| 1 | Supply & installation of Flameproof weatherproof (IP66) Control panel as per IS/IEC 60079-0:2017, enclosure size 2000(H) x 600(W) x 300 (D) mm, as per IEC 60079-1:2014, suitable for Gas Group IIA, IIB, EPL Gb & Db (Ex\"D), Temp Class T6, made of cast aluminium alloy LM6, wall mounted, with 1 No incomer MCCB 4P 250A, 25 KA and outgoing MCCBs 4P 160A-25KA No-01, 125A-25KA No- 01, 100A-18KA No-01 with extended rotary handle, copper busbar 25x10mm with wiring and terminals, switchgears Category Part No : SSPL/110 Make : Shyaam Switchgears/ Baliga/CG/Flexpro Electricals/Bajaj certified by CIMFR Dhanbad & PESO Nagpur complete all as specified and directed by Engineer-in-Charge. |
| 2 | Supply & installation of Flameproof weatherproof (IP66) Control panel as per IS/IEC 60079-0:2017, enclosure size 600(H) x 455(W) x 300 (D) mm, as per IEC 60079-1:2014, suitable for Gas Group IIA, IIB, EPL Gb & Db (Ex\"D), Temp Class T6, made of cast aluminium alloy LM6, wall mounted, with 1 No MCCB 4Pole 160Amp, 25 KA with extended rotary handle with wiring and terminals, switchgears Category Part No : SSPL/110 Make : Shyaam Switchgears/ Baliga/CG/Flexpro Electricals/Bajaj certified by CIMFR Dhanbad & PESO Nagpur complete all as specified and directed by Engineer-in-Charge. |
| 3 | Supply and fix PVC FRLS Armoured Copper cable of 1.5 sqmm x 3 core including saddling on wall / surface at any height complete all as specified and as directed. |
| 4 | Supply and fixPVC FRLS Armoured Copper cable of 4 sqmm x 4 core including saddling on wall / surface at any height complete all as specified and as directed. |
| 5 | Supply and fixPVC FRLS Armoured Copper cable of 2.5 sqmm x 3 core including saddling on wall / surface at any height complete all as specified and as directed. |
| 6 | Supply and fix flameproof switch of LM-6 body, rotary switch, SP, 16 Amps for ON / OFF light / fan point to operate on single phase 230 Volts, AC CMRIcertified, ISI-2145 marked complete all as specified and directed by Engineer-in-charge |
| 7 | Material and labour for flameproof switch socket combination suitable for 2P+E 16 Amps, 250 volts including plug and top, LM-6 body, CMRI certified, ISI marked complete all as specified and directed by Engineer-in-charge. |
| 8 | Supply and fixingflameproof switch socket combination 4P+E with MCB TPN 32 Amps, \"C\" curve, 500 volts including plug and top, LM-6 body, CMRI certified, ISI marked complete all as specified and directed by Engineer-in-charge. |
| 9 | Supply, installation, testing and commissioning of online water analyser to test & monitor water parameters like pH/ORP/TDS/TSS/ Conductivity and data logger with sim with following specification.InputsOne pH/ORP inputOne dissolved Oxygen inputTwo 4-20 mA inputs, 2-wire or 4-wire (15V DC galvanically isolated source, 50Ma maximum) for analogic probes (dissolved oxygen, chlorine turbidity)OutputsTwo 4-20mA outputs (Load of 500 Ohm maximum)CommunicationRS232 MODBUS or HTP/Web interfaceRS485 port for MODBUS communicationRS485 for 4 digit probes (dissolved oxygen, turbidity pH, ORP) USBOptional Wi-Fi and Ethernet interface.Memory - 288 lines of measurements (upto 16 channels) with time.Power Supply - 90-265 VAC 47/63 Hz or 24V DC 0.5 A Maximum protection for peak curren 8/20Touch Screen - Colour TFT LCD 480x272 pixels with LED back light.Certification - CE, EN 61010=1, EN 61326Enclosure - IP65, Aluminium with epoxy coating for wall mounting with optional pipe mounting brackets.Dimensions - 140 x 140 x 91 mmWeight - 2 Kg |
| 10 | Supply, installation, testing and commissioning of sensors to online water analyser with following specification.ORP SensorORP Range : -2000 to +2000 MvSensor type - Convertible style combination ORP sensorBody material - RytonSensing Element - PlatinumReference - Double Junction wohoros TeflonMounting - Imersion or In-LineOperating temperature Range 0-80˚ CMaximum operating pressure - 100 psiIntegral Sensor cable length - 6 meterMounting thread on sensor body - 3/4\" NPT threads, front & backpH SensorpH Range - 0-14Response time - 5 seconds to 95% of full responsepH Sensor type - Convertible style combination pH sensorBody Material - RytonReference - Double Junction with porous TeflonMounting - Imersion or In-LineOperating temperature Range 0-80˚ CMaximum operating pressure - 100 psiTemperature element - Pt-100 Ohm RTDTemperature compensation - AutomaticIntegral Sensor cable length - 6 meterMounting thread on sensor body - 3/4\" NPT threads, front & back |
| 11 | TDS SensorBody material - PolypropyleneMounting - In-Line (flow through)Operating temperature Range 0-80˚ CMaximum operating pressure - 100 psiTemperature element - Pt-100 Ohm RTDTemperature compensation - AutomaticIntegral Sensor cable length - 6 meterMounting thread on sensor body - 3/4\" NPT threads, front & backConductivity online electrode -6 meters cableELCOND-1 - Range 0-20ms, Cell constant k=1.0cm-1 (medium range) built-in ATC RTD 100 OhmELCOND-0.01 - Range 0-200us, Cell constant k=1.0cm-1 (very low range) built-in ATC RTD 100 OhmELCOND-0.1 - Range 0-200us, Cell constant k=1.0cm-1 (low range) built-in ATC RTD 100 OhmELCOND-10 - Range 0-200ms, Cell constant k=1.0cm-1 (high range) built-in ATC RTD 100 OhmICOND -Inductive conductivity online probe, Range 0-100ms, 3 meters cableTSS SensorMeasuring range - 0-1500 mg/L.Measurement High range - 250-30000 mg/LAccuracy low range sensor - 5% of reading or 5mg/L whichever is higherAccuracy hihg range sensor - 5% or reading or 50 mg/L whichever is higherStability 2% of readingRepeatability - 2% of readingWorking temperature range 0-60˚CMeasurement Technique - IR light absorptionResponse time - 60 second to 90% (T-90)Wetted material - Epoxy, Polyurethane and PVC |
| 12 | Supply, install, testing and commissioning of LT Panel BoardCPRI approved cubical with KIOSK type made of 3.15 mm thick outdoor type with IP 65 grade of protection dustproof and vermin proof with ingress protection CRCA sheet, powder coated, with support of 50mm x 50mm x 6mm angle iron bottom frame with double hinged rear openable shutters of each feeder control unit with locking arrangement in front and back openable inspection doors PVC sleeved aluminium bus bar of capacity 600 Amps-4 Nos, for each phases and neutral fixed on suitable insulator all housed in suitable bus bar chamber and provision and fixing of digital Voltmeter,Ammeter with built in selector switch, CTs of suitable ratio, and pilot indication lamps complete along with provision of necessary cable entry / exit boxes for all incoming and out going cables with suitable cable glands etc fixed on suitable PCC foundations complete testing and commissioning complete all as specified and directed and shall be consisting the following :-(i) Incomer: (a) MCCB 4 pole thermal / magnetic setting, 400 amps, 415 Volts 25 KA - 01 No(b) Bus bar chamber with electrolytic aluminium bus bar suitable for 600 Amps capacity for 3 phase and neutral (all connection inside the panel shall be through aluminium strip) connected duly supported with FRP insulators including colour code heat shrinked insulating sleeves. (ii) Outgoing:(a) MCCB 4 pole 200 Amps, 415 Volts 36 KA-01 No(b) MCCB 4 pole 125 Amps, 415 Volts 36 KA-06 Nos(c) Panel mounted type digital multifunctional energy meter A, V, Z, KW, PF, CT operated, LT 3 phase, 4 wire - 01 No(d) LED type indicating lamp for phases and neutral.Note : All MCCB having spreader links with direct Rotary handles. |
| 13 | Supply, install, testing and commissioning in repair of LT Panel BoardCPRI approved cubical with KIOSK type made of 2.0 mm thick indoor typewith IP 65 grade of protection dustproof and vermin proof with ingress protection CRCA sheet, powder coated, with support of 50mm x 50mm x 6mmangle iron bottom frame with double hinged rear openable shutters of each feeder control unit with locking arrangement in front and back openable inspection doors PVC sleeved aluminium bus bar of capacity 1000 Amps-4 Nos, for each phases and neutral fixed on suitable insulator all housed in suitable bus bar chamber and provision and fixing of digital Voltmeter, Ammeter with built in selector switch, CTs of suitable ratio, and pilot indication lamps completealong with provision of necessary cable entry / exit boxes for all incoming and out going cables with suitable cable glands etc fixed on suitable PCC foundations complete testing and commissioning complete all as specified and directed and shall be consisting the following :-(i) Incomer: (a) MCCB 4 pole thermal / magnetic setting, 630 amps, 415 Volts 50 KA - 01 No(b) Bus bar chamber with electrolytic aluminium bus bar suitable for 600 Amps capacity for 3 phase and neutral (all connection inside the panel shall be through aluminium strip) connected duly supported with FRP insulators including colour code heat shrieked insulating sleeves. (ii) Outgoing:(a) MCCB 4 pole 250 Amps, 415 Volts 36 KA-02 No(b) MCCB 4 pole 100 Amps, 415 Volts 25 KA-04 Nos(c) Panel mounted type digital multifunctional energy meter A, V, Z, KW, PF, CT operated, LT 3 phase, 4 wire - 01 No(d) LED type indicating lamp for phases and neutral.Note : All MCCB having spreader links with direct Rotary handles. |
| 14 | Supply, install, testing and commissioningof LT Panel BoardCPRI approved cubical with KIOSK type made of 3.15 mm thick outdoor typewith IP 65 grade of protection dustproof and vermin proof with ingress protection CRCA sheet, powder coated, with support of 50mm x 50mm x 6mmangle iron bottom frame with double hinged rear openable shutters of each feeder control unit with locking arrangement in front and back openable inspection doors PVC sleeved aluminium bus bar of capacity 400 amps-4 Nos, for each phases and neutral fixed on suitable insulator all housed in suitable bus bar chamber and provision and fixing of digital Voltmeter, Ammeter with built in selector switch, CTs of suitable ratio, and pilot indication lamps completealong with provision of necessary cable entry / exit boxes for all incoming and out going cables with suitable cable glands etc fixed on suitable PCC foundations complete testing and commissioning complete all as specified and directed and shall be consisting the following :-(i) Incomer: (a) MCCB 4 pole 250 amps, 415 Volts 25 KA - 01 No(b) Bus bar chamber with electrolytic aluminium bus bar suitable for 400 Amps capacity for 3 phase and 01 neutral (all connection inside the panel shall be through aluminium strip) connected duly supported with FRP insulators including colour code heat shrinked insulating sleeves. (ii) Outgoing:(a) MCCB 4 pole 125 Amps, 415 Volts 25 KA-03 No(b) MCCB 4 pole 100 Amps, 415 Volts 25 KA-02 Nos(c) MCB 4 pole 63 Amp, 415 Volts 10 KA - 02 Nos(d) MCB SPN 32 Amps, 220 Volts, 15 KA -02 Nos(e) Panel mounted type digital multifunctional energy meter A, V, Z, KW, PF, CT operated, LT 3 phase, 4 wire - 01 No(f) LED type indicating lamp for phases and neutral. |
| 15 | Material and labour for earthing with galvanised steel earth plate electrode 600 x 600 x 6 mm thick buried directly in ground earth pit not less than 2.25 Metre deep below ground level with top edge of the plate not less than 1.5 Metre below normal ground level connected to galvanised wire 4mm dia by means of nuts, bolts, check nuts, washers of galvanised iron or steel all as shown in electrical plate No. 03 of SSR Part I connected to earthing test point including excavation / earth work in any type of strata, removal of surplus excavated material, GI pipe for watering and funnel, PCC 1:3:6 type C1 chamber including necessary formwork / mould for fair and even surfaces, precast RCC 1:2:4 type B0 chamber cover slab, GI funnel, with GI watering pipe 20 mm bore medium graded, wire mesh, protection pipe 40 mm bore, charcoal and salt, GI pipe light grade for earth lead upto 7.50 metre long including testing complete all as specified and directed by Engineer-in-Charge.Note : (i)GI strip beyond 7.5 metre will be measured and paid sepeartely.(ii)Test report shall be prepared and submitted by the contractor in triplicate duly obtaining signatures of MES JE / AGE & PMG / user.Test results are to be written in letters of 20mm height in white colour on black paint back ground. (iii) The earth resistance should be less than 3 Ohm.(iv) If the test result of earth resistance not obtained below 2 Ohms the contractor shall improve the earth resistance with own arrangement no extra payment will be paid by the department. |