panel shall be dust vermin proof IP-65 class proctection andmade of 3.15 mm CRCA sheet and supported on 40 x 40x 6mm thick MS angle iron frame workand powder coated for weather-proofwith one coat of red oxide primer on outside surface and painted inside with two coats of red oxide primer with locking arrangement and PCC earth work etc.Panel shall include following accessories and any other electrical items required not mentioned below for effective functioning of AMF Panel shall demeed to be included in the quoated rates:-*DG AMF controller with LCD display to monitor multiple parameters, universal compatibility, button lay out with labelled terminals and self start function with all control wiring*Automatic transfer switch 800 amp four pole with auto/manual function and selectable main and standby supply Make: ABB/L&K/Havells/Schneider/Legrand/Elmeasure/C&S/Siemens*Onload change over switch 800 Amp four pole - 02 Nos*HRC fuse 800 Amp with base and connection terminals - 6 Nos*Interconnection copper busbars of size 60X 10 mm*VMR 3P 1 Nos*Relay Card 12 Volt 4CH 1 Nos*Battery Charger 12 Volt 10A 1 Nos*MCB 6-32A @ 10 Nos*LED Indicator 220 Volt qty as required*Push Button 2 Nos*VAF Meter 1 Nos*700/5 CT 3 Nos*Mode selection Switch(Auto/Manual) - 02*Control cable from DG set to AMF panel of suitable size |
| 81 | Supply, installation, Testing& Commissioningof out door AMF Panel board (CPRI Certified) with canopy and change over arrangement suitable for both DG set of capacity 380 & 200 KVA suitable for 415 V 3Phase, 4wire, 50 HZ AC supply system having bus bar chamber with copper bus barsof coloured sleeves (Current density 1.2 Amp/sqmm) . The panel shall be dust vermin proof IP-65 class proctection andmade of 3.15 mm CRCA sheet and supported on 40 x 40x 6mm thick MS angle iron frame work and powder coated for weather-proofwith one coat of red oxide primer on outside surface and painted inside with two coats of red oxide primer with locking arrangement and PCC earth work etc.Panel shall include DG AMF controller with LCD display to monitor multiple parameters, universal compatibility, button lay out with labelled terminals and self start function wityh all control wiring - 02 Nos, VMR 3P 2 Nos,Relay Card 12 Volt 4CH - 2 Nos,Battery Charger 12 Volt 10A -2 Nos,MCB 6-32A @ 20 Nos,LED indicator 220 Volt qty as required,Push Button - 4 Nos,VAF Meter -2 Nos, CT s of suitable capacities,Mode selection Switch(Auto/Manual) - 04,Control cable from DG set to AMF panel of suitable size and space for the following switchgears of Make: ABB/L&K/Havells/Schneider/Legrand/Elmeasure/ C&S/Siemens and any other electrical items required not mentioned above for effective functioning of AMF Panel and automatic start and stop of both 380 kVA and 200 kVA DG sets shall demeed to be included in the quoated rates:-*MCCB four pole 630 Amp 25 kA - 02 Nos*MCCB four pole 315 Amp 25 kA - 02 Nos*Contactorfour pole 315 amp - 02 Nos*Contactorfour pole 630 amp - 02 Nos*Onload change over switch 315 Amp four pole - 02 Nos*Onload change over switch 630 Amp four pole - 02 Nos |
| 82 | Supply, installation, Testing& Commissioningof out door Change over Panel board (CPRI Certified) with canopy suitable for 415 V 3Phase, 4wire, 50 HZ AC supply system having bus bar chamber with copper bus barsof size 40X6 mm with coloured sleeves. The panel shall be dust vermin proof IP-65 class proctection andmade of 3.15 mm CRCA sheet and supported on 40 x 40x 6mm thick MS angle iron frame work and powder coated for weather-proofwith one coat of red oxide primer on outside surface and painted inside with two coats of red oxide primer with locking arrangement and PCC earth work etc.Panel shall include,LED indicator 220 Volt qty as required, Onload change over switch 315 Amp four pole - 02 Nos all as specified and directed. |
| 83 | M&L for provision of sloped roof covered shed not less than 3.0 mtr height and covering area 5.0 mtr x 7 mtr for preventing out door installed Disel genrating set from rainfall/unwanted damage etc, shed to be fabricated out of steel structural sections, i.e.50mm dia medium grade GIpipe for vertical supports firmly grovoted two feet deep with 1:3:6 PCC work, and 50x50x5mm angle iron for horizontal supports and roof using ALuminum Sheer thickness not less than 0.5mm thickness including necessary cutting, drilling, bending hot or cold, welding, suitable size of nut, bolt, \"J\" hook and washers etc as required at site and providing PCC 1:3:6 block masonary wall 9 inch thick & 1.5 mtr heigh all around with opening for hinged type double door at front side fabricated using 50x50x5mm MS angle iron and chain link wiremesh and covering other open area of wall using chain link wire mesh using 4.0mm dia GI wire, welded with support by using 40x5 MS flat iron complete including plastering 10mm thick in 1:4 CM to exposed surface of wall all as specified and directed by Engr-in-charge. |
| 84 | M & L Earthing complete with galvanised steel earth plate electrode 60×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less\"than 1.5 metres below normal ground level, connected to galvanised strip of size 32 mm x 6 mm as earth lead, by means of bolts, buts, check nuts and washers of galvanised iron or steel, galvanized iron pipe of 40 mm diameter, connected to earthing test point,all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion , including exacavation and earth work in any type of soil PCC chamber, RCC Cover all as dircted by engineer-in-charge. GI strip of size 32mm x 6mm from Earth pit to LT Panel/ DG set is to be included in quoted rates. |
| 85 | Excavation in trenches not exc 1.5m widthand not exc1.5 min depth and getting out forlaying of pipes etc in soft/loose soil . |
| 86 | Returning filling in including spreading levelling watering and ramming in layers not exceeding 25 cm in any type of soil. |
| 87 | Removing of excavated surplus soil to a distance not exceeding50M where directed and at a level not exceeding 1.5 M above the starting point. |
| 88 | Sand cushioning for above and below the under ground cable all as specified vand directed. |
| 89 | Supplying and laying reinforced precastconcrete cable cover, Class LV, Type I, flat, size 250mm x 150mm x 40mm |
| 90 | Supply only rubber hose pipe set (Hose oil/Hose radiator/CR Hose/Makeup Hose) suitable for DG sets of capacity 63 KVA all as per existing sample with GI clamps and Nut bolt, washers for DG set as directed by Engr-in-charge. |
| 91 | Supply only rubber hose pipe set (Hose oil/Hose radiator/CR Hose/Makeup Hose) suitable for DG sets of capacity ranging from 100 KVA to 200 KVA all as per existing sample with GI clamps and Nut bolt, washers for DG set as directed by Engr-in-charge. |
| 92 | Supply only rubber hose pipe set (Hose oil/Hose radiator/CR Hose/Makeup Hose) suitable for DG sets of capacity 250 to 650 KVA and above all as per existing sample with GI clamps and Nut bolt, washers for DG set as directed by Engr-in-charge. |
| 93 | S&F in repairs Air filter element inner and outersuitable for existing type of modeleDG set Engine ofcapacity630 KVA. |
| 94 | S&F in repairs Air filter element inner and outersuitable for existing type of modeleDG set Engine ofcapacity500 KVA. |
| 95 | S&F in repairs Air filter element inner and outersuitable for existing type of modeleDG set Engine ofcapacity380 KVA. |
| 96 | S&F in repairs Air filter element suitable for existing type of modele DG set Engine ofcapacity200 KVA. |
| 97 | S&F in repairs Air filter elementinner and outersuitable for existing type of modele DG set Engine ofcapacity 125 KVA |
| 98 | S&F in repairs Air filter elementinner and outersuitable for existing type of modele DG set Engine of make Kirloskar and capacity 100 KVA. |
| 99 | S&F in repairs Air filter elementinner and outersuitable for existing type of modele DG set Engine of capacity62.5 KVA. |
| 100 | Cleaning and back purge RECDof any capacity including taking out and refixing all as specified and per directed by engineer-in -charge. |
| 101 | Supply and installation of DG AMF controller with LCD display to monitor multiple parameters, universal compatibility, button lay out with labelled terminals and self start functionincluding all control wiring and installation kit with silicone gasket for sealing and detailed installation manual for settings all as including all control wiring specified and directed. |
| 102 | Shifting of DG set capacity up to 380 KVA from one location to other location (within 7 KM ) including isolation of mechanically and electrically both in previous location and after shifting,reconnected mechanically and electrically both in other location as Engr in charge. |