| 1 | Deployment of Wireman Gr-II and khallasi for annual lights maintenanc of Park lighting as per inventory, terms and conditions attached. |
| 2 | LED Street light fixture, powder coated pressure die cast aluminum body (System lumen efficacy ≥120 <135 lm/Watt) Supplying, replacement, Testing & Commissioning of Street light LED fixture powder coated pressure die cast aluminum body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 VoltAC, freq 50/60 hz, Operating temp range -15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , P. F.≥0.95, IP- 66,IK-10, CRI >80, under voltage and over voltage protection, EMIEMC As per CISPR 15 , lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED,Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin), SDCM(Standard DeviationColor Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). 45 Watt |
| 3 | LED Flood Light, powder coated pressure die cast aluminum (System lumen efficacy ≥120 and <135 lm/Watt)Supplying,replacement, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminum body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , P. F.≥0.95, IP-66,IK-10, CRI >80 , under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle 30 deg- 120deg as per the application and the project requirement deg, suitable tilt able fitting, life time (LED,Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) , SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 and <135 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C).70 watt |
| 4 | Supplying & drawing of following size FRLS PVC insulated copper conductor, single core cable in the existing surface/recessed steel/PVC conduit as required.a)3 x 1.5 sq. mm |
| 5 | b) 3 x 2.5 sq. mm |
| 6 | c) 3 X 4 sq. mm |
| 7 | Supplying of following sizes of XLPE insulated PVC sheathed Al. cond. Armoured power cable of 1.1 KV grade including connection, testing etc. as required. a) 2C x 16 sq. mm |
| 8 | b) 4C x 25 sq. mm. |
| 9 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size direct in ground including excavation and refiling the trench but excludingsand cushioning, protective covering.a) Upto 35 sq. mm |
| 10 | Laying of one number PVC insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of following size in the existing RCC/HUME/METAL pipe as required.a)Upto 35 sq. mm |
| 11 | Supplying and making straight through joint with heat shrinkable kit including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required. i)2C x 16 sq.mm |
| 12 | ii)4C x 25 sq.mm |
| 13 | Supplying and replacement of following capacity electrical lamps and other accessories in the existing light fittingof 220V, 50Hz, single phase AC supply,on the existing 3 mtr. to 10 mtr. High poles, connection testing etc. complete as reqd. a) 40 Watt LED Lamp |
| 14 | b) 20 Watt LED Lamp |
| 15 | c) 9 Watt LED Lamp |
| 16 | Supply & replacement of pole connector box made out of Glass Reinforced Polyester Sheet Moulding Compound Conforming to IS:13410-1992 Grade S1 of outside dimensions 280 mm(H) x 170 mm(W)x 115 mm (D) (all the corners of the box should be round & not pointed ones) suitable to mount on 40/50/65 mm dia GI pole with the followingprovisions/accessories mounting in box complete as reqd.(i)2 nos. clamps made out of 19mm x 3 mm GI strip of suitable length for mounting box on the pole (if required).(ii) Water tight front cover with 2 nos. stainless steel hinges & 1 no. screw for tightening.(iii)4 way, 220 V, 30 A, dough moulded connector (SMC with stainless steel inserts) - 1 No.(iv) 16 amp. Moulded SMC rewireable kit-kat---1 no.(v) Suitable size hole at suitable location on rear wall for cable & wire entry in the connector box.(vi) Earthing bolt M6 x 20 mm |
| 17 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing , along with existing surface/recessed conduit/sub main wiring/cable as required. |
| 18 | Supplying and replacement of following items, connection, testing etc. in the existing LT panel board as reqd. a)Ammeter 0-30A, 96mm x 96 mm |
| 19 | b)Volt meter 0-500 V, 96 mm x 96 mm |
| 20 | c) 32A, AC-3, 3 pole power contactor |
| 21 | d)Analogue Time Switch, 24 hours programmable. |
| 22 | e) 100 Amp, 4 pole MCCB, 30 kA |
| 23 | f) 63 Amp, TP&N & MCB, 10 KA C-curve |
| 24 | g)32A TP & N MCB- 10KA C-Curve |
| 25 | h)6 amp to 32 amp SPMCBs C-Curve |
| 26 | i)32 amp DPMCB C-Curve |
| 27 | Digging outof 1 No. faulty PVCinsulated, PVC sheathed/ XLPE power cable laid in gound and relaying of the same after removing of the cable fault i/c refilling and redressing of the trench etc. as reqd. |
| 28 | Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required.(a) Group C |
| 29 | Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthingas required. |
| 30 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor single core cable in surface /recessed steel conduit as required. a) 2 X 1.5 sq.mm +1 X 1.5 sq.mm earth wire |
| 31 | Supplying and replacement of 20 Wattround /square profile LED batten tubelight fixture with extruded polycarbonate, as approved by engineer in charge i/c testing etc. complete as required. |
| 32 | Supply, Replacement, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal (Aluminum alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, remote (preferably mobile app based) for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Ceiling Fan compliant to IS 374:2019 fan Supply, earthing etc. complete as req.1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |
| 33 | Supply & replacement of following size exhaust fan including all accessories & making opening, making good the damage, connection, testing, commissioning etc. as required.a) 300 mm sweep |
| 34 | Supplying, Fabrication and replacement (including dismentaling if existing) of 4 mtr. high pole made out of 65 mm dia NB, B class G.I pipe ISI marked duly welded with MS base plate of size 300 mm x 300 mm x 12 mm thick with stiffner of size 130 mm x 60 mm x 5 mm thick ,supplying and fixing of suitable size of braket for mounting the light fitting on the pole,suitable earth stud on base plate ,making suitable size hole in pole at a height of 2.5 meter from base plate for cable entry/exit(as per drawing approved by Engineer-in-charge), painting & numbering of pole, making suitable size hole in base plate for cable entry/exit into the pole and fixing the pole on the existing foundation with the existing nuts-bolts, washers etc. complete as required. |
| 35 | Providing and laying in position 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate)reinforced cement concrete foundation of size450 mm x 450 mm x 1200 mm deep (800 mm below ground level and 400 mm above ground level) including excavation of earth, refilling, providing, cutting, bending and placing in position, reinforcement of cold twisted bars of 12mm. dia-1200mm long (approx) -8Nos, and reinforcement ring of cold twisted bar of 8mm dia -1400mm long (approx) -6 nos, (with suitable spacing) including centering & shuttering as required with providing, fixing and positioning of one set of foundation bolts comprising of 4 nos., 16 mm dia, 750 mm long J-Type MS bolts (Threaded portion shall be galvanized) along with 3 nos. GI nuts and 2 nos. GI washers etc. per bolt and 1 no. anchor plate (3mm thick) of suitable size and providing 63 mm.(O.D) DWC pipe ISI marked for cable entry & exit etc. complete as required. |
| 36 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 37 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 38 | Painting and numbering (2 coating) of existing G.I. pole of upto 4 /5mtr. hight including painting of base plate & mounting arrangement etc. complete as reqd. |
| 39 | Supplying, Replacement (Dismantling the existing feeder pillar), testing and commissioning of floor mounted LT feeder pillar cubical type double door of size1000 mm x 900mm x 300 mm deep duly compartmentalized and with general arrangement made out of 2mm thick CRCA sheet having hinged gasket cover and screwed knobs with double locking arrangement and rain protection covers 100 mm and supported withMS angle iron legs and bottom frame of size 35mm x 35mm x 5mm x 1mtr. long grouted with 1:3:6 CC foundation and should be 0.7 mtr. above ground level. Legs should be covered with brick walls, connections, inter connections with suitable size of FRLS PVC insulated copper conductor using thimbles wherever required, painting, numbering including supply and fixing of following accessories complete etc. as required (as per drawing approved by Engineer-in-charge) .(a)63 Amps. Four Pole MCB (\"C\"-Series), 10kA----1 No.(b)16 Amps. SP MCB (\"C\"-Series), 10 kA------ 6Nos(c) Analogue Timer switch for daily operation and toggle switch forauto/manual --1 No. (d) 32 Amps. AC-3, 3 pole power contactor -----1 No. (e) 30 Ampere 4 way neutral link/connector ------2 Nos. (f) Voltmeter(0-500 Volt) 96mm X 96mm square type with selector switch---1 No (g) Phase Indicating Lamp Set with fuses ----1 Set (h) Danger notice plate -----1 No (i) AI. Bus Bar 100 amp. 4 strip, 300 mm long with sleeve and nut bolts-----1 Set.(j)Ammeter (0-30Amp) 96mm X 96mm square type ----1No.(k)Lifting hook on the top of panel board and lighting arrangement inside the feeder pillar---- 1 No. |
| 40 | Supplying, Fabrication, replacement and Installation of wire mesh protection frame for existing feeder pillar made out of 8 SWG M.S wire mesh size (75mmX25mm rectangle nominal) of following size with M.S angle iron base frame 35mm X 35mm X 5mm angle iron and with M.S strip support of size 35mm X 5mm in cross and 0.5mtr long legs support of same angle (as per drawing attached), i/c door in front portion, supplying and fitting of go down lock i/c locking arrangement, painting and grouting of angle iron frame with lugs in CC 1:3:6 foundation etc. as approved by Engineer incharge etc. complete as regd.(a) 2 mtr (H) X 1.5 mtr (W) X 1.0 mtr (D) |
| 41 | Painting of existing wire mesh protection frame/ feeder pillar of different size with 2 Nos of enamel paint coating incuding primer,cleaning etc. complet as required. |
| 42 | Dismantling of existing damaged panel foundation & re-casting the same including brick, mortar, cement plaster etc. complete as required. |
| 43 | Repairing of existing wiremesh protection frame including supplying & fixing of 8 SWG M.S. wiremesh (of size 75mm x 25mm) with M.S. angle iron base frame (of size 35mm x 35 mm x 5 mm), cutting, welding, painting, making locking arrangement etc. complete as reqd. |