| 1 | Excavation in trenches in soft/loose soil not exceeding1.5 meter wide and not exceeding 1.5 meter deep for laying of cable, pole foundation, etc including taking out old brick cable protection cover and getting out forming bottom surface to required gradient complete all as specified and directed. |
| 2 | Returning, filling in, earth including spreading, leveling watering and well ramming in layers each not exceeding 25cm thick each layer, complete all as specified and directed. |
| 3 | Removal of surplus soil to a distance not exc. 50 meter and depositing where directed at a level not exc. 1.5 meter above the starting point complete all as specified and directed. |
| 4 | Supply and laying well burnt old size sub class \"B\" bricks laid in trenches for cable protection. all as specified and directed. |
| 5 | M & L for Dry and clean fine sand for cable cushioningto underground cable protection, complete all as specified and directed. (Excavation and earth work measuredseparately). Note- Punned down thickness shall be measured. |
| 6 | Dismantling and taking down old wornt outACSR conductor of any type and size complete all as specified and directed. |
| 7 | Dismantling & taking down old wornt outMS clamps/crossarms/channels complete with nuts & bolts etc complete all as specified and directed. |
| 8 | Dismantling and taking down old U/S insulators of any type and size complete all asspecified anddirected. |
| 9 | Dismantling and taking down old U/S Service wire of any type and size complete all asspecified anddirected. |
| 10 | Dismantling and taking down old U/S LT cable of size 16 Sqmm 4 core complete all asspecified anddirected. |
| 11 | Dismantling and taking down old U/S LT cable of size 25/35 Sqmm 3.5 core complete all asspecified anddirected. |
| 12 | Supply & fixingstreet light pole cable junction box IP-65 with box size of 200x160x98 with 4 Nos of terminal block, 1 Nos of earth terminal metnic knockoutsforcable entryand the box made out of thermal plastic material suitable for 16/25 UG sqmm cable including clamps bolts, nutsduly painted and MCB SP 6 Amp etc. complete all as specified & directed. |
| 13 | Supply & fixing 3 core 1.5 sqmm PVC insulated and FR PVC round sheathed copper conductor flexible 1100 voltsfor connection from Junction Box to street light fittings including clamps for FR PVC wire as specified & directed. |
| 14 | S&F cableXLPE insulated, armoured heavy duty electric cable withaluminium conductor, 1100 volts grade, cross-sectional area 16 sqmm 4 core, complete all as specified and directed. |
| 15 | Supplying, laying and connecting XLPE insulated and sheathed armoured 1100 volts grade heavy duty electric cable with multistranded aluminium conductor laid in trenches/duct through pipe, in floor on poles in and including aluminium thimble or aluminium line tape of size 185 sq mm 3.5 core nominalcross section area complete all as specifiedMake : Hevells, PolyCab and Finolex. |
| 16 | All as per item No 15 here-in-before but size 240 sq mm 3.5 core, complete all as specified and directed. |
| 17 | All as per item No 15 here-in-before but size 70 sq mm 3.5 core, complete all as specified and directed. |
| 18 | All as per item No 15 here-in-before but size 50 sq mm 3.5 core,complete all as specified and directed. |
| 19 | All as per item No 15 here-in-before but size 35 sq mm 3.5 core, complete all as specified and directed. |
| 20 | All as per item No 15 here-in-before but size 25 sq mm 3.5 core, complete all as specified and directed. |
| 21 | Supply and fixing GI Bracket for street light fitting bend to shape made out of GI pipe light grade 40mm bore upto1.2 mtr longetc complete with two sets of MS flat clamps of size 40 x 5 mm duly painted with two coat of aluminum paint with nuts/ bolts/ washers for fixing arrangement to pole /wall all as specified and directed.. |
| 22 | Supply & fixing galvanised iron pipe light grade ISI marked 100 mm bore for passing of cable, fixed to poles/ walls/ laid under floor complete with and including fittings complete all as specified and directed. |
| 23 | Material & labour for boring hole under the road/payment/ hard standing upto 100 mm Bore Pipenot less than one metre below ground level complete all as specified and directed. |
| 24 | Material & labour for boring hole under the road/payment/ hard standing upto 50/80 mm Bore Pipenot less than one metre below ground level complete all as specified and directed. |
| 25 | Supply & fixing galvanised iron pipe light grade ISI marked 50 mm bore for passing of cable, fixed to poles/ walls/ laid under floor complete with and including fittings complete all as specified and directed. |
| 26 | Supply and fixing GI pipe light grade 40mm dia upto 1.5 Mtr from surface to junction box with all fittings for cable protection, complete all as specified and directed. |
| 27 | Supply, installation, testing and commissioning in replacement of CPRI approved, factory made, LT panel board cubical, Outdoor type, floor mounted double door, Front & Rear openable with locking arrangement, suitable for AC,3 phase, 4 wire, 50 cycles, 415 Volts. The panel board shall be made of 3.15 thick CRCA/MS sheet (Min size 2.0 m x 1.6 m x 0.8 m ) with Powder coated.The panel have to provide proper compartment as per IS specification and wiring of panel with suitable size of copper conductor FRLS cable not less than 2.5 Sqmm with thimbles all as directed.Base frame of the panel shall bemade of angle iron of size 50 x50 x 6mm of upto 1/2 mtr hight from GL& 1/2 mtr for Below GL including PCC (1:3:6) type C-2 using 40 mm stone aggregatescomprising of following:- LOC:- Propose MainLT Panel (Back side Store-1&2) Contd...27.01/- |
| 28 | (i) Panel having common aluminium bus bar of capacity 630 Amp TPN each and suitable capacity TPN bus bar for outgoing MCCB\"s, including aluminium lugs to connect the cable and cable gland for Each cable entry as per cable size.(ii) Incoming:-(a)MCCB adjustable thermal and adjustable magnetic setting with overload short circuit and earth fault protection ofcapacity, 350 Amps, 4 Pole ICS=100% ICU , 36 KA with overload variation 80-100% (Incoming)(iii) Outgoing:-(a)MCCB Thermal release based adjustable type with suitable size and capacity,200 Amp 4 Pole ICU = ICS = 36 KA with overload variation 40-100%- 01 Nos.(outgoing)(b)Same as above but of Capacity 125 Amps, 4 Pole 36 KA -02 Nos (outgoing)(c)Same as above but of Capacity 63 Amps, 4 Pole 16 KA -02 Nos (outgoing)(d) MCB 32 Amp SPN -01 Nos (outgoing)(iv) Volt Meter 0 - 500 Volts digital type square shapeflush mounted with selector switch - 1 Set(v) Ammeter 0 - 630 Amps digital type square shape 96mm flush mounted with selector switch and CT\"s 630/5 A - 1 Nos Set.(vi) Indicator lamp RYB :01 Set. with CT Coil complete. |
| 29 | Supply , installation, testing and commissioning factory made LT bus bar panel board cubical, out door type, floor mounted double door, 3 phasse 4 wire, 50 cycles, 415 volts IP- 65 the panel board shall be made of 3.15 mm thick CRCA sheet for load bearing members shall be powder coated both side. Base frame of the panel shall be made of ICMC channel of size 50x50x6 mm, duly grouted on PCC plareform of size (0.8mx0.8m) made of brick work in CM (1:4), including 15 mm thick plastering in CM (1:6) having minimum height of 600mm including digital type ampere meter (0-400 Amp) and volt meter(0-500 volts). The panel board shall be ssuitable for AC, 415 Volts, 50 Hz, 3 phase, 4 wire supply complete with and comprising of the following :-(i) Epoxy insulated 400 Amps rated high conductivity aluminium bas bar including aluminium lugs to conect the cable.(ii) MCCB 4 Pole, 415 V, Adjustable type, 63 Amps with breaking capacity 25 KA-01 No (For main Incomming) |
| 30 | Supply, installation, testing and commissioning in replacement of CPRI approved, factory made, LT panel board cubical, Outdoor type, floor mounted double door, Front & Rear openable with locking arrangement, suitable for AC,3 phase, 4 wire, 50 cycles, 415 Volts. The panel board shall be made of 3.15 thick CRCA/MS sheet (Min size 2.0 m x 1.6 m x 0.8 m ) with Powder coated.The panel have to provide proper compartment as per IS specification and wiring of panel with suitable size of copper conductor FRLS cable not less than 2.5 Sqmm with thimbles all as directed.Base frame of the panel shall bemade of angle iron of size 50 x50 x 6mm of upto 1/2 mtr hight from GL& 1/2 mtr for Below GL including PCC (1:3:6) type C-2 using 40 mm stone aggregatescomprising of following:- LOC:- Back side of Adm Block. Contd...29.01/- |
| 31 | (i) Panel having common aluminium bus bar of capacity 400 Amp TPN each and suitable capacity TPN bus bar for outgoing MCCB\"s, including aluminium lugs to connect the cable and cable gland for Each cable entry as per cable size.(ii) Incoming:-(a)MCCB adjustable thermal and adjustable magnetic setting with overload short circuit and earth fault protection ofcapacity, 315 Amps, 4 Pole ICS=100% ICU , 36 KA with overload variation 80-100% (Incoming)(iii) Outgoing:-(a)MCCB Thermal release based adjustable type with suitable size and capacity,100 Amp 4 Pole ICU = ICS = 36 KA with overload variation 40-100%- 01 Nos.(outgoing)(b)Same as above but of Capacity 63 Amps, 4 Pole 25 KA -03 Nos (outgoing)(d) MCB 32 Amp SPN -02 Nos (outgoing)(iv) Volt Meter 0 - 500 Volts digital type square shapeflush mounted with selector switch - 1 Set(v) Ammeter 0 - 630 Amps digital type square shape 96mm flush mounted with selector switch and CT\"s 630/5 A - 1 Nos Set.(vi) Indicator lamp RYB :01 Set. with CT Coil complete. |
| 32 | Supply, installation, testing and commissioning in replacement of CPRI approved, factory made, LT panel board cubical, Outdoor type, floor mounted double door, Front & Rear openable with locking arrangement, suitable for AC,3 phase, 4 wire, 50 cycles, 415 Volts. The panel board shall be made of 3.15 thick CRCA/MS sheet (Min size 2.0 m x 1.6 m x 0.8 m ) with Powder coated.The panel have to provide proper compartment as per IS specification and wiring of panel with suitable size of copper conductor FRLS cable not less than 2.5 Sqmm with thimbles all as directed.Base frame of the panel shall bemade of angle iron of size 50 x50 x 6mm of upto 1/2 mtr hight from GL& 1/2 mtr for Below GL including PCC (1:3:6) type C-2 using 40 mm stone aggregatescomprising of following:-LOC:- (TSP Back Side)Contd...30.01/- |
| 33 | (i) Panel having common aluminium bus bar of capacity 400 Amp TPN each and suitable capacity TPN bus bar for outgoing MCCB\"s,including aluminium lugs to connect the cable and cable gland for Each cable entry as per cable size.(ii) Incoming:-(a)MCCB adjustable thermal and adjustable magnetic setting with overload short circuit and earth fault protection ofcapacity,200 Amps, 4 Pole ICS=100% ICU , 36 KA with overload variation 80-100% (Incoming)(iii) Outgoing:-(a)MCCB Thermal release based adjustable type with suitable size and capacity,63 Amp 4 Pole ICU = ICS = 25 KA with overload variation 40-100%- 04 Nos.(outgoing)(b)MCB 32 Amp SPN -02 Nos (outgoing)(iv) Volt Meter 0 - 500 Volts digital type square shapeflush mounted with selector switch - 1 Set(v) Ammeter 0 - 630 Amps digital type square shape 96mm flush mounted with selector switch and CT\"s 630/5 A - 1 Nos Set.(vi) Indicator lamp RYB :01 Set. with CT Coil complete. |
| 34 | Supply, installation, testing and commissioning in replacement of CPRI approved, factory made, LT panel board cubical, Outdoor type, floor mounted double door, Front & Rear openable with locking arrangement, suitable for AC,3 phase, 4 wire, 50 cycles, 415 Volts. The panel board shall be made of 3.15 thick CRCA/MS sheet (Min size 2.0 m x 1.6 m x 0.8 m ) with Powder coated.The panel have to provide proper compartment as per IS specification and wiring of panel with suitable size of copper conductor FRLS cable not less than 2.5 Sqmm with thimbles all as directed.Base frame of the panel shall bemade of angle iron of size 50 x50 x 6mm of upto 1/2 mtr hight from GL& 1/2 mtr for Below GL including PCC (1:3:6) type C-2 using 40 mm stone aggregatescomprising of following:- LOC:- (Wet Canteen back side).Contd...31.01/- |
| 35 | (i) Panel having common aluminium bus bar of capacity 400 Amp TPN each and suitable capacity TPN bus bar for outgoing MCCB\"s,including aluminium lugs to connect the cable and cable gland for Each cable entry as per cable size.(ii) Incoming:-(a)MCCB adjustable thermal and adjustable magnetic setting with overload short circuit and earth fault protection ofcapacity, 200 Amps, 4 Pole ICS=100% ICU , 36 KA with overload variation 80-100% (Incoming)(iii) Outgoing:-(a)MCCB Thermal release based adjustable type with suitable size and capacity,63 Amp 4 Pole ICU = ICS = 36 KA with overload variation 40-100%- 04 Nos.(outgoing)(b)MCB 32 Amp SPN -02 Nos (outgoing).(iv) Volt Meter 0 - 500 Volts digital type square shapeflush mounted with selector switch - 1 Set(v) Ammeter 0 - 630 Amps digital type square shape 96mm flush mounted with selector switch and CT\"s 630/5 A - 1 Nos Set.(vi) Indicator lamp RYB :01 Set. with CT Coil complete. |
| 36 | M & L for Earthing complete with galvanized steel plate electrode of size60 cm x 60cm x 6.3 mm thick buried directly in ground vertically to a depth not less than 2.5 mtr below the ground level with top edge of earth plate at a depth not less than 1.5 mtr below ground level. Earth plate surrounded by 15mm thick packed alternative layers of charcoal dust and comman salt, galvanised ironstrip 32 × 6mm by means of bolts , nuts, check nuts and washers of galvanised iron with thimbles. The other end of GI earth wire is connected to main switch board and protected by light grade GI pipe of 15 mm bore. provision of 20mm bore light grade GI pipe for watering including GI funnel and wire mesh. Pipe shall be provided vertically upto top level of earth pit and then taken horizontally to the earth pit. Cement concrete chamber of PCC ( 1:3:6 ) type C-2using 40 mm graded stone aggregate. |